Download Instruction Manual
Transcript
Instruction Manual Detailed Setup August 2012 D103409X012 will be a minimum value. For those actuators that fill from the test starting point, the pressure limit will be a maximum value. The pressure signal used for this threshold depends on relay type and is summarized below. Relay Type A or C B B Special App. C Special App. Pressure Signal Port A - Port B Port B - Port A Port B Port A PST Press Limit (double-acting actuators)— During the Setup Wizard or Auto Calibration, the Partial Stroke Pressure Limit value will be set to a negative value for actuators where the Partial Stroke Start Point is opposite of the Zero Power Condition (e.g., Partial Stroke Start Point= Open and Zero Power Condition = Closed) and to a positive valve for actuators where the Partial Stroke Start Point is the same as the Zero Power Condition. To set the partial stroke pressure limit manually for single acting actuators select min pressure. Select min diff press for double acting actuators. Note In order to manually set the partial stroke pressure limit with the correct value, you must be able to run a valve signature test using ValveLink software. It is then possible to set the partial stroke pressure limit with the Field Communicator, using the information generated by the valve signature test. To manually set the partial stroke pressure limit, disable the travel deviation alert by setting Travel Dev Alert Pt to 125%. Also disable “end point pressure control” and disable the partial stroke pressure limit by setting the values shown in table 4‐9. Table 4‐9. Values for Disabling Partial Stroke Pressure Limit Actuator Type Relay Type Zero Power Condition Closed A or C Open Single Acting Closed B Open Closed Double Acting A Open Partial Stroke Start Point Partial Stroke Pressure Limit (Disabled) Open 0.0 Closed Psupply Open Psupply Closed 0.0 Open Psupply Closed 0.0 Open 0.0 Closed Psupply Open -Psupply Closed Psupply Open Psupply Closed -Psupply Run the partial stroke test using the Field Communicator. Once the test is completed download the partial stroke test results using ValveLink software. Select the Press/Time radio button from the partial stroke valve signature graph. If actuator pressure starts high and moves low, find the minimum actuator pressure, Pmin. Otherwise, find the maximum actuator pressure, Pmax. Use table 4‐10 to estimate the partial stroke pressure limit. The default value is 0. 74