ZigBee Converter User’s Manual
Warranty
All products manufactured by ICP DAS are warranted against
defective materials for a period of one year from the date of delivery
to the original purchaser.
Warning
ICP DAS assumes no liability for damages consequent to the use of
this product. ICP DAS reserves the right to change this manual at
any time without notice. The information furnished by ICP DAS is
believed to be accurate and reliable. However, no responsibility is
assumed by ICP DAS for its use, or for any infringements of patents
or other rights of third parties resulting from its use.
Copyright
Copyright 2008 by ICP DAS. All rights are reserved.
Trademark
The names used for identification only may be registered
trademarks of their respective companies.
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
1
Table of Contents
1.
Introduction..................................................................................................................................3
2.
3.
Specifications ...............................................................................................................................4
Product Description .....................................................................................................................6
3.1.
Pin assignment .................................................................................................................6
3.2.
Block diagram ..................................................................................................................7
4.
Applications .................................................................................................................................8
4.1.
Application Introduction ..................................................................................................8
4.2.
Application Example........................................................................................................9
1. Serial Port Operating Mode1: ...............................................................................9
2. Serial Port Operating Mode2: .............................................................................10
3. Serial Port Operating Mode3: ............................................................................. 11
4. Ethernet Operating Mode1:.................................................................................12
5. Ethernet Operating Mode2:.................................................................................13
6. Ethernet Operating Mode3:.................................................................................14
5.
Quick Start for the ZigBee Converter ........................................................................................15
5.1.
Installation the Hardware ..............................................................................................15
5.2.
5.3.
5.4.
5.5.
6.
7.
Dimensions.................................................................................................................................30
Appendix.....................................................................................................................................31
7.1.
Download Setting Tool from Our Website :
7.2.
Download Document form Our Website:...................................................................31
7.3.
Introduction to ZigBee Series: ...................................................................................31
7.4.
7.5.
7.6.
8.
Installation the Configuration Tool ...............................................................................18
Quick Start for ZigBee Converter Configuration Utility ..............................................20
Configure the Serial Port of the ZigBee Converter.......................................................22
Configure the Ethernet of the ZigBee Converter ..........................................................26
Technical Service: .........................................................................................................31
Encryption Setting:.....................................................................................................31
Network Status Detection Time Setting:....................................................................31
Realse Note ................................................................................................................................32
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
2
1. Introduction
ZigBee is a specification based on the IEEE 802.15.4 standard for
wireless personal area networks (WPANs). ZigBee operates in the ISM
radio bands and its focus is to define a general-purpose, inexpensive,
self-organizing, mesh network that can be used for industrial control,
embedded sensing, medical data collection, smoke and intruder warning,
building automation, home automation, and domotics, etc.
ICP DAS provided ZB-2570(Host) and ZB-2571(Slave). At present
supports RS-232, RS-485 and Ethernet three kind of communication
interfaces, its main design goal is the limited data communication by
wireless way transmission,so may to provide one kind of better solution for
the wiring difficult environment,
ZigBee converter provided six operating modes, please refer to the
tenth page.
Transmission frequency range of ZB-2570 and ZB-2571 between
2.405GHz and 2.480GHz, separates by each 5MHz, provided 16 Channels
for user. And provide 65535 PANID for user to set the Network group.
We also provides the Repeater modul, when broke the communication
rage of ZigBee converter, you can use the repeater modul to increase the
communication rage of ZB-2570 and ZB-2571.
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
3
2. Specifications
Features:
ISM 2.4 GHz operating frequency
Full compliant 2.4G IEEE802.15.4 / ZigBee specifications.
Wrieless transmission range up to 100M(Line of sight).
DIN-Rail mount.
