Download 040000071 - pRack PR100 compressor rack controller
Transcript
pRack PR100 compressor rack controller Quick guide LEIA E CONSERVE ESTAS INSTRUÇÕES READ AND SAVE THESE INSTRUCTIONS NO POWER & SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT! I n t e g r a t e d C o n t r o l S o l u t i o n s & E n e r g y S a v i n g s ENG CAREL, its employees or subsidiaries be liable for any lost earnings or sales, losses of data and information, costs of replacement goods or services, damage to things or people, downtime or any direct, indirect, incidental, actual, punitive, exemplary, special or consequential damage of any kind whatsoever, whether contractual, extra-contractual or due to negligence, or any other liabilities deriving from the installation, use or impossibility to use the product, even if CAREL or its subsidiaries are warned of the possibility of such damage. IMPORTANT CAREL bases the development of its products on decades of experience in HVAC, on the continuous investments in technological innovations to products, procedures and strict quality processes with in-circuit and functional testing on 100% of its products, and on the most innovative production technology available on the market. CAREL and its subsidiaries nonetheless cannot guarantee that all the aspects of the product and the software included with the product respond to the requirements of the final application, despite the product being developed according to start-of-the-art techniques. The customer (manufacturer, developer or installer of the final equipment) accepts all liability and risk relating to the configuration of the product in order to reach the expected results in relation to the specific final installation and/or equipment. CAREL may, based on specific agreements, act as a consultant for the positive commissioning of the final unit/application, however in no case does it accept liability for the correct operation of the final equipment/system. DISPOSAL INFORMATION FOR USERS ON THE CORRECT HANDLING OF WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT (WEEE) In reference to European Union directive 2002/96/EC issued on 27 January 2003 and the related national legislation, please note that: • WEEE cannot be disposed of as municipal waste and such waste must be collected and disposed of separately; • the public or private waste collection systems defined by local legislation must be used. In addition, the equipment can be returned to the distributor at the end of its working life when buying new equipment; • the equipment may contain hazardous substances: the improper use or incorrect disposal of such may have negative effects on human health and on the environment; • the symbol (crossed-out wheeled bin) shown on the product or on the packaging and on the instruction sheet indicates that the equipment has been introduced onto the market after 13 August 2005 and that it must be disposed of separately; • in the event of illegal disposal of electrical and electronic waste, the penalties are specified by local waste disposal legislation. The CAREL product is a state-of-the-art product, whose operation is specified in the technical documentation supplied with the product or can be downloaded, even prior to purchase, from the website www. CAREL.com. Each CAREL product, in relation to its advanced level of technology, requires setup / configuration / programming / commissioning to be able to operate in the best possible way for the specific application. The failure to complete such operations, which are required/indicated in the user manual, may cause the final product to malfunction; CAREL accepts no liability in such cases. Only qualified personnel may install or carry out technical service on the product. The customer must only use the product in the manner described in the documentation relating to the product. In addition to observing any further warnings described in this manual, the following warnings must be heeded for all CAREL products: • Prevent the electronic circuits from getting wet. Rain, humidity and all types of liquids or condensate contain corrosive minerals that may damage the electronic circuits. In any case, the product should be used or stored in environments that comply with the temperature and humidity limits specified in the manual. • Do not install the device in particularly hot environments. Too high temperatures may reduce the life of electronic devices, damage them and deform or melt the plastic parts. In any case, the product should be used or stored in environments that comply with the temperature and humidity limits specified in the manual. • Do not attempt to open the device in any way other than described in the manual. • Do not drop, hit or shake the device, as the internal circuits and mechanisms may be irreparably damaged. • Do not use corrosive chemicals, solvents or aggressive detergents to clean the device. • Do not use the product for applications other than those specified in the technical manual. Warranty on the materials: 2 years (from the date of production, excluding consumables). Approval: the quality and safety of CAREL INDUSTRIES Hqs products are guaranteed by the ISO 9001 certified design and production system. WARNING: separate as much as possible the probe and digital input signal cables from the cables carrying inductive loads and power cables to avoid possible electromagnetic disturbance. Never run power cables (including the electrical panel wiring) and signal cables in the same conduits. NO POWER & SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT! Key icone NOTE: All of the above suggestions likewise apply to the controllers, serial boards, programming keys or any other accessory in the CAREL product portfolio. CAREL adopts a policy of continual development. Consequently, CAREL reserves the right to make changes and improvements to any product described in this document without prior warning. IMPORTANT: TUTORIAL: The technical specifications shown in the manual may be changed without prior warning. to bring attention to a very important subject; in particular, regarding the practical use of the various functions of the product. to bring critical issues regarding the use of the pRack PR100 to the attention of the user. some simple examples to accompany the user in configuring the most common settings. The liability of CAREL in relation to its products is specified in the CAREL general contract conditions, available on the website www. CAREL.com and/or by specific agreements with customers; specifically, to the extent where allowed by applicable legislation, in no case will 3 pRack +040000071 rel. 1.1 - 14.10.2011 ENG Content 1. 1.1 1.2 1.3 1.4 2. 1.5 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 3. START UP 7 Starting the first time .............................................................................................................................................7 Pre-configurations ..................................................................................................................................................7 Wizard .............................................................................................................................................................................7 Example of configuring a system with 2 suction and condenser lines using .................... the Wizard ....................................................................................................................................................................8 PRE-CONFIGURATION 10 Advanced configuration ..................................................................................................................................10 Pre-configuration 1: RS2 ..................................................................................................................................11 Pre-configuration 2: RS3 ..................................................................................................................................12 Pre-configuration 3: RS3p ..............................................................................................................................14 Pre-configuration 4: RS3i .................................................................................................................................16 Pre-configuration 5: RS4 ..................................................................................................................................18 Pre-configurazione 6: RS4i ..............................................................................................................................20 Pre-configuration 7: SL3d................................................................................................................................22 Pre-configuration 8: SL5d................................................................................................................................24 Pre-configuration 9: SW1.................................................................................................................................26 Pre-configuration 10: SW2 ..............................................................................................................................28 Pre-configuration 11: d-RS2 ...........................................................................................................................30 Pre-configuration 12: d-RS3 ...........................................................................................................................32 Pre-configuration 13: d-RS4 ...........................................................................................................................34 PARAMETERS TABLE 36 5 pRack +040000071 rel. 1.1 - 14.10.2011 ENG 1. 1.1 START UP sure the Carel default values have been reset as described in paragraph 6.8.2 of the User Manual cod.+0300011EN. Starting the first time After having correctly installed pRack, as described in the User Manual cod. +0300011EN, a number of preliminary operations are required to configure the installation. Important: after having configured the system, power down the controller and power up again. Tutorial: the pRack PR100 configuration procedure varies according to the complexity of the installation: A. systems with only one board and maximum one external terminal. In this case, simply connect the terminal (if not built-in), power up the board and select one of the configuration solutions described below. B. systems with more than one board in pLAN or two external terminals. In this case, the additional operations described in Appendix A. 2 of the User Manual cod.