Download PowerLogic Series 800 Power Meter
Transcript
PowerLogic® Series 800 Power Meter Chapter 8—Logging 63230-500-225A1 6/2006 CHAPTER 8—LOGGING Introduction This chapter briefly describes the following logs of the power meter: • • • • Alarm log Maintenance log Billing log User-defined data logs See the table below for a summary of logs supported by each power meter model. Table 8–1: Number of logs supported by model Number of Logs Per Model Log Type PM820 PM850 PM870 Alarm Log 1 1 1 Maintenance Log 1 1 1 Billing Log 1 1 1 Data Log 1 1 1 1 Data Log 2 — 1 1 Data Log 3 — 1 1 Logs are files stored in the nonvolatile memory of the power meter and are referred to as “onboard logs.” The amount of memory available depends on the model (see Table 8–2). Data and billing log files are preconfigured at the factory. You can accept the preconfigured logs or change them to meet your specific needs. Use SMS to set up and view all the logs. See the SMS online Help for information about working with the power meter’s onboard logs. Table 8–2: Available Memory for Onboard Logs Power Meter Model Total Memory Available PM820 80 KB PM850 800 KB PM870 800 KB Waveform captures are stored in the power meter’s memory, but they are not considered logs (see Chapter 9—Waveform Capture on page105). Refer to “Memory Allocation for Log Files” for information about memory allocation in the power meter. © 2006 Schneider Electric. All Rights Reserved. 95