Specifications:
Core
CPU
SRAM
Flash Memony
80186,80MHz or compatible
512 Kbytes
512KBytes; Erase unit is one sector (64K bytes);100,000
erase/write cycles
EEPROM
16K bytes (8 blocks, each block has 256 bytes); Data
retention > 40 years;1,000,000 erase/write cycles
Communication Interface
COM0(ZB-2570) RS-232 (TXD, RXD, GND);D-SUB9 Female, Non-isolation
RS-485 (D+, D-;self-tuner ASCI inside); Non-isolation
COM0(ZB-2571) RS-232 (TXD, RXD, GND);D-SUB9 Male,Non-isolation
RS-485 (D+, D-;self-tuner ASCI inside); Non-isolation
Ethernet Port
10/100 Base-TX (Auto-negotiating, Auto_MDIX, LED
indicstors)
LED Indicators
Power (Red)
ZigBee Rx (Yellow)
ZigBee Net State (Green)
COM0 Setting
Baudrate
1200~115200 bps
Data bit
7, 8
Parity
Even, Odd, None
Stop bit
1
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
4
Power
Protection
EMS Protection
Required Supply Voltage
Power consumption
Connection
Dimensions
Case
Flammability
Dimensions
Installation
Environment
Operating Temperature
Storage Temperature
Relative Humidity
Power reverse polarity protection
ESD, Surge, EFT
+10 to +30VDC
2.5W
5-Pin 5.08mm Removable Terminal Block
Plastic
UL 94V-0 materials
33mm×107mm×78mm (W×H×D)
DIN-Rail
-25℃ to +75℃
-40℃ to +80℃
5% to 95% Non-condensing
Wireless:
RF channels
Receive sensitivity
Transmit Power
Data encryption
Network Topology support
Certification
Antenna
16
-102 dBm
12dBm
AES CTR
Star, Mesh and cluster tree
TUV
2.4GHz – 3dBi Directional antenna.
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
5
3. Product Description
3.1. Pin assignment
Bottom View:
:
Front View:
:
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
6
3.2. Block diagram
The ZigBee converter have three communication interface to use, they
are RS-232, RS-485 and Ethernet, and communication with ZigBee by
embedded contronller controls.
When you want to configure the ZigBee converter, you need to adjust the
switch to the ZBSET, and then make its power on .
When you want to work the ZigBee converter, you need to adjust the
switch to the RUN, and then make its power on .
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
7
4. Applications
4.1. Application Introduction
Interface
Serial Port
(RS-232/RS-485)
Operating Modes
Operating Mode 1
Transparent without addressable
Refer to Serial Port Mode 1
Operating Mode 2
Transparent with addressable
Refer to Serial Port Mode 2
Operating Mode 3
Modbus RTU
Refer to Serial Port Mode 3
Interface
Ethernet
(RS-45)
Operating Modes
Operating Mode 1
Transparent without addressable
Refer to Ethernet Mode 1
Operating Mode 2
Transparent with addressable
Refer to Ethernet Mode 2
Operating Mode 3
Modbus TCP
Refer to Ethernet Mode 3
Refer to chapter 5 for further setting argument information.
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
8
4.2. Application Example
1. Serial Port Operating Mode1:
:
When you want to converter the RS-232/RS-485 interface into to ZigBee and the
device is addressable such as ICPDAS I-7000/M-7000/I-87k remote I/O modules, you can
use our ZB-2571 (slave) to connect to these I/O modules and use the ZB-2570 (host) to
connect to your controller or PC.
$01M
ZB-2570
i-7188
PC
!017xxx
ZB-2570
i-7188
PC
In some applications that the host controller needs to broadcast the data to all
RS-232/RS-485 devices and these devices receive data only (no response), you can also
use this mode.
Refer to ZigBee Converter Serial Port Setting for further setting argument information.
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
9
2. Serial Port Operating Mode2:
:
If the RS-232/RS-485 interface modules aren’t addressable, you can use mode 2 to
set an address to the ZB-2571 from 1~0xFFFF (ZB-2570 is always set as 0). Add 5 ASCII
characters to the header of your controller’s original request data, then the remote device
that is the correct address will responses it. This mode is similar as ICPDAS I-752N
products.
:0002XXX
ZB-2570
i-7188
PC
XXX
ZB-2570
i-7188
PC
Refer to ZigBee Converter Serial Port Setting for further setting argument information.
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
10
3. Serial Port Operating Mode3:
:
This is specific mode for Modbus RTU devices.
M-7000 Module
ZB-2571
RS-485
Address:
:01
01 05 00 01 FF 00
RU-87Px
ZB-2571
ZB-2570
i-7188
RS-485
Address:
:02
PC
ZB-2571
M-87Kx
RS-485
01 05 00 01 FF 00
ZB-2571
M-7000 Module
Address:
:03
RS-485
Address:
:01
ZB-2570
i-7188
PC
Refer to ZigBee Converter Serial Port Setting for further setting argument information.