+0300011EN need to be completed before proceeding with configuration. 1.2 Pre-configurations Start up Select Config.Item: PRE-CONFIGURATION Choose one from the configuration in the list Fig. 1.a This solution is used to choose between thirteen configurations pre-loaded in the pRack PR100 software. For the description of the pre-configurations see the table below, while for the complete description of each configuration see Chap.2. pRack PR100 automatically configures the inputs and outputs as described in paragraph 4.1.4 of the User Manual cod.+0300011EN; for details on the inputs and outputs associated with each pre-configuration, see Chap. 2. The procedure for configuring an installation described below is the same for all system configurations that feature just one pRack PR100 board, and for system configurations with more than one board connected in a pLAN. When first starting the pRack PR100 board, after waiting around 1 minute, a screen is shown for choosing the language used to display the program (English or Italian). Press ENTER ( ) to change the language displayed, while pressing ESC displays the following screen. 1.3 Wizard Note: If no option is chosen within a time set by parameter and visible on the screen, the current language remains selected. Start up Note: pRack PR100 is available as standard with English and Italian languages loaded on board. Other languages are available at ksa.carel.com that can be loaded onto the control using the pRack Manager software, following the procedure described in Chap. 10 of the User Manual cod.+0300011EN. Answer the questions to have a fully configuration Select Config.Item: WIZARD Fig. 1.b This solution is used to obtain the recommended configuration for the specific installation. By responding to a series of questions, screen by screen, the user is guided through the selection of the devices present. Once the guided selection procedure has been completed, the end result (report) is shown, and if the configuration is suitable the parameters to start operation of the pRack PR100 can be installed directly, including those associated with the inputs and outputs as described in parag. 4.1.4 of the User Manual cod.+0300011EN. After having selected the user interface language, the pRack PR100 software shows a screen for choosing between three possible system configuration solutions, as follows: • Pre-configurations • Wizard • Advanced configuration. Important: after having configured the system, the configuration can be modified, it can be modified by repeating the same procedure, making Note: after having configured the parameters using the Wizard, the configuration can be modified manually, within the context of the selected 7 pRack +040000071 rel. 1.1 - 14.10.2011 ENG system configuration. Important: before starting the pRack PR100, carefully check the settings made automatically by the software. Then select the type of system as SUCTION & CONDENSER: Wizard Tutorial: The following paragraph shows a Ib01 Type of Installation: configuration example using the Wizard for an installation with two suction lines. SUCTION & CONDENSER 1.4 Example of configuring a system with 2 suction and condenser lines using the Wizard Fig. 1.d Set the type of compressors and control for suction line 1, answering the questions prompted by the pRack PR100 software, e.g.: Below is a possible example of using the Wizard to configure a typical system like the one shown in the figure, with 2 suction lines and 2 condenser lines on different boards: J7 J6 J5 J10 Y1 J9 Compressor type: RECIPROCATING C2 Y2 PWM 0/10V GNX NO2 GND Tx/Rx J8 ISOLATED J10 serial card 2 J4 pLAN J7 J6 J5 GND Y2 C2 Tx/Rx GND J9 serial card 2 J4 I/O TLAN GNX NO2 Y1 Tx/Rx J8 ISOLATED GND Tx/Rx GND GND TLAN I/O PWM 0/10V Wizard Ib03 Compressor config. Compressor number: NO1 NC1 C1 GND ID1 J3 +VDC +5Vref GND SYNC B6 B5 G0 B4 B3 B2 G I/O J2 3 Fig. 1.e serial card 1 J1 NO1 NC1 C1 GND ID1 J3 +VDC +5Vref SYNC GND B6 G0 G B5 B4 B3 J2 B2 J1 B1 input voltage: max. power: 24 V (+10/-15%); 50/60 Hz 8 VA / 6 W 48 V (36Vmin…72 Vmax) serial card 1 B1 input voltage: max. power: 24 V (+10/-15%); 50/60 Hz 8 VA / 6 W 48 V (36Vmin…72 Vmax) Wizard Ib40 Compressor config. Regulation by: PRESSURE Measure unit: barg I/O Fig. 1.c Refrigerant: The preliminary operations to be completed before configuration are as follows: 1. with the boards not connected in the pLAN, power up the second pRack board and set the pLAN address to 2 (for details see Appendix A.2 of the User Manual cod.+0300011EN) 2. power down and connect the two boards in the pLAN, plus any terminals, as described in paragraph 3.7 of the User Manual cod.+0300011EN. 3. power up the boards and wait for the Wizard selection screen to be displayed R404A Fig. 1.f Wizard Ib41 Compressor config. Regulation type: PROPORTIONAL BAND Enable integral time action: YES Fig. 1.g After having configured suction line 1, a prompt will be shown to configure another suction line, obviously the answer is YES: pRack +040000071 rel. 1.1 - 14.10.2011 8 ENG After having also configured the second condenser line, the software asks if a summary should be displayed of the settings made: Wizard Ib43 Compressor config. Wizard Configure another suction line: Ib2a Visualize Wizard report: YES Fig. 1.h NO (Push (DOWN) to continue) To the next question, which prompts if there is a pRack board dedicated to the second line, answer YES; in this way, the pRack PR100 software prepares to configure the board with address 2 in the pLAN: Fig. 1.l Wizard Ib45 Compressor config. If the settings are correct, the set values can be installed: Wizard Ib3a Board necessary 1 Dedicated pRack board for suction line: YES 2 All boards prsent (ENTER) to continue Fig. 1.i After having answered the questions for the configuration of the second suction line, the software then asks if there is a pLAN board dedicated to condenser line 1. In the case shown in the example, answer NO. Fig. 1.m After waiting a few seconds, the unit can be started. Wizard Wizard Ib90 Compressor config. Successfully complete Dedicated pRack board for suction line: Press (ENTER) to continue NO Fig. 1.n Fig. 1.j Note: after having configured pRack PR100, the After having configured condenser line 1, the software asks if condenser line 2 is used; answer YES: Wizard device needs to be switched off and on again to permanently save the new data. Ib96 Configure another condensing line: YES Fig. 1.k 9 pRack +040000071 rel. 1.1 - 14.10.2011 ENG 1.5 Advanced configuration Start up Select Config.Item: ADVANCED CONFIGURATION It only defines the structure of the plant For very expert users Fig. 1.o This solution is used to establish the configuration of the pLAN structure required for correct system operation. Once the procedure for selecting the various factors that affect the final configuration has been completed, the pRack PR100 software verifies whether the pLAN configuration is exact and prepares the user interface for configuration of the parameters that need to be set manually by the user. Important: this configuration solution is only recommended for expert users, as all the system parameters need to be set manually 2. PRECONFIGURATION Here below there are listed the configuration pre-set in the pRack software with the related features. To enter the pre-configuration list it is necessary to select the item PRE-CONFIGURATION in the screen shown by pRack software at start up (see Chapter 1). Summary of pre-configurations compressors N° index lines type N° capacity modulation No. of step comp. alarms 1 RS2 1 Piston - Scroll 2 1 2 RS3 1 Piston - Scroll 3 1 3 RS3p 1 Piston - Scroll 3 1 2 4 RS3i 1 Piston - Scroll 3 Inverter 3 5 RS4 1 Piston - Scroll 4 2 6 RS4i 1 Piston - Scroll 4 Inverter 3 7 SL3d 1 Scroll 3 Digital 1 8 SL5d 1 Scroll 5 Digital 1 9 SW1 1 Screw 1 2 2 10 SW2 1 Screw 2 2 2 11 d-RS2 2 Piston - Scroll 2 1 2 1 12 d-RS3 2 Piston - Scroll 3 1 3 1 13 d-RS4 2 Piston - Scroll 4 Inverter 3 4 Inverter 3 fans N° inverter Units in the pLAN(as well as the terminal) pRack PR100 Version 2 3 1 1 4 1 2 1 2 1 2 Inverter Inverter Inverter Inverter Inverter - 1 1 1 1 1 1 1 1 1 1 1 Compact Small Medium Medium Medium Large Medium Medium Small Small Medium 3 3 1 1 Inverter Inverter 1 Large 1,2 Medium + Medium Tab. 2.a pRack +040000071 rel. 1.1 - 14.10.2011 10 ENG 2.1 Pre-configuration 1: RS2 B7/ID5 T dis B4 C1 NO1 B5/ID3 T suct B3 C2 NO2 B6/ID4 Psuct B1 F1 NO3 F2 NO4 NO5 Fig. 2.a Description 2 reciprocating/ scroll compressors 2 fans 1 generic alarm for each compressor 1 generic alarm for condensers HP/LP pressostats pRack compact, PRK100X** I/O list Digital outputs pRack PR100 Compact NO1 NO2 NO3 NO4 NO5 pRack PR100 S, M, L, XL NO1 NO2 NO3 NO4 NO5 Compressor 1 Compressor 2 Fan 1 Fan 2 Alarms output Digital inputs ID1 ID2 B5 B6 B7 ID1 ID2 ID3 ID4 ID5 Suction HP pressostat Suction LP pressostat Generic compressor 1 alarm Generic compressor 2 alarm Generic condenser alarm Analog inputs B1 B3 B4 B1 B3 B4 Suction pressure probe Suction temperature probe Discharge temperature probe 4...20 mA NTC HTNTC -0.5..7.0 barg Tab. 2.b Main parameters Parameter Suction regulation by Suction regulation type Suction setpoint Suction differential Compressors rotation type Refrigerant High suction pressure alarm threshold Low suction pressure alarm threshold Condenser regulation by Condenser regulation type Condenser setpoint Condenser differential High condenser pressure alarm threshold Low condenser pressure alarm threshold Mask index Cab01 Cab01 Cab03 Cab08 Caf10 Caf04 Cae24 Cae26 Dab01 Dab01 Dab03 Dab09 Dae01 Dae03 Value PRESSURE NEUTRAL ZONE 3.5,barg 0.3 barg FIFO R404A 6.0 barg 0.0 barg TEMPERATURE PROPORTIONAL BAND 30.0 °C 2.0 °C 55.0 °C 5.0 °C Tab. 2.c 11 pRack +040000071 rel. 1.1 - 14.10.2011 ENG 2.2 Pre-configuration 2: RS3 ID6 Tdis Pcond B4 B2 F1 NO4 F2 NO5 C2 C3 C1 NO3 NO1 NO2 ID5 ID3 ID4 Tsuct Psuct B3 B1 NO7 Fig. 2.b Description 3 reciprocating/ scroll compressors 3 fans 1 generic alarm for each compressor 1 generic alarm for condenser HP/LP pressostats pRack S, PRK100S** pRack +040000071 rel. 1.1 - 14.10.2011 F3 NO6 12 ENG I/O list Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 Compressor 1 Compressor 2 Compressor 3 Fan 1 Fan 2 Fan 3 Alarms output Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 Suction HP pressostat Suction LP pressostat Generic compressor 1 alarm Generic compressor 2 alarm Generic compressor 3 alarm Common fan overload Analog inputs B1 B2 B3 B4 Suction pressure probe Condensing