Download Catalogue
Transcript
MASTERGUARD Series C UPS Systems from 10 to 60 kVA 12. Special Versions 12.2 LAM-version Series C – LAM includes two internal transformers for isolation and voltage adaptation from 400V to 208/220V phase to phase. DESCRIPTION These transformers are installed in place of batteries (10-40 kVA): the one on the input (isolation transformer) allows full galvanic isolation and voltage adaptation (208/220 primary side, 400V secondary side), the one Unit kVA on the output (auto-transformer) allows voltage adaptation (400V primary side, 208/220V secondary side). Technical data will change accordingly to the following table. UPS power rating 10 15 20 30 40 50 60 Electrical data INPUT OUTPUT Voltage Vrms Current (single phase) Arms Frequency Hz Power rating Voltage 208/220V, 3Ø (+N), + 15%, (-30% with derating) 33 50 66 kVA 10 15 20 kW 8 12 16 Arms Frequency Hz Wave form - 132 165 198 30 40 50 60 24 32 40 48 111 139 167 5820 7200 8100 60 Hz Vrms Current @ 208 Vrms 99 208, 220V, 415V , 3Ø+N 28 42 56 84 60 Hz sinusoidal Max dissipation (@ nominal load and battery in recharge) W 1450 2060 2650 3660 Mechanical data Depth mm Width mm 500 800 Height mm 1400 Weight kg 350 Max. noise level (@ 1m) dBA <55 19 835 550 620 1600 470 1780 583 <58 720 <58 MKA4CAT0UKC/Rev. 4-07/2008/UK