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
11
4. Ethernet Operating Mode1:
:
This mode is similar as serial port operating mode 1 but connect to the Ethernet
devices. You should create a socket with ZB-2570 instead of remote device at controller
side. The ZB-2071 will create a socket connection to the rear device (you should set the
connection IP and port number via our utility software before you use it.). When the
controller sends a TCP package to ZB-2570, the ZB-2570 will broadcast it. When the
ZB-2571 receives the data from ZB-2570, it will forward it the rear device. If the device
responses data, the ZB-2571 will only send the TCP package to the ZB-2570. Then your
controller will receive the data that is forwarded from ZB-2570.
ZB-2571
TCP/IP
i-7188
PC
TCP Package
ZB-2571
ZB-2570
i-7188
TCP/IP
TCP/IP
PC
PC
i-7188
ZB-2571
TCP/IP
TCP Package
i-7188
PC
ZB-2571
TCP/IP
i-7188
PC
TCP Package
ZB-2570
ZB-2571
i-7188
TCP/IP
TCP/IP
PC
i-7188
TCP Package
PC
ZB-2571
TCP/IP
i-7188
PC
Refer to ZigBee Converter Ethernet Setting for further setting argument information.
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
12
5. Ethernet Operating Mode2:
:
This mode is similar as serial port operating mode 2 but connect to the Ethernet
devices.
ZB-2571
TCP/IP
TCP Package
:0001xxx
Address:
:01
i-7188
PC
ZB-2571
ZB-2570
i-7188
TCP/IP
TCP/IP
PC
i-7188
Address:
:02
PC
ZB-2571
TCP/IP
TCP Package
xxx
i-7188
PC
Address:
:03
ZB-2570
i-7188
TCP/IP
PC
Refer to ZigBee Converter Ethernet Setting for further setting argument information.
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
13
6. Ethernet Operating Mode3:
:
This is specific mode for Modbus TCP devices. You should set a mapping address to
the Modbus TCP device in the ZB-2571 via our utility software. Then you can send an
Modbus TCP request command from your SCADA software or your own software via our
ZB-2570, then the device that is correct address will response it.
For example, if your Modbus TCP device’s default address is 1 and you set the
mapping address of the ZB-2571 to address 2, then at your software you should send a
Modbus TCP request command with the address filed is 02 to request the data.
Refer to ZigBee Converter Ethernet Setting for further setting argument information.
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
14
5. Quick Start for the ZigBee Converter
5.1. Installation the Hardware
1. Serial Port - RS-232
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
15
2. Serial Port - RS-485
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
16
3. Ethernet – RJ-45
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
17
5.2. Installation the Configuration Tool
1. Please download the file from
http://ftp.icpdas.com/pub/cd/usbcd/napdos/zigbee/utility/
2. Uncompress the file in your PC and double-click the setup.exe to install
the configuration tool for ZigBee converter.
3. Click the OK button to start the installation when the following screen pops
up.
4. When the following screen shows up afterwards, you can use our default
directory or click Change Directory to change the installation directory in
your PC. Click
to install the software or click Exit Setup to exit the
installation.
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
18
5. Click Continue to complete the software installation or click Cancel to exit
the installation.
6. Click OK. And the installation is successfully completed.
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
19
5.3. Quick Start for ZigBee Converter Configuration Utility
1. When you configure the ZigBee converter, you need to turn the switch to
the ZBSET(Figure 1), and then makes its power on, After configuration is
done, you need to turn the switch to the RUN(Figure 2), and make the
power on again.
Figure 1
Figure 2
2. After you install the utility, you can find the executable file at
Start\Application file\ICPDAS\ZB_257x Configuration Utility v2.0
3. Connect one of the communication interface (RS-232, RS-485 or Ethernet;
the default configuration interface is RS-232) and execute the utility.
4. When the following screen shows up:
1
2
3
(1).Click Module to select the module which you want to configure
(ZB-2570 or ZB-2571).
(2).Click Connection to configure the ZB-2570 or ZB-2571.
(3).Click Connect to configure the ZB-2570 or ZB-2571.
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
20
5. When the following screen shows up:
1
Click Here
2
4
3
4
(1) Click “Click Here” to select the interface that brings the PC and the
ZigBee converter together.