pressure probe Suction temperature probe Discharge temperature probe 4...20 mA 4...20 mA NTC HTNTC -0.5..7.0 barg 0.0..30.0 barg Tab. 2.d Main parameters Parameter Suction regulation by Suction regulation type Suction setpoint Suction differential Compressors rotation type Refrigerant High suction pressure alarm threshold Low suction pressure alarm threshold Condenser regulation by Condenser regulation type Condenser setpoint Condenser differential High condenser pressure alarm threshold Low condenser pressure alarm threshold Mask index Cab01 Cab01 Cab03 Cab08 Caf10 Caf04 Cae24 Cae26 Dab01 Dab01 Dab03 Dab07 Dae01 Dae03 Value PRESSURE NEUTRAL ZONE 3.5,barg 0.3 barg FIFO R404A 6.0 barg 0.0 barg PRESSURE PROPORTIONAL BAND 12.0 barg 2.0 barg 24.0 barg 7.0 barg Tab. 2.e 13 pRack +040000071 rel. 1.1 - 14.10.2011 ENG 2.3 Pre-configuration 3: RS3p Y1 ID10 Text B5 Tdis Pcond B4 B2 C1 NO1 NO2 ID3 ID4 C2 NO3 NO4 ID5 ID6 Tsuct B3 F NO7 ID9 C3 NO5 NO6 ID7 ID8 Psuct B1 NO8 Fig. 2.c Description 3 reciprocating compressors with one unloader each 1 fan stage with inverter 2 alarms for each compressor: thermal overload, oil 1 generic alarm for condenser HP/LP pressostats pRack M, PRK100M* pRack +040000071 rel. 1.1 - 14.10.2011 14 ENG I/O list Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 Compressor 1 Compressor 1, unloader Compressor 2 Compressor 2, unloader Compressor 3 Compressor 3, unloader Fan Alarms output Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 Suction HP pressostat Suction LP pressostat Compressor 1, thermal overload alarm Compressor 1, oil alarm Compressor 2, thermal overload alarm Compressor 2, oil alarm Compressor 3, thermal overload alarm Compressor 3, oil alarm Common fan overload Inverter alarm Analog outputs Y1 Common condenser inverter Analog inputs B1 B2 B3 B4 B5 Suction pressure probe Condensing pressure probe Suction temperature probe Discharge temperature probe External temperature probe 4...20 mA 4...20 mA NTC HTNTC NTC -0.5..7.0 barg 0.0..30.0 barg Tab. 2.f Main parameters Parameter Suction regulation by Suction regulation type Suction setpoint Suction differential Compressors rotation type Refrigerant High suction pressure alarm threshold Low suction pressure alarm threshold Condenser regulation by Condenser regulation type Condenser setpoint Condenser differential High condenser pressure alarm threshold Low condenser pressure alarm threshold Mask index Cab01 Cab03 Cab08 Caf10 Caf04 Cae24 Cae26 Cab01 Dab01 Dab03 Dab07 Dae01 Dae03 Cab01 15 Value PRESSURE NEUTRAL ZONE 3.5,barg 0.3 barg FIFO R404A 6.0 barg 0.0 barg PRESSURE PROPORTIONAL BAND 12.0 barg 2.0 barg 24.0 barg 7.0 barg Tab. 2.g pRack +040000071 rel. 1.1 - 14.10.2011 ENG 2.4 Pre-configuration 4: RS3i Y2 ID14 Text B5 Y1 Tdis Pcond ID13 B4 B2 C1 NO1 ID3 ID4 ID5 C2 NO2 ID6 ID7 ID8 Tsuct B3 F NO4 ID12 C3 NO3 ID9 ID10 ID11 Psuct B1 NO5 Fig. 2.d Description 3 reciprocating compressors, the first with inverter 1 fan stage with inverter 3 alarms for each compressor: thermal overload, oil, HP/LP 1 generic alarm for condenser HP/LP pressostats pRack M, PRK100M pRack +040000071 rel. 1.1 - 14.10.2011 16 ENG I/O List Digital outputs NO1 NO2 NO3 NO4 NO5 Compressor 1 Compressor 2 Compressor 3 Fan 1 Alarms output Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 Suction HP pressostat Suction LP pressostat Compressor 1, thermal overload alarm Compressor 1, oil alarm Compressor 1, HP/LP alarm Compressor 2, thermal overload alarm Compressor 2, oil alarm Compressor 2, HP/LP alarm Compressor 3, thermal overload alarm Compressor 3, oil alarm Compressor 3, HP/LP alarm Common fan overload Compressor inverter alarm Condenser inverter alarm Analog outputs Y1 Y2 First compressor inverter Condenser inverter 0...10 Vdc 0...10 Vdc Analog inputs B1 B2 B3 B4 B5 Suction pressure probe Condensing pressure probe Suction temperature probe Discharge temperature probe External temperature probe 4...20 mA 4...20 mA NTC HTNTC NTC -0.5..7.0 barg 0.0..30.0 barg Tab. 2.h Main parameters Parameter Suction regulation by Suction regulation type Suction setpoint Suction differential Compressors rotation type Refrigerant High suction pressure alarm threshold Low suction pressure alarm threshold Condenser regulation by Condenser regulation type Condenser setpoint Condenser differential High condenser pressure alarm threshold Low condenser pressure alarm threshold Mask index Cab01 Cab01 Cab03 Cab08 Caf10 Caf04 Cae24 Cae26 Dab01 Dab01 Dab03 Dab07 Dae01 Dae03 Value PRESSURE NEUTRAL ZONE 3.5,barg 0.3 barg FIFO R404A 6.0 barg 0.0 barg PRESSURE PROPORTIONAL BAND 12.0 barg 2.0 barg 24.0 barg 7.0 barg Tab. 2.i 17 pRack +040000071 rel. 1.1 - 14.10.2011 ENG 2.5 Pre-configuration 5: RS4 Text B5 ID11 Tdis Pcond B4 B2 C1 NO1 ID3 ID4 C2 NO2 ID5 ID6 C3 NO3 ID7 ID8 Tsuct B3 Psuct B1 F1 NO5 F2 NO6 C3 NO4 ID9 ID10 F4 NO8 NO9 Fig. 2.e Descrizption 4 reciprocating/ scroll compressors 4 fans 2 alarms for each compressor: thermal overload, oil 1 generic alarm for condenser HP/LP pressostats pRack M, PRK100M* pRack +040000071 rel. 1.1 - 14.10.2011 F3 NO7 18 ENG I/O List Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 Compressor 1 Compressor 2 Compressor 3 Compressor 4 Fan1 Fan2 Fan3 Fan4 Alarms output Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 Suction HP pressostat Suction LP pressostat Compressor 1, thermal overload alarm Compressor 1, oil alarm Compressor 2, thermal overload alarm Compressor 2, oil alarm Compressor 3, thermal overload alarm Compressor 3, oil alarm Compressor 4, thermal overload alarm Compressor 4, oil alarm Common fan overload Analog inputs B1 B2 B3 B4 B5 Suction pressure probe Condensing pressure probe Suction temperature probe Discharge temperature probe External temperature probe 4...20 mA 4...20 mA NTC HTNTC NTC -0.5..7.0 barg 0.0..30.0 barg Tab. 2.j Main parameters Parameter Suction regulation by Suction regulation type Suction setpoint Suction differential Compressors rotation type Refrigerant High suction pressure alarm threshold Low suction pressure alarm threshold Condenser regulation by Condenser regulation type Condenser setpoint Condenser differential High condenser pressure alarm threshold Low condenser pressure alarm threshold Mask index Cab01 Cab01 Cab03 Cab08 Caf10 Caf04 Cae24 Cae26 Dab01 Dab01 Dab03 Dab07 Dae01 Dae03 Value PRESSURE NEUTRAL ZONE 3.5,barg 0.3 barg FIFO R404A 6.0 barg 0.0 barg PRESSURE PROPORTIONAL BAND 12.0 barg 2.0 barg 24.0 barg 7.0 barg Tab. 2.k 19 pRack +040000071 rel. 1.1 - 14.10.2011 ENG 2.6 Pre-configurazione 6: RS4i Y2 ID17 Text B5 Y1 ID16 Tdis Pcond B4 B2 C1 NO1 ID3 ID4 ID5 C2 NO2 ID6 ID7 ID8 Tsuct B3 C3 NO3 ID9 ID10 ID11 F NO5 ID15 C3 NO4 ID12 ID13 ID14 NO6 Psuct B1 Fig. 2.f Description 4 reciprocating/ scroll compressors, the first with inverter 1 fan stage with inverter 3 alarms for each compressor: thermal overload, oil differential, HP/LP 1 generic alarm for condenser HP/LP pressostats pRack L, PRK100L** pRack +040000071 rel. 1.1 - 14.10.2011 20 ENG I/O List Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 Compressor 1 Compressor 2 Compressor 3 Compressor 4 Fan Alarms output Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 ID15 ID16 ID17 Suction HP pressostat Suction LP pressostat Compressor 1, thermal overload alarm Compressor 1, oil differential alarm Compressor 1, HP/LP alarm Compressor 2, thermal overload alarm Compressor 2, oil differential alarm Compressor 2, HP/LP alarm Compressor 3, thermal overload alarm Compressor 3, oil differential alarm Compressor 3, HP/LP alarm Compressor 4, thermal overload alarm Compressor 4, oil differential alarm Compressor 4, HP/LP alarm Common fan overload Compressor inverter alarm Condenser inverter alarm Analog outputs Y1 Y2 First compressor inverter Common condenser inverter 0...10 Vdc 0...10 Vdc Analog inputs B1 B2 B3 B4 B5 Suction pressure probe Condensing pressure probe Suction temperature probe Discharge temperature probe External temperature probe 4...20 mA 4...20 mA NTC HTNTC NTC -0.5...7.0 barg 0.0...30.0 barg Tab. 2.l Main parameters Parameter Suction regulation by Suction regulation type Suction setpoint Suction differential Compressors rotation type Refrigerant High suction pressure alarm threshold Low suction pressure alarm threshold Condenser regulation by Condenser regulation type Condenser setpoint Condenser differential High condenser pressure alarm threshold Low condenser pressure alarm threshold Mask index Cab01 Cab01 Cab03 Cab08 Caf10 Caf04 Cae24 Cae26 Cab01 Dab01 Dab03 Dab07 Dae01 Dae03 Value PRESSURE NEUTRAL ZONE 3.5,barg 0.3 barg FIFO R404A 6.0 barg 0.0 barg PRESSURE PROPORTIONAL BAND 12.0 barg 2.0 barg 24.0 barg 7.0 barg Tab. 2.m 21 pRack +040000071 rel. 1.1 - 14.10.2011 ENG 2.7 Pre-configuration 7: SL3d ID6 Tdis Pcond B4 B2 C2 C1 NO1, N07 NO2 ID4 ID3 C3 NO3 ID5 Tsuct B3 Psuct B1 F1 NO4 NO6 Fig. 2.g Description 3 scroll compressors, the first Digital Scroll 2 fans 1 generic alarm for each compressor 1 generic alarm for condenser HP/LP pressostats pRack M, PRK100M** pRack +040000071 rel. 1.1 - 14.10.2011 F2 NO5 22 ENG Lista I/O Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 - SSR Compressor 1 Compressor 2 Compressor 3 Fan 1 Fan 2 Alarms output Compressor 1 – Digital Scroll Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 Suction HP pressostat Suction LP pressostat Compressor 1, generic alarm Compressor 2, generic alarm Compressor 3, generic alarm Common fan overload Analog inputs B1 B2 B3 B4 B5 Suction pressure probe Condensing pressure probe Suction temperature probe Discharge temperature probe External temperature probe 4...20 mA 4...20 mA NTC HTNTC NTC -0.5..7.0 barg 0.0..30.0 barg Tab. 2.n Main parameters Parameter Suction regulation by Suction regulation type Suction setpoint Suction differential Compressors rotation type Refrigerant High suction pressure alarm threshold Low suction pressure alarm threshold Condenser regulation by Condenser regulation type Condenser setpoint Condenser differential High condenser pressure alarm threshold Low condenser pressure alarm threshold Mask index Cab01 Cab01 Cab03 Cab08 Caf10 Caf04 Cae24 Cae26 Dab01 Dab01 Dab03 Dab07 Dae01 Dae03 Value PRESSURE NEUTRAL ZONE 3.5,barg 0.3 barg FIFO R404A 6.0 barg 0.0 barg PRESSURE PROPORTIONAL BAND 12.0 barg 2.0 barg 24.0 barg 7.0 barg Tab. 2.o 23 pRack +040000071 rel. 1.1 - 14.10.2011 ENG 2.8 Pre-configuration 8: SL5d Y1 ID9 Text B5 F NO6 ID8 Tdis Pcond B4 B2 C1 C2 NO1, N07 NO2 ID3 ID4 Tsuct B3 C3 NO3 ID5 C4 NO4 ID6 C5 NO5 ID7 Psuct B1 Fig. 2.h Description 5 scroll compressors, the first Digital Scroll 1 fan stage with inverter 1 generic alarm for each compressor 1 generic alarm for condenser