Chapter 8: PID Loop Operation
To change the bias (operating point), ladder logic only has to write the desired value to V+04.
The PID loop calculation first reads the bias value from V+04 and modifies the value based
on the current integrator calculation. Then it writes the result back to location V+04. This
arrangement creates a sort of “transparent” bias term. All you have to do to implement feed
forward control is write the correct value to the bias term at the right time (see the following
example).
NOTE: When writing the bias term, one must be careful to design ladder logic to write the value only
once, at the moment when the new bias operating point is to occur. If ladder logic writes the bias
value on every scan, the loop’s integrator is effectively disabled.
Feedforward Example
How do we know when to write to the bias term, and what value to write? Suppose we have
an oven temperature control loop, and we have already tuned the loop for optimal
performance. Refer to the figure below. We notice that when the operator opens the oven
door, the temperature sags a bit while the loop bias adjusts to the heat loss. Then when the
door closes, the temperature rises above the SP until the loop adjusts again. Feedforward
control can help diminish this effect.
Oven Closed
door
Open
PV
PV sags
Closed
PV excess
Bias
First, we record the amount of bias change the loop controller generates when the door opens
or closes. Then, we write a ladder program to monitor the position of an oven door limit
switch. When the door opens, our ladder program reads the current bias value from V+04,
adds the desired change amount, and writes it back to V+04. When the door closes, we
duplicate the procedure, but subtracting desired change amount instead. The following figure
shows the results.
Oven Closed
door
Open
Closed
PV
Feed-forward
Feed-forward
Bias
The step changes in the bias are the result of our two feed-forward writes to the bias term. We
can see the PV variations are greatly reduced. The same technique may be applied for changes
in setpoint.