(2) If you use the serial port as the configuration interface, first select the
port number of PC that connects to the ZigBee converter
(3) If you use Ethernet as the configuration interface, enter IP and port of
the ZigBee converter; the default IP is 192.168.255.1, and the default
port is 10000.
(4) Click OK to configure the ZigBee converter or Click Cancel to cancel
connection.
When the following screen displays, it means that connection succeeds, and
click OK to continue the configuration.
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
21
5.4. Configure the Serial Port of the ZigBee Converter
1. ZigBee Converter Serial Port Hardware
I.
you need to turn the switch to the ZBSET, and then make its power on.
II. How to Configure the Serial Port!
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
22
2. ZigBee Converter Serial Port Setting
I. Serial Port Operating Mode1 ─ Transparent:
:
(1.) ZigBee Parameter Configuration:
:PAN ID and Channel must be the same as each
other, ZB-2570’s NodeID must be 00 00, the range of ZB-2571’s NodeID is 00 01 ~
FF FF.
(2.) Converter Operating Interface:
:check Serial Port Interface, then sets Serial Port
Configuration.
(3.) Serial Port Configuration:
:Mode chooses Transparent; Baudrate support
1200~115200 bps, Data Bit support 7 and 8, Parity Check support Even, None and
Odd, Stop Bit support 1 and 2.
(4.) Click Setting to configuration.
(5.) When the window pops up like the picture
the “Configuration Utility” window.
, click Disconnect botton in
*Note:Encryption and Network Status Detection Time Interval refer to Chapter 7.
5
4
5
1
4
1
2
2
3
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
3
23
II. Serial Port Operating Mode2 ─ Addressable:
:
(1.) ZigBee Parameter Configuration:
:PAN ID and Channel must be the same as each
other, ZB-2570’s NodeID must be 00 00, the range of ZB-2571’s NodeID is 00 01 ~
FF FF.
(2.) Converter Operating Interface:
:check Serial Port Interface, then sets Serial Port
Configuration.
(3.) Serial Port Configuration:
:Mode chooses Addressable, the address is equal to
NodeID; Baudrate support 1200~115200 bps, Data Bit support 7 and 8, Parity Check
support Even, None and Odd, Stop Bit support 1 and 2.
(4.) Click Setting to configuration.
(5.) When the window pops up like the picture
the “Configuration Utility” window.
, click Disconnect botton in
*Note:Encryption and Network Status Detection Time Interval refer to Chapter 7.
5
4
5
1
4
1
2
2
3
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
3
24
III.
Serial Port Operating Mode3 ─ Modbus RTU:
:
(1.) ZigBee Parameter Configuration:
:PAN ID and Channel must be the same as each
other, ZB-2570’s NodeID must be 00 00, the range of ZB-2571’s NodeID is 00 01 ~
FF FF.
(2.) Converter Operating Interface:
:check Serial Port Interface, then sets Serial Port
Configuration.
(3.) Serial Port Configuration:
:Mode chooses Modbus RTU, range of Command
Space is 1~FF; Baudrate support 1200~115200 bps, Data Bit support 7 and 8, Parity
Check support Even, None and Odd, Stop Bit support 1 and 2.
(4.) Click Setting to configuration.
(5.) When the window pops up like the picture
the “Configuration Utility” window.
, click Disconnect botton in
*Note:Encryption and Network Status Detection Time Interval refer to Chapter 7.
5
4
5
1
4
1
2
2
3
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
3
25
5.5. Configure the Ethernet of the ZigBee Converter
1. ZigBee Converter Etheret Hardware
I. you need to turn the switch to the ZBSET, and then make its power on.
II. How to Configure the Ethernet!
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
26
2. ZigBee Converter Ethernet Setting
I. Ethernet Operating Mode1 ─ Transparent:
:
(1.) ZigBee Parameter Configuration:
:PAN ID and Channel must be the same as each
other, ZB-2570’s NodeID must be 00 00, the range of ZB-2571’s NodeID is 00 01 ~
FF FF.
(2.) Converter Operating Interface:
:check Ethernet Interface, then sets ZigBee’s
Ethernet Configuration.
(3.) ZigBee’s Ethernet Configuration:
:Mode chooses Transparent ; IP of the ZB-2571
must be not the same as the ZB-2570, the range of IP is 0~255.0~255.0~255.0~255,
the range of mask is 0~255.0~255.0~255.0~255, the range of gateway is
0~255.0~255.0~255.0~255, the range of port is 1~32767.