HP/LP pressostats pRack L, PRK100L** pRack +040000071 rel. 1.1 - 14.10.2011 24 NO8 ENG I/O List Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 - SSR NO8 Compressor 1 Compressor 2 Compressor 3 Compressor 4 Compressor 5 Fan Compressor 1 – Digital Scroll Alarms output Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 Suction HP pressostat Suction LP pressostat Compressor 1, generic alarm Compressor 2, generic alarm Compressor 3, generic alarm Compressor 4, generic alarm Compressor 5, generic alarm Common fan overload Condenser inverter alarm Analog outputs Y1 Common condenser inverter 0..10 Vdc Analog inputs B1 B2 B3 B4 B5 Suction pressure probe Condensing pressure probe Suction temperature probe Discharge temperature probe External temperature probe 4...20 mA 4...20 mA NTC HTNTC NTC -0.5..7.0 barg 0.0..30.0 barg Tab. 2.p Main parameters Parameter Suction regulation by Suction regulation type Suction setpoint Suction differential Compressors rotation type Refrigerant High suction pressure alarm threshold Low suction pressure alarm threshold Condenser regulation by Condenser regulation type Condenser setpoint Condenser differential High condenser pressure alarm threshold Low condenser pressure alarm threshold Mask index Cab01 Cab01 Cab03 Cab08 Caf10 Caf04 Cae24 Cae26 Dab01 Dab01 Dab03 Dab07 Dae01 Dae03 Value PRESSURE NEUTRAL ZONE 3.5,barg 0.3 barg FIFO R404A 6.0 barg 0.0 barg PRESSURE PROPORTIONAL BAND 12.0 barg 2.0 barg 24.0 barg 7.0 barg Tab. 2.q 25 pRack +040000071 rel. 1.1 - 14.10.2011 ENG 2.9 Pre-configuration 9: SW1 ID5 Text B5 Tdis Pcond B4 B2 F1 NO3 C1 NO1 NO2 NO7 NO12 ID3 ID4 Tsuct B3 Psuct B1 Fig. 2.i Description 1 screw compressor with continuous modulation - 2 pulsing capacity valves - 2 relays for start up 2 fan stages 2 alarms for each compressor: generic, oil warning 1 generic alarm for condenser HP/LP pressostats pRack S, PRK100S** pRack +040000071 rel. 1.1 - 14.10.2011 26 F2 NO4 NO5 ENG I/O List Digital outputs NO1 NO2 NO3 NO4 NO5 NO7 - SSR NO12 - SSR Line relay Part winding Fan 1 Fan 2 Alarms output CR1 pulsing capacity valve CR2 pulsing capacity valve Digital inputs ID1 ID2 ID3 ID4 ID5 Suction HP pressostat Suction LP pressostat Compressor 1, generic alarm Compressor 1, oil flow warning Common fan overload Analog inputs B1 B2 B3 B4 B5 Suction pressure probe Condensing pressure probe Suction temperature probe Discharge temperature External temperature 4...20 mA 4...20 mA NTC HTNTC NTC -0.5...7.0 barg 0.0...30.0 barg Tab. 2.r Main parameters Parameter Suction regulation by Suction regulation type Suction setpoint Suction differential Compressors rotation type Refrigerant High suction pressure alarm threshold Low suction pressure alarm threshold Condenser regulation by Condenser regulation type Condenser setpoint Condenser differential High condenser pressure alarm threshold Low condenser pressure alarm threshold Mask index Cab01 Cab01 Cab03 Cab08 Caf10 Caf04 Cae24 Cae26 Dab01 Dab01 Dab03 Dab07 Dae01 Dae03 Value PRESSURE NEUTRAL ZONE 3.5,barg 0.3 barg FIFO R404A 6.0 barg 0.0 barg PRESSURE PROPORTIONAL BAND 12.0 barg 2.0 barg 24.0 barg 7.0 barg Tab. 2.s 27 pRack +040000071 rel. 1.1 - 14.10.2011 ENG 2.10 Pre-configuration 10: SW2 Y1 ID8 Text B5 F2 NO9 ID7 Tdis Pcond B4 B2 C1 NO1 NO2 NO3 NO4 ID3 ID4 C2 NO5 NO6 NO7 NO8 ID5 ID6 Tsuct B3 Psuct B1 Fig. 2.j Description 2 screw compressors - 2 capacity valves each - 2 relays for start up each 1 fan stage with inverter 2 alarms for each compressor: generic, oil warning 1 generic alarm for condenser HP/LP pressostats pRack M, PRK100M** pRack +040000071 rel. 1.1 - 14.10.2011 28 NO10 ENG I/O List Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 NO8 NO9 NO10 Screw compressor 1, line relay Screw compressor 1, part winding Screw compressor 1, CR1 valve Screw compressor 1, CR2 valve Screw compressor 2, line relay Screw compressor 2, part winding Screw compressor 2, CR1 valve Screw compressor 2, CR2 valve Fan 1 Alarms output Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 Suction HP pressostat Suction LP pressostat Compressor 1, generic alarm Compressor 1, oil flow warning Compressor 2, generic alarm Compressor 2, oil flow warning Common fan overload Condenser inverter alarm Analog outputs Y1 Common condenser inverter 0...10 Vdc Analog inputs B1 B2 B3 B4 B5 Suction pressure probe Condensing pressure probe Suction temperature probe Discharge temperature probe External temperature probe 4...20 mA 4...20 mA NTC HTNTC NTC -0.5...7.0 barg 0.0...30.0 barg Tab. 2.t Main parameters Parameter Suction regulation by Suction regulation type Suction setpoint Suction differential Compressors rotation type Refrigerant High suction pressure alarm threshold Low suction pressure alarm threshold Condenser regulation by Condenser regulation type Condenser setpoint Condenser differential High condenser pressure alarm threshold Low condenser pressure alarm threshold Mask index Cab01 Cab01 Cab03 Cab08 Caf10 Caf04 Cae24 Cae26 Dab01 Dab01 Dab03 Dab07 Dae01 Dae03 Value PRESSURE NEUTRAL ZONE 3.5,barg 0.3 barg FIFO R404A 6.0 barg 0.0 barg PRESSURE PROPORTIONAL BAND 12.0 barg 2.0 barg 24.0 barg 7.0 barg Tab. 2.u 29 pRack +040000071 rel. 1.1 - 14.10.2011 ENG 2.11 Pre-configuration 11: d-RS2 ID5 Text B7 Tdis Pcond B5 B2 L1 F1 NO3 F2 NO4 L2 NO5 C1_L1 C2_L1 NO1 NO2 ID3 ID4 T suct Psuct B4 B1 C1_L2 C2_L2 NO6 NO7 ID8 ID9 T suct Psuct B6 B3 Fig. 2.k Description Double suction line 2 reciprocating/ scroll compressors for each line 2 fans 1 generic alarm for each compressor 1 generic alarm for condenser HP/LP1/LP2 pressostats pRack M, PRK100M* pRack +040000071 rel. 1.1 - 14.10.2011 30 ENG I/O List Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 L1-Compressor 1 L1-Compressor 2 Fan 1 Fan 2 Alarms output L2-Compressor 1 L2-Compressor 2 Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 HP1 suction pressostat LP1 suction pressostat L1-Compressor 1, generic alarm L1-Compressor 2, generic alarm Common fan overload HP2 suction pressostat LP2 suction pressostat L2-Compressor 1, generic alarm L2-Compressor 2, generic alarm Analog inputs B1 B2 B3 B4 B5 B6 B7 Suction pressure probe L1 Condensing pressure probe Suction pressure probe L2 Suction temperature probe L1 Discharge temperature probe Suction temperature probe L2 External temperature probe 4...20 mA 4...20 mA 4...20 mA NTC HTNTC NTC NTC -0.5...7.0 barg 0.0...30.0 barg -0.5...7.0 barg Tab. 2.v Main parameters Parameter Suction regulation by Suction regulation type Suction setpoint Suction differential Compressors rotation type Refrigerant High suction pressure alarm threshold Low suction pressure alarm threshold Condenser regulation by Condenser regulation type Condenser setpoint Condenser differential High condenser pressure alarm threshold Low condenser pressure alarm threshold Mask index Cab01/ Cbb01 Cab01/ Cbb01 Cab03/ Cbb03 Cab08/ Cbb08 Caf10/ Cbf10 Caf04/ Cbf04 Cae24/ Cbe24 Cae26/ Cbe26 Dab01 Dab01 Dab03 Dab07 Dae01 Dae03 Value PRESSURE NEUTRAL ZONE 3.5,barg 0.3 barg FIFO R404A 6.0 barg 0.0 barg PRESSURE PROPORTIONAL BAND 12.0 barg 2.0 barg 24.0 barg 7.0 barg Tab. 2.w 31 pRack +040000071 rel. 1.1 - 14.10.2011 ENG 2.12 Pre-configuration 12: d-RS3 L1 ID6 Text B9 Tdis Pcond B5 B2 F1 NO4 F2 NO5 F3 NO6 C2 C3 C1 NO3 NO1 NO2 ID5 ID3 ID4 Tsuct Psuct B4 B1 NO7 L2 ID12 Tdis Pcond B8 B6 F1 NO11 F2 NO12 C2 C3 C1 NO10 NO8 NO9 ID11 ID9 ID10 Tsuct Psuct B7 B3 Fig. 2.l Description 2 lines in the same board 3 reciprocating/ scroll compressors for each line 3 fans for each line 1 generic alarm for each compressor 1 generic alarm for each condenser HP/LP pressostats pRack L, PRK100L* pRack +040000071 rel. 1.1 - 14.10.2011 32 F3 NO13 ENG I/O List Digital outputs NO1 NO2 NO3 NO4 NO5 NO6 NO7 L1-Compressor 1 L1-Compressor 2 L1-Compressor 3 L1-Fan 1 L1-Fan 2 L1-Fan 3 Common alarms output Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 L1-Suction HP pressostat L1-Suction LP pressostat L1-Compressor 1, generic alarm L1-Compressor 2, generic alarm L1-Compressor 3, generic alarm L1-Common fan overload L2-Suction HP pressostat L2-Suction LP pressostat L2-Compressor 1, generic alarm L2-Compressor 2, generic alarm L2-Compressor 3, generic alarm L2-Common fan overload Analog inputs B1 B2 B3 B4 B5 B6 B7 B8 B9 L1-Suction pressure probe L1-Condensing pressure probe L2-Suction pressure probe L1-Suction temperature probe L1-Discharge temperature probe L2-Condensing pressure probe L2-Suction temperature probe L2-Discharge temperature probe External temperature probe NO8 NO9 NO10 NO11 NO12 NO13 L2-Compressor 1 L2-Compressor 2 L2-Compressor 3 L2-Fan 1 L2-Fan 2 L2-Fan 3 4...20 mA 4...20mA 4...20 mA NTC HTNTC 4...20mA NTC HTNTC NTC -0.5...7.0 barg 0.0...30.0 barg -0.5...7.0 barg 0.0...30.0 barg Tab. 2.x Main parameters Parameter Suction regulation by Suction regulation type Suction setpoint Suction differential Compressors rotation type Refrigerant High suction pressure alarm threshold Low suction pressure alarm threshold Condenser regulation by Condenser regulation type Condenser setpoint Condenser differential High condenser pressure alarm threshold Low condenser pressure alarm threshold Mask index Cab01/ Cbb01 Cab01/ Cbb01 Cab03/ Cbb03 Cab05/ Cbb05 Caf10/ Cbf10 Caf04/ Cbf04 Cae24/ Cbe24 Cae26/ Cbe26 Dab01/ Dbb01 Dab01 /Dbb01 Dab03/ Dbb03 Dab07/ Dbb07 Dae01/ Dbe01 Dae03/ Dbe03 Value PRESSURE NEUTRAL ZONE 3.5,barg 0.3 barg FIFO R404A 6.0 barg 0.0 barg PRESSURE PROPORTIONAL BAND 12.0 barg 2.0 barg 24.0 barg 7.0 barg Tab. 2.y 33 pRack +040000071 rel. 1.1 - 14.10.2011 ENG 2.13 Pre-configuration 13: d-RS4 L1 Y2 ID17 Text B5 Y1 ID16 Tdis Pcond B4 B2 C1 NO1 ID3 ID4 ID5 C2 NO2 ID6 ID7 ID8 Tsuct B3 C3 NO3 ID9 ID10 ID11 F NO5 ID15 C3 NO4 ID12 ID13 ID14 NO6 Psuct B1 L2 Y2 ID17 Text B5 Y1 ID16 Tdis Pcond B4 B2 C1 NO1 ID3 ID4 ID5 C2 NO2 ID6 ID7 ID8 Tsuct B3 C3 NO3 ID9 ID10 ID11 F NO5 ID15 C3 NO4 ID12 ID13 ID14 NO6 Psuct B1 Fig. 2.m Description 2 lines in separated boards 4 reciprocating/ scroll compressors for each line First compressor with inverter 1 fan stage with inverter for each line 3 alarms for each compressor: thermal overload, oil, HP/LP 1 generic alarm for each condenser HP/LP pressostats 2 pRack M, PRK100M**, one for each line pRack +040000071 rel. 1.1 - 14.10.2011 34 ENG I/O list for each board Digital outputs NO1 NO2 NO3 Compressor 1 Compressor 2 Compressor 3 NO4 NO5 NO6 Compressor 4 Fan Alarms output Digital inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10 ID11 ID12 ID13 ID14 Suction HP pressostat Suction LP pressostat Compressor 1, thermal overload alarm Compressor 1, oil differential alarm Compressor 1, HP/LP alarm Compressor 2, thermal overload alarm Compressor 2, oil differential alarm Compressor 2, HP/LP alarm Compressor 3, thermal overload alarm Compressor 3, oil differential alarm Compressor 3, HP/LP alarm Compressor 4, thermal overload alarm Compressor 4, oil differential alarm Compressor 4, HP/LP alarm ID15 ID16 ID17 Common fan overload Compressor inverter alarm Condenser inverter alarm Analog outputs Y1 Y2 First compressor inverter Common condenser inverter 0...10 Vdc 0...10 Vdc Analog inputs B1 B2 B3 B4 B5 – solo linea 1 Suction pressure probe Condensing pressure probe Suction temperature probe Discharge temperature probe External temperature probe 4...20 mA 4...20 mA NTC HTNTC NTC -0.5...7.0 barg 0.0...30.0 barg Tab. 2.z Main parameters Parameter Suction regulation by Suction regulation type Suction setpoint Suction differential Compressors rotation type Refrigerant High suction pressure alarm threshold Low suction pressure alarm threshold Condenser regulation by Condenser regulation type Condenser setpoint Condenser differential High condenser pressure alarm threshold Low condenser pressure alarm threshold Mask index Cab01/ Cbb01 Cab01/ Cbb01 Cab03/ Cbb03 Cab05/ Cbb05 Caf10/ Cbf10 Caf04/ Cbf04 Cae24/ Cbe24 Cae26/ Cbe26 Dab01 /Dbb01 Dab01 /Dbb01 Dab03/ Dbb03 Dab07/ Dbb07 Dae01/ Dbe01 Dae03/ Dbe03 Value PRESSURE NEUTRAL ZONE 3.5,barg 0.3 barg FIFO R404A 6.0 barg 0.0 barg PRESSURE PROPORTIONAL BAND 12.0 barg 2.0 barg 24.0 barg 7.0 barg Tab. 2.aa 35 pRack +040000071 rel. 1.1 - 14.10.2011 36 PARAMETERS TABLE B.In./Out.a.Statusb.Analog.in. ----Suction Condensing Superheat Suct.temp. Disch.temp. Display description --------- Main screen for single suction line and single condenser --line(display only) Mask index Main screen configuration and the access level. Number of compressors on (with unit ON) Compressor activation percentage (with unit ON) Number of fans on (with unit ON) Fan activation percentage (with unit ON) Unit status (with unit OFF) Hours and minutes Date Suction pressure or temperature Condensing pressure or temperature Superheat Suction temperature Discharge temperature Description --------- --- … … ----------- Default --% --% --- … … … … … … … UOM … … … (**) … (**) … (**) … (**) … (**) Unit OFF from alarm Unit OFF from blackout Unit OFF from supervisor Unit OFF by default Unit OFF by DIN Unit Off from keypad Unit OFF by manual op. 0…12 0…100 0…16 0…100 Values Note:Not all the screens and parameters shown in the table are always visible or can be set, the screens and parameters that are visible or can be set depend on the Below is the table of the parameters that can be displayed on the terminal. The values indicated with ‘---‘ are not Significant or are not set, while the values indicated with ‘…’ may vary according to the configuration, with the possible options visible on the user terminal. A row of ‘…’ means that there are a series of parameters Similar to the previous ones. Main menù reach the parameters corresponding to the suction pressure probe with mask index Bab01, proceed as follows: “Mask index”: indicates the unique address of each screen and consequently the path needed to reach the parameters available on this screen; for example, to 3. 37 Unit status (with unit OFF) Compressor activation percentage (with unit ON, line 1) Compressor activation percentage (with unit ON, line 2) Fan activation percentage (with unit ON, line 1) Fan activation percentage (with unit ON, line 2) --------- --------- --- --------- Suction temperature (line 2) Superheat (line 2) Discharge temperature (line 1) Discharge temperature (line 2) --- --- Superheat (line 1) ----------… … ----------- Unit status (with unit OFF) --- ------------------- --- … … ----------- Number of compressors on (with unit ON, line 2) Compressor activation percentage (with unit ON, line 2) Number of fans on (with unit ON, line 2) Fan activation percentage (with unit ON, line 2) Hours and minutes Date Suction pressure or temperature (line 1) Condensing pressure or temperature (line 1) Suction pressure or temperature (line 2) Condensing pressure or temperature (line 2) Suction temperature (line 1) Number of compressors on (with unit ON, line 1) Compressor activation percentage (with unit ON, line 1) Number of fans on (with unit ON, line 1) Fan activation percentage (with unit ON, line 1) Suction pressure or temperature (line 2) Condensing pressure or temperature (line 2) Superheat (line 2) Suction temperature (line 2) Discharge temperature (line 2) Unit status (with unit OFF) --------L2-Suction L2-Condens. L2-Superheat L2-Suct.temp. L2-Disch.temp --- ------------L1-Suction L1-Condens. L2-Suction L2-Condens. Main screen for dou- L1-Suct.temp. L1-Superheat Condenble suction line and sing double condenser L2-Suct.temp. line, same screen for L2-Superheat both lines (display L1-Disch.temp only) L2-Disch.temp Main screen for double suction line and double condenser line, separate screens for each line(display only) Hours and minutes Date Suction pressure or temperature (line 1) Condensing pressure or temperature (line 1) Superheat (line 1) Suction temperature (line 1) Discharge temperature (line 1) ----L1-Suction L1-Condens. L1-Superheat L1-Suct.temp. L1-Disch.temp % % % % --- … … … … … --% --% … … … … … … … --- --% --% … … … … … --- … … … … … … … … (**) … (**) … (**) … (**) See values on screen for single line 0…100 0…100 0…100 0…100 … (**) … … … (**) … (**) … (**) … (**) … (**) See values on screen for single line 0…12 0…100 0…16 0…100 … (**) … (**) … (**) … (**) … (**) See values on screen for single line 0…12 0…100 0…16 0…100 … … … (**) … (**) … (**) … (**) … (**) 38 Display description Aa05 (display only) Aa04 (display only) Aa03 (display only) Aa02 (display only) Aa01 (display only) Effective suction pressure set point (with compensation applied, line 1) Time remaining to next compressor start (line 1) Capacity delivered by compressor 1 on line 1 (a ''!'' to the right of the value means that some form of compressor capacity override is active, e.g. times, alarms, start-up procedure) … Capacity delivered by compressor 12 (line 1) Suction temperature (line 1) Superheat (line 1) … C12 Temperature Superheat C01 Compressor control type (line 1) Setpoint C01, C02, …C12 --- Control status (according to the type of control set, line 1) … ------- --- …(**) --- Neutral zone …(**) …(**) ----…(**) …(**) --- Reg.type Reg.status Differential Pressure Sat.temp. Act.setpoint Differential Actual/req. Act.setpoint ----- Default ------- --- … … ------------------- Suction pressure (line 1) Saturated suction temperature (line 1) Effective set point for pressure control (with compensation applied, line 1) Control differential for pressure control (line 1) Suction pressure (line 1) Saturated suction temperature (line 1) Effective set point for temperature control (with compensation applied, line 1) Control differential for temperature control (line 1) Capacity delivered/capacity required for suction line (line 1) Description Compressor activation percentage (with unit ON, line 1) Compressor activation percentage (with unit ON, line 2) Fan activation percentage (with unit ON, line 1) A.Unit status Pressure Sat.temp. Mask index Unit status (with unit OFF) ------- Hours and minutes Date Suction pressure or temperature (line 1) Suction pressure or temperature (line 2) Condensing pressure or temperature Suction temperature (line 1) Discharge temperature (line 1) Superheat (line 1) Suction temperature (line 2) Discharge temperature (line 2) Superheat (line 2) --- --Suction: L1 L2 Condensing L1-Suct.temp. Main screen for double suction line L1-Disch.temp L1-Superheat and single condenser L2-Suct.temp. line, L2-Disch.temp (display only) L2-Superheat … % … … % … s --- --- … … … … … % … … … UOM % % % --- … … … … … … … … … … … … 0…100 …(**) …(**) 0…100 …(**) …(**) …(**) …(**) …(**) 0/0 …100/100 Stop Increas Operating Decrease Timings Standby Allarms Proportional band Neutral zone …(**) 0…32000 …(**) … (**) … (**) Values … … … (**) … (**) … (**) … (**) … (**) … (**) … (**) … (**) … (**) See values on screen for single line 0…100 0…100 0…100 39 Aa23 (display only) Aa22 (display only) Aa21 (display only) Aa20 (display only) Aa16 (display only) Aa15 (display only) Aa13 (display only) Aa11 (display only) Mask index Oil status Control differential for temperature control (line 1) Capacity delivered/capacity required for condenser line (line 1) Control status (according to the type of control set, line 1) Condenser control type (line 1) Condenser control effective set point (with compens. applied, line 1) Power output of fan 1 on line 1 (a ''!'' to the right of the value means that some form of power override is active) … Power output of fan 8 on line 1 (a ''!'' to the right of the value means that some form of power override is active) Differential Actual/req. Status Reg.type Setpoint F8 … F1 Digital ScrollTM compressor time count (line 1) Digital ScrollTM compressor status (line 1) Digital ScrollTM valve status(line 1) Digital ScrollTM compressor capacity required (line 1) Digital ScrollTM compressor effective capacity (line 1) Condensing pressure (line 1) Saturated condensing temperature (line 1) Effective set point for pressure control (with compens. applied, line 1) Control differential for pressure control (line 1) Condensing pressure (line 1) Saturated condensing temperature (line 1) Effective set point for temperature control (with compe. applied, line 1) Digital Scroll compressor operating status (line 1) Countdown Compr. Valve Requested cap. Current capac. Pressure Sat.temp. Act.setpoint Differential Pressure Sat.temp. Act.setpoint Status TM Digital ScrollTM compressor oil dilution status (line 1) Discharge temperature Cap.reduction Oil sump temp. Liq.inj.6: DO … Liq.inj.1: DO Description Discharge temperature, compressor 1 (line 1) … Discharge temperature, compressor 6 (line 1) Number of digital output associated and status of liquid injection/ economizer (*) compressor 1 (line 1) … Number of digital output associated and status of liquid injection/ economizer (*) compressor 6 (line 1) Digital ScrollTM compressor discharge temperature (line 1) Digital ScrollTM compressor capacity reduction in progress (line 1) Digital ScrollTM compressor oil sump temperature (line 1) Display description Disch.1 … Disch.6 --- … % … … % --- --- --- % … s ----% % … … … … … … … --- … … … … … UOM … … … … (**) Neutral zone --- --- … (**) --------------… (**) … (**) ----… (**) --- --- --- --- … --- Default --… --- Off by time On by time Mod. manual In pump down ON / OFF ON / OFF 0…100 … 0…100 0/0 …100/100 Stop Operating Increase Timings Decrease Alarms Stand-by Proportional band Neutral zone …(**) … (**) Off Start up On Alarm 0…999 OFF / ON OFF / ON 0…100 0…100 … (**) … (**) … (**) … (**) … (**) … (**) … (**) Ok / Diluite …(**) NO / YES …(**) 0…29 … 0…29 Values …(**) … …(**) 40 Aa45 (display only) Aa43 (display only) Aa41 (display only) Aa05 (display only) Aa34 (display only) Aa33 (display only) Aa32 (display only) Aa31 (display only) Aa25 (display only) Aa24 (display only) Mask index Display description Effective suction pressure set point (with compensation applied, line 2) Time remaining to next compressor start (line 2) Capacity delivered by compressor 1 on line 2 (a ''!'' to the right of the value means that some form of compressor capacity override is active, e.g. times, alarms, start-up procedure) … Capacity delivered by compressor 12 (line 2) Suction temperature (line 2) Superheat (line 2) Discharge temperature, compressor 1 (line 2) … Discharge temperature, compressor 6 (line 2) N.ro of digital output associated and status liquid injection com.1 (line 2) … Number of digital output associated and status liquid injection compr. 