(4.) Click Setting to configuration.
(5.) When the window pops up like the picture
the “Configuration Utility” window.
, click Disconnect botton in
*Note:Encryption and Network Status Detection Time Interval refer to Chapter 7.
5
4
5
1
4
1
2
2
3
3
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
27
II. Ethernet Operating Mode2 ─ Addressable:
:
(1.) ZigBee Parameter Configuration:
:PAN ID and Channel must be the same as each
other, ZB-2570’s NodeID must be 00 00, the range of ZB-2571’s NodeID is 00 01 ~
FF FF.
(2.) Converter Operating Interface:
:check Ethernet Interface, then sets ZigBee’s
Ethernet Configuration.
(3.) ZigBee’s Ethernet Configuration:
:Mode chooses Addressable, the address is
equal to NodeID; IP of the ZB-2571 must be not the same as the ZB-2570, the range
of IP is 0~255.0~255.0~255.0~255, the range of mask is 0~255.0~255.0~255.0~255,
the range of gateway is 0~255.0~255.0~255.0~255, the range of port is 1~32767.
(4.) Click Setting to configuration.
(5.) When the window pops up like the picture
the “Configuration Utility” window.
, click Disconnect botton in
*Note:Encryption and Network Status Detection Time Interval refer to Chapter 7.
5
4
5
1
4
1
2
2
3
3
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
28
III.
Ethernet Operating Mode3 ─ Modbus TCP:
:
(1.) ZigBee Parameter Configuration:
:PAN ID and Channel must be the same as each
other, ZB-2570’s NodeID must be 00 00, the range of ZB-2571’s NodeID is 00 01 ~
FF FF.
(2.) Converter Operating Interface:
:check Ethernet Interface, then sets Device’s
Ethernet Configuration.
(3.) Device’s Ethernet Configuration:
:Mode chooses Modbus TCP; the range of IP is
0~255.0~255.0~255.0~255, the range of mask is 0~255.0~255.0~255.0~255, the
range of gateway is 0~255.0~255.0~255.0~255, the range of port is 1~32767.
(4.) Click Setting to configuration.
(5.) When the window pops up like the picture
the “Configuration Utility” window.
, click Disconnect botton in
*Note:Encryption and Network Status Detection Time Interval refer to Chapter 7.
5
4
5
1
4
1
2
2
3
3
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
29
6. Dimensions
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
30
7. Appendix
7.1. Download Setting Tool from Our Website :
http://ftp.icpdas.com/pub/cd/usbcd/napdos/zigbee/utility/
7.2. Download Document form Our Website:
:
http://ftp.icpdas.com/pub/cd/usbcd/napdos/zigbee/manual/
7.3. Introduction to ZigBee Series:
:
http://www.icpdas.com/products/GSM_GPRS/zigbee/zigbee_converte
r.htm
7.4. Technical Service:
If you have any questions,please send your problem to
[email protected] .
7.5. Encryption Setting:
:
If you select “Yes”, the data transmission will be encrypt; If you select “No”, the data
transmission will be no encrypt;
7.6. Network Status Detection Time Setting:
:
If the parameter is 0x14, it will detect network status every 20 second, If the parameter
is 0x00, the mechanism will be disenable.
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
31
8. Realse Note
8.1. The Cannel chooses 4, 9, 14, 15 to avoid noise ,if the environment have WiFi,
Bluetooth etc.
8.2. Please don’t adjust the switch to the INIT, the function is used for ICP DAS engineer
to program.
8.3. Default setting of manufactory:
:
ZB-2570
Interface
RS-232
Mode
Transparent
PanID
00 01
NodeID
00 00
Channel
1
Data Format
115200, N, 8, 1
IP
192.168.255.1
Mask
255.255.0.0
Gateway
192.168.0.1
Port
10000
ZB-2571
Interface
RS-232
Mode
Transparent
PanID
00 01
NodeID
00 01
Channel
1
Data Format
115200, N, 8, 1
IP
192.168.255.1
Mask
255.255.0.0
Gateway
192.168.0.1
Port
10000
ICPDAS ZigBee Converter User’s Manual, Ver:
:1.0, 2008/9/22
32