6 (line 2) Digital ScrollTM compressor discharge temperature (line 2) Digital ScrollTM compressor capacity reduction in progress (line 2) Digital ScrollTM compressor oil sump temperature (line 2) Digital ScrollTM compressor oil dilution status (line 2) Discharge temperature Cap.reduction Oil sump temp. Oil status Liq.inj.6: DO … C12 Temperature Superheat Disch.1 … Disch.6 Liq.inj.1: DO … C01 Compressor control type (line 2) Setpoint C01, C02, …C12 Control status (according to the type of control set, line 2) Description Power output of fan 9 on line 1 (a ''!'' to the right of the value means that some form of power override is active) … Power output of fan 16 on line 1 (a ''!'' to the right of the value means that some form of power override is active) Discharge temperature (line 1) Outside temperature (line 1) Suction pressure (line 2) Saturated suction temperature (line 2) Effective set point for pressure control (with compensation applied, line 2) Control differential for pressure control (line 2) Suction pressure (line 2) Saturated suction temperature (line 2) Effective set point for temperature control (with compensation applied, line 2) Control differential for temperature control (line 2) Capacity delivered/capacity required for suction line (line 2) Reg.type Status Differential Actual/req. Act.setpoint Differential Pressure Sat.temp. Act.setpoint Discharge temperature External temperature Pressure Sat.temp. F16 … F9 … --- … … --- --- … % … … … … … … … % … s --- --- … % … … … … … … --------… ----… --- …(**) --- Neutral zone --- …(**) --- …(**) …(**) ----- …(**) … … … … % ----------- … % UOM … --- Default …(**) NO / SI …(**) Ok / Dilute 0…29 … 0…100 …(**) …(**) …(**) … …(**) 0…29 … 0…100 ON / OFF ON / OFF …(**) 0/0 …100/100 Stop Operating Increas Timings Decrease Alarms Standby Proportional band Neutral zone …(**) 0…32000 …(**) …(**) …(**) …(**) …(**) …(**) …(**) … (**) … (**) 0…100 … 0…100 Values 41 Aa55 (display only) Aa54 (display only) Aa53 (display only) Aa52 (display only) Aa51 (display only) Aa50 (display only) Aa46 (display only) Mask index Condenser control effective set point (with compensat. applied, line 2) Power output of fan 1 on line 2 (a ''!'' to the right of the value means that some form of power override is active) … Power output of fan 8 on line 2 (a ''!'' to the right of the value means that some form of power override is active) Power output of fan 9 on line 2 (a ''!'' to the right of the value means that some form of power override is active) … Power output of fan 16 on line 2 (a ''!'' to the right of the value means that some form of power override is active) Discharge temperature (line 2) Outside temperature (line 2) Discharge temperature External temperature F16 … F9 F8 … F1 Condenser control type (line 2) Setpoint Control status (according to the type of control set, line 2) Reg.type Reg.status Differential Actual/req. Act.setpoint Differential Pressure Sat.temp. Act.setpoint Digital ScrollTM compressor time count (line 2) Digital ScrollTM compressor status (line 2) Digital ScrollTM valve status(line 2) Digital ScrollTM compressor capacity required (line 2) Digital ScrollTM compressor effective capacity (line 2) Condensing pressure (line 2) Saturated condensing temperature (line 2) Effective set point for pressure control (with compensation applied, line 2) Control differential for pressure control (line 2) Condensing pressure (line 2) Saturated condensing temperature (line 2) Effective set point for temperature control (with compensation applied, line 2) Control differential for temperature control (line 2) Capacity delivered/capacity required for condenser line (line 2) … … % ------- … % % … … --- --- … … % --- --- --- … % … … … … … s ----% % … … --- UOM …(**) Neutral zone --- …(**) --- …(**) …(**) ----- …(**) --------------- --- Digital ScrollTM compressor operating status (line 2) Status Countdown Compr. Valve Requested cap. Current capac. Pressure Sat.temp. Default Description Display description Off da tempo On da tempo Mod.manuale In pump down …(**) …(**) 0…100 … 0…100 0…100 … 0…100 …(**) 0/0 …100/100 Stop Increas Operating Timings Decrease Standby Alarms Proportional band Neutral zone …(**) …(**) …(**) …(**) …(**) …(**) Values Off Start up On Alarm 0…999 OFF / ON OFF / ON 0…100 0…100 … (**) … (**) 42 Aa71 (display only) Aa70 (display only) Aa62 (display only) Aa61 (display only) Aa60 (display only) Mask index Status required for the screw compressor 1 with stepped modulation Status, req. Effective status of screw compressor 2 Status required for the screw compressor 2 Countdown for minimum on time screw comp. 2 Countdown for minimum off time or wait between successive starts screw comp. 2 Countdown for next step activation screw comp. 2 Envelope zone for screw compressor 1 Maximum duration allowed in the zone Countdown Maximum capacity allowed in the zone Start-up status for screw compressor 1 Number of restarts Status, req. Minimum on time Startup status N° startup restart Next step Zone Max admit.time Countdown Max admit.power Min.off/starts --- --- --- --- --- --- Default --- --- ----- --- --- --- --- Screw comp. 1 off time with continuous capacity modulation --Countdown for minimum off time or wait between successive starts --screw comp. 1 with continuous capacity modulation Countdown to start screw comp. 1 with continuous capacity modulation --- Effective status of screw compressor 1 with continuous capacity modulation Status,curr. Min.on countdown Max.pow.countdown Shut down countd. Status Next step Min.off/starts Countdown for minimum on time screw comp. 1 with stepped modulation Countdown for minimum off time or wait between successive starts screw comp. 1 with stepped modulation Countdown for next step activation screw comp. 1 with stepped modulation Effective status of screw compressor 1 with stepped modulation Status,curr. Minimum on time Description Display description --- --- s --min s % s s --- --- s s s --- s s s --- --- UOM Stage 2 Stage 3 Stage 4 Stage 2 Stage 3 Stage 4 Shut down Stage 2 Stage 3 Stage 4 Stage 2 Stage 3 Stage 4 0…999 0…14 0…999 0…32000 0…100 Off Compressor on Intermediate interval Final interval Compressor off RestartAlarm 0…99 0…999 0…999 Off Start up Stage1 Off Start up Stage1 0…999 0…999 Off Start up Norm. operating 0…999 0…999 0…999 0…999 Values Off Start up Stage1 Off Start up Stage1 43 Aaav (display only) Aaau (display only) Aaat (display only) Aaas (display only) Aaar (display only) … Aaan (display only) Aa72 (display only) Mask index Description Type of error in envelope definition Type of alarm activated Type of error in selection of predefined envelope Control variable value for generic stage function 1 Enabling variable status for generic stage function 1 Control set point for generic stage function 1 Control differential for generic stage function 1 Control mode for generic stage function 1 (direct or reverse) Status of generic stage function 1 … Control variable value for the generic stage function 5 Enabling variable status for the generic stage function 5 Control set point for the generic stage function 5 Control differential for the generic stage function 5 Control mode for the generic stage function 5 (direct or reverse) Status of generic stage function 5 Control variable value for generic modulating function 1 Enabling variable status for generic modulating function 1 Control set point for generic modulating function 1 Control differential for generic modulating function 1 Control mode for generic modulating function 1 (direct or reverse) Status of generic modulating function 1 Control variable value for generic modulating function 2 Enabling variable status for generic modulating function 2 Control set point for generic modulating function 2 Control differential for generic modulating function 2 Control mode for generic modulating function 2 (direct or reverse) Status of generic modulating function 2 Control variable status for generic alarm function 1 Enabling variable status for generic alarm function 1 Type of alarm for generic alarm function 1 Control differential for generic alarm function 1 Status of generic alarm function 1 Control variable status for generic alarm function 2 Enabling variable status for generic alarm function 2 Type of alarm for generic alarm function 2 Control differential for generic alarm function 2 Status of generic alarm function 2 Display description Err.code Al.code Envel.def.error code Reg.var. Enable Setpoint Differential Mode Status … Reg.var. Enable Setpoint Differential Mode Status Reg.variable Enable Setpoint Differential Mode Status Reg.variable Enable Setpoint Differential Mode Status Reg.variable Enable Type Delay time Status Reg.variable Enable Type Delay time Status ------------… --------------------------------------------------------- --- --- --- Default … --… … ----… … --… … ----… --… … --% … --… … --% ------s --------s --- --- --- --- UOM Values No error Env. def. inconsist. No Alarm Max time elapsed Zone not allowed Max. no. of restarts No error Comp. not supported Gas type not allowed …(**) Not active / active …(**) …(**) D, R Not active / active … …(**) Not active / active …(**) …(**) D, R Not active / active …(**) Not active / active …(**) …(**) D, R 0.0…100.0 …(**) Not active / active …(**) …(**) D, R 0.0…100.0 Not active / active Not active / active Light / Serious 0…9999 Not active / active Not active / active Not active / active Light / Serious 0…9999 Not active / active 44 Ab01 (display only) Aaa3 (display only) Aaa2 (display only) Aaa1 (display only) Aaaz (display only) Aaay (display only) Aaax (display only) Aaaw (display only) Mask index Diff. Actual.setpoint User setp. Cond.temp. Liquid Temp. Subcooling Status Cond.temp. Liquid Temp. Subcooling Status Time fan 100% Status Ext.temp. Ext.temp.thr. Time fan 100% Status Status Heat recl. temp. An.OUT modulat. HR Prevent Status Heat recl. temp. An.OUT modulat. HR Prevent Status Ext.temp. Ext.temp.thr. TB4: --:-- -> --:-- … TB1: --:-- -> --:-- Display description Weekday Description Day of the week Enabling and definition of time band 1: start hour and minutes, end hour and minutes for the generic scheduling function … Enabling and definition of time band 4: start hour and minutes, end hour and minutes for the generic scheduling function Status of generic scheduling function Status of heat recovery function (line 1) Heat recovery temperature (line 1) Status of modulating heat recovery valve output (line 1) Status of prevention via heat recovery (line 1) Status of heat recovery function (line 2) Heat recovery temperature (line 2) Status of modulating heat recovery valve output (line 2) Status of prevention via heat recovery (line 2) Status of ChillBooster device (line 1) Outside temperature (line 1) ChillBooster activation threshold (line 1) Number of minutes elapsed with fans at 100/number of minutes allowed (line 1) Status of ChillBooster device (line 2) Outside temperature (line 2) ChillBooster activation threshold (line 2) Number of minutes elapsed with fans at 100/number of minutes allowed (line 1) Saturated condensing temperature (line 1) Liquid temperature (line 1) Subcooling (line 1) Status of subcooling function (line 1) Saturated condensing temperature (line 2) Liquid temperature (line 2) Subcooling (line 2) Status of subcooling function (line 2) User-defined set point for suction pressure control, proportional control (line 1) Effective set point for suction pressure control, proportional control (with compensation applied, line 1) Suction pressure control differential, proportional control (line 1) … --- --- --- … … … … … … --… … … --- min ------------------- --… … min --------- ----… ------… ------… … … ------------------------- --- … --… UOM --- Default --- …(**) …(**) …(**) …(**) …(**) …(**) Open / Closed …(**) …(**) …(**) Open / Closed 0…999/0…999 OFF / ON …(**) …(**) 0…999/0…999 Not active / active OFF / ON …(**) 0.0…100.0 OFF / ON OFF / ON …(**) 0.0…100.0 OFF / ON OFF / ON …(**) …(**) … … … Values Monday, …, Sunday 45 Ab07 (display only) Ab06 (display only) Ab05 (display only) Ab04 (display only) Ab03 (display only) Ab02 (display only) Mask index Display description Diff. Actual.setp. User setp. Decr.diff. Incr.diff. Neutral zone Actual.setp. User setp. Diff. Actual.setp. User setp. Decr.diff. Incr.diff. Neutral zone Actual.setp. User setp. Diff. Actual.setp. User setp. Decr.diff. Incr.diff. Neutral zone Actual.setpoint User setp. Description User-defined set point for suction pressure control, proportional control (line 1) Effective set point for suction pressure control, proportional control (with compensation applied, line 1) Neutral zone for suction pressure control (line 1) Increase differential for suction pressure control, neutral zone control (line 1) Decrease differential for suction pressure control, neutral zone control (line 1) User-defined set point for suction pressure control, proportional control (line 2) Effective set point for suction pressure control, proportional control (with compensation applied, line 2) Suction pressure control differential, proportional control (line 2) User-defined set point for suction pressure control, proportional control (line 2) Effective set point for suction pressure control, proportional control (with compensation applied, line 2) Neutral zone for suction pressure control (line 2) Increase differential for suction pressure control, neutral zone control (line 2) Decrease differential for suction pressure control, neutral zone control (line 2) User-defined set point for condensing pressure control, proportional control (line 1) Effective set point for condensing pressure control, proportional control (with compensation applied, line 1) Condensing pressure control differential, proport.control (line 1) User-defined set point for condensing pressure control, proportional control (line 1) Effective set point for condensing pressure control, proportional control (with compensation applied, line 1) Neutral zone for condensing pressure control (line 1) Increase differential for the condensing pressure control, neutral zone control (line 1) Decrease differential for the condensing pressure control, neutral zone control (line 1) User-defined set point for condensing pressure control, proportional control (line 2) Effective set point for condensing pressure control, proportional control (with compensation applied, line 2) Condensing pressure control differential, proportional control (line 2) … … ----- … … … … … … … --- --- --- --- --- --- --- … … ----- … … ----- … … … … … … … … … --- --- --- --- --- --- --- --- --- … … ----- UOM Default …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) …(**) Values 46 Ac07 Ac06 Ac04 Ac03 Ac02 Ac01 Ab12 Ab13 Ab14 Ab15 Ab08 (display only) Mask index OFF Off from keypad --- On-Off from keypad (line 1) Unit status (display only) --L1: L2: ----Enable of unit OnOff By digit input By supervisor By black out Unit on delay after blackout Enable of unit OnOff By digit input By supervisor By black out Unit on delay after blackout NO System on delay after black out (line 2) 0 NO NO NO Enable unit On/Off from digit input (line 2) Enable unit On/Off from supervisor (line 2) Enable unit On/Off from black out (line 2) 0 System on delay after black out (line 1) NO NO Enable unit On/Off from digit input (line 1) Enable unit On/Off from supervisor (line 1) Enable unit On/Off from black out (line 1) OFF OFF On-Off from keypad (line 1) On-Off from keypad (line 2) s ----- --- s ----- --- ----- --- Off from keypad --- … … … … … … … … Unit status (display only) 3.5 barg 12.0 barg 3.5 barg 12.0 barg --- --- --- --- … --- Status Setpoint Setpoint Setpoint Setpoint Decr.diff. Incr.diff. Neutral zone Actual setp. UOM Default Description User-defined set point for condensing pressure control, proportional control (line 2) Effective set point for condensing pressure control, proportional control (with compensation applied, line 2) Neutral zone for condensing pressure control (line 2) Increase differential for the condensing pressure control, neutral zone control (line 2) Decrease differential for the condensing pressure control, neutral zone control (line 2) Setpoint without compensation (suction line 1) Setpoint without compensation (condenser line 1) Setpoint without compensation (suction line 2) Setpoint without compensation (condenser line 2) Display description User setp. Off by default Off by DIN Off from keypad Manual op. Prevent HP 0…999 NO / YES NO / YES NO / YES 0…999 NO / YES NO / YES NO / YES OFF / ON OFF / ON …(See above Ac01) …(**) …(**) …(**) …(**) Waiting.. Unit On/ Off from alarm Off from blackout Off from BMS Off by default OFF / ON …(**) …(**) …(**) …(**) …(**) Values 47 Display Description Description Default UOM Values B.Ingr./Usc. (the I/Os available depend on the selected configuration, the following are just some examples. For the complete list of I/O positions available see Appendix A.5) DI Alarm 1 for compressor 1 DI position (line 1) 03 -----, 01…18, B1…B10 (****) Status (display only) Status of alarm 1 for compressor 1 DI (line 1) ----Chiuso / Aperto Baa02 Logic Logic of alarm 1 for compressor 1 DI (line 1) NC --NC / NO Function (display only) Alarm 1 for compressor 1 function status (line 1) ----Not active / active … … … … … … Bab01 --Suction pressure probe position (line1) B1 -----, B1…B10 (****) --Suct pressure probe type (line 1) ---4...20mA --0-1V - 0-10V- 4...20mA- 0-5V --- (display only) Suction pressure value (line 1) --… …(**) Bab01 Upper value Suct pressure maximum value (line 1) 7.0 barg … …(**) Lower value Suct pressure minimum value (line 1) -0,5 barg … …(**) Calibration Suction pressure probe adjustment (line 1) 0.0 barg … …(**) … … … … … … Line relay DO Compressor 1 line DO position and status (On/Off ) display (line 1) … -----, 01…29 (****) Part winding DO/Star Compressor 1 part winding or star DO position and status (On/Off ) … -----, 01…29 (****) Bac02 relay DO (*) display (line 1) ---/ Delta relay DO (*) Compressor 1 delta DO position and status (On/Off ) display (line 1) … -----, 01…29 (****) DO Compressor 1 unloader 1 DO position (line 1) … -----, 01…29 (****) Status (display only) Status for compressor 1 unloader 1 DO (line 1) ----Closed / Open Bac03 Logic Logic for compressor 1 unloader 1 DO (line 1) NO --NC / NO Function (display only) Compressor 1 unloader 1 function status (line 1) ----Not active / active … … … … … … AO Compressor modulating device AO position (line 1) 0 -----, 01…06 (****) Bad01 Status (display only) Modulating device output value (line 1) 0 % 0.0…100.0 … … … … … … Suction L1 Suction line 1 in manual mode DIS --DIS / AB Suction L2 Suction line 2 in manual mode DIS --DIS / AB Bb01 Discharge L1 Condenser line 1 in manual mode DIS --DIS / AB Discharge L2 Condenser line 2 in manual mode DIS --DIS / AB Timeout Manual mode duration after last key pressed 10 min 0…500 Compressor 1 Manual stages request for compressor 1 (line 1) OFF / ON 3 STAGES (*) Bba02 OFF --Force to 2 STAGES(*) 4 STAGES (*) … … … … … … Compressor 12 Manual stage request for compressor 12 (line 1) OFF / ON 3 STAGES (*) Bba16 OFF --Force to 2 STAGES(*) 4 STAGES (*) Oil cool pump1 Manual operating status for oil cooling pump 1 (line 1) OFF --OFF / ON Force to Bba17 Oil cool pump2 Manual operating status for oil cooling pump 2 (line 1) OFF --OFF / ON Force to Oil cool fan Manual operating status for oil cooling fan (line 1) Bba18 OFF --OFF / ON Force to Compressor 1 Manual stage request for compressor 1 (line 2) OFF / ON 3 STAGES (*) Bba20 OFF --Force to 2 STAGES (*) 4 STAGES (*) … … … … … Mask index 48 Bc01 Bbb12 Bbb11 Bbb10 Bbb09 Bbb08 Bbb07 Bbb06 Bbb05 Bba74 Bba73 Bba72 … Bba57 Bba55 Bba54 Bba53 … Bba38 Bba37 Bba35 Bba34 Mask index Display Description Compressor 12 Force to Oil cool pump1 Force to Oil cool pump2 Force to Oil cool fan Force to Fan1 force … Fan16 force Heat reclaim pump force ChillBooster force Fan1 force … Fan16 force Heat reclaim pump force ChillBooster force Compressor 1 Force to Oil cool pump Force to Compressor 1 Force to Oil cool pump Force to Fan1 Force to Heat reclaim pump force Fan1 Force to Heat reclaim pump force Test Dout Timeout Enable DO test mode Test mode duration after last button pressed Manual request for heat recovery pump (line 2) Manual continuous capacity request for fan 1 (line 2) Manual request for heat recovery pump (line 1) Manual continuous capacity request for fan 1 (line 1) Manual request for oil cooling pump (line 2) Manual continuous capacity request for compressor 1 (line 2) Manual request for oil cooling pump (line 1) Manual continuous capacity request for compressor 1 (line 1) Manual operating status for ChillBooster (line 2) Manual operating status for heat recovery pump (line 2) … Manual operating status for fan 16 (line 2) Manual operating status for fan 1 (line 2) Manual operating status for ChillBooster (line 1) Manual operating status for heat recovery pump (line 1) … Manual operating status for fan 16 (line 1) Manual operating status for fan 1 (line 1) Manual operating status for oil cooling fan (line 2) Manual operating status for oil cooling pump 2 (line 2) Manual operating status for oil cooling pump 1 (line 2) Description Manual stage request for compressor 12 (line 2) NO 10 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 OFF OFF OFF … OFF OFF OFF OFF … OFF OFF OFF OFF OFF Default --min % % % % % % % % --- --- --- … --- --- --- --- … --- --- --- --- --- UOM NO / YES 0…500 0.0…100.0 0.0…100.0 0.0…100.0 0.0…100.0 0.0…100.0 0.0…100.0 0.0…100.0 0.0…100.0 OFF / ON OFF / ON OFF / ON … OFF / ON OFF / ON OFF / ON OFF / ON … OFF / ON OFF / ON OFF / ON OFF / ON Values OFF / ON 3 STAGES (*) 2 STAGES (*) 4 STAGES (*) 49 … DO29 … Display Description Mask index Description Description Enable AO test mode Test mode duration after last button pressed DO 1 logic for test DO 1 value for test … DO 29 logic for test DO 29 value for test AO 1 value for test … AO 6 value for test Default Default NO 10 NO OFF … NO OFF 0.0 … 0.0 UOM UOM --min ----… ------… --- Values Values NO / SI 0…500 NO / NC OFF/ ON … NO / NC OFF / ON 0.0…100.0 … 0.0…100.0 C.Compressors (*) (The I/Os available depend on the selected configuration, the following are just some examples. For the complete list of I/O positions available see Appendix A.5) DI Alarm 1 for compressor 1 DI position (line 1) 03 -----, 01…18, B1…B10 (****) Status (display only) Status of alarm 1 for compressor 1 DI (line 1) ----Closed / Open Caa01 Logic Logic of alarm 1 for compressor 1 DI (line 1) NC --NC / NO Function (display only) Alarm 1 for compressor 1 function status (line 1) ----Not active / active … … … … … … Line relay DO Compressor 1 part winding or star DO position and status (On/Off ) … -----, 01…29 (****) display (line 1) Caa08 Part winding DO/Star Compressor 1 delta DO position and status (On/Off ) display (line 1) … -----, 01…29 (****) relay DO (*) ---/ Delta relay DO (*) Compressor 1 line DO position and status (On/Off ) display (line 1) … -----, 01…29 (****) DO Unloader 1 for compressor 1 DO position (line 1) … -----, 01…29 (****) Status (display only) Status of unloader 1 for compressor 1 DI (line 1) ----Closed / Open Caa09 Logic Logic of unloader 1 for compressor 1 DI (line 1) NC --NC / NO Function (display only) Unloader 1 for compressor 1 function status (line 1) ----Not active / active … … … … … … AO Compressor modulating device AO position (line 1) 0 -----, 01…06 (****) Caa14 Status (display only) Modulating device output value (line 1) 0 % 0.0…100.0 … … … … … … --Suction pressure probe position (line1) B1 -----, B1…B10 (****) --Suct pressure probe type (line 1) ---0-1V 4...20mA --0-10V 4...20mA Caaal 0-5V --- (display only) Suction temperature value (line 1) --… …(**) Upper value Suct pressure maximum limit (line 1) 7.0 barg … …(**) Lower value Suct pressure minimum limit (line 1) -0,5 barg … …(**) Calibration Suction pressure probe adjustment (line 1) 0.0 barg … …(**) … … … … … … AO6 Bcb10 … Bcb12 Bca26 Bca10 AO1 Display Description Test Aout Timeout DO1 Bc02 Mask index 50 Cad03 Cad02 Cad01 Cac14 Cac13 Cac11 … Cac01 Cab13 Cab12 Cab09/Cab11 (**) Cab08/Cab10 (**) Cab05/Cab7 (**) Cab04/Cab6 (**) Cab03 Cab02 Cab01 Mask index Compressor setpoint lower limit (line 1) Compressor setpoint higher limit (line 1) Compressor setpoint (line 1) Type for proportional control (line 1) Integral time for proportional control (line 1) Differential for proportional control (line 1) Neutral zone control differential (line 1) Neutral zone control differential for device activation (line 1) Neutral zone control differential for device deactivation (line 1) Enable capacity immediate decreasing to 0 (line 1) Threshold for capacity decreasing to 0 (line 1) Minimum time to increase capacity request to 100%, Neutral zone control (suction line 1) Maximum time to increase capacity request to 100%, Neutral zone control (suction line 1) Minimum time to decrease capacity request to 0%, Neutral zone control (suction line 1) Maximum time to decrease capacity request to 0%, Neutral zone control (suction line 1) Compressor 1 operating hours (line 1) Minimum Maximum Setpoint Reg.type Integral time Differential NZ diff. Activ.diff. Deact.diff. En.force off power Setp.for force off Power load to 100% min time Power load to 100% max time Power unload to 0% min time Power unload to 0% max time Working hours Compressor 1 (Check in…) Compressor 2 (Check in…) … Working hours Compressor 11 (Check in…) Compressor 12 (Check in…) Compressor threshold working hours Compressor hours reset Enable suction setpoint compensation Enable compensation by analog IN Winter offset Closing offset Enable setpoint compensation by scheduler Offset applied for Winter period Offset applied for closing period Enable scheduler setpoint compensation (suction line 1) Enable setpoint compensation by probe (suction line 1) Reset compressor operating hours (line 1) Enable setpoint compensation (suction line 1) Compressor 11 remaining operating hours (line 1) Compressor 12 operating hours (line 1) Compressor 12 remaining operating hours (line 1) Compressor maintenance threshold hours (line 1) Compressor 1 remaining operating hours (line 1) Compressor 2 operating hours (line 1) Compressor 2 remaining operating hours (line 1) … Compressor 11 operating hours (line 1) Description Compressor control by temperature or pressure (line 1) Compressor control type (line 1) Display Description Regulation by Regulation type NO 0.0 0.0 NO --- … … --- --- NO h --- N 88000 h h h h --… --… h h h … h … --… … --- s s 30 180 s s 15 90 … … … --s … … … … --… --- UOM --- …(**) …(**) …(**) PROPORT. 300 …(**) …(**) …(**) …(**) NO …(**) Neutral zone Default PRESSURE NO / YES -999,9…999,9 -999,9…999,9 NO / YES NO / YES NO / YES 0…9999999 0…999999 0…999999 0…999999 0…999999 0…999999 0…999999 0…999999 … 0…999999 0…9999 0…9999 0…9999 0…9999 Values PRESSURE TEMPERATURE Proportional band Neutral zone …(**) …(**) …(**) PROPORTIONAL PROP.+INT. 0…999 …(**) …(**) …(**) …(**) NO / YES …(**) 51 Cae24 … Cae04 Cae03 Cae02 Cae01 Cad10 Cad09 Cad08 Cad06 Cad05 Cad04 Mask index 0 High suction pressure/temperature alarm threshold --… ASSOLUTO …(**) s s ----… --- --- --- min … … … --- … … … --- ----- --- --- 0 0 AUT. GRAVE … Activation delay for compressor alarm 1 during working (line 1) Activation delay for compressor alarm 1 at start up (line 1) Type of reset for compressor alarm 1 (line 1) Type of priority for compressor alarm 1 (line 1) … Type of high suction pressure/temperature alarm threshold Activ.delay Start up delay Reset Priority … Suction pressure/temperature high alarm Threshold … 1/4 (*) 0 …(**) …(**) …(**) NO ------- Selection of the first compressor alarm description: Rotation, Oil warning (line 1) … Selection of the first compressor alarm description: Generic, Overload, High pressure, Low pressure, Oil (line 1) Reduction time when supervisor is offline for floating setpoint (suction line 1) Number of alarms for each compressor (line 1) Maximum delta admitted for floating setpoint (suction line 1) Minimum compressor floating setpoint settable (line 1) Max compressor floating setpoint settable (line 1) Compensation value (line 1) Maximum value of compensation (line 1) Minimum value of compensation (line 1) Enable floating setpoint (suction line 1) Alarm1 description (*) Number of alarms for each compressor Alarm1 description --- (display only) max min Enable floating suction setpoint Maximum floating setpoint Minimum floating setpoint Max.setpoint variation admitted Offline decreasing time Change set by DI ----- --- … --- … … --… UOM Default Enable setpoint compensation by digital input (suct/cond line 1) NO Position of the probe for suction pressure setpoint compensation (line1) --Type of the probe for suction pressure setpoint compensation (line1) 4...20mA Copy settings to other days Copy to Changes … TB4: --:-- -> --:-- Description Day of the week Time band 1 enabling and definition: start hour and minute, end hour and minute (suction line 1) … Time band 4 enabling and definition: start hour and minute, end hour and minute (suction line 1) Time band change action Display Description Activ.Time Bands TB1: --:-- -> --:-- …(**) ABSOLUTE / RELATIVE (Not available) (Not selected) (Selected) (Not available) (Not selected) (Selected) 0…999 0…999 AUT. / MAN. Light / Serious … 0…4/7 (*) 0…999 …(**) …(**) …(**) NO / YES --CONFIRM&SAVE LOAD PREVIOUS CLEAR ALL MONDAY…SUNDAY; MON-FRI; MON-SAT; SAT&SUN; ALL DAYS NO / YES ---, B1…B10 (****) ---0-1V - 0-10V- 4...20mA- 0-5V -99.9…99.9 -99.9…99.9 -99.9…99.9 … … … Values LUN, MAR, ...DOM 52 Caf08 Caf07 Caf06 Caf05 Caf04 Caf03 Caf02 Cae40 Cae30 Cae29 Cae28 Cae27 Cae26 Cae25 Mask index Star time Star line delay Star delta delay Partwinding delay Min on time Min off time Min time to start same compressor Ignition type Compressors number Cmp1,… Refrigerant type High suction pressure/temperature alarm delay Type of low suction pressure/temperature alarm threshold Alarm delay Suction pressure/temperature low alarm Threshold Alarm diff. Alarm delay Enable oil temperature alarm management (*) Enable discharge temp. alarm management (*) Low superheat alarm threshold Alarm diff. Switch OFF comp. Reset Alarm delay Time of semi-automatic alarm evaluation N° of reties before alarm becomes manual Switch off comp.1 Reset Alarm delay Compressors type Star relay run time Delay between star and line relay Delay between star and delta relay Partwinding delay Type of compressors start up Minimum compressor on time (line 1) Minimum compressor off time (line 1) Minimum time between same compressor starts (line 1) Number of compressors (line 1) Enable compressors (line 1) Type of refrigerant (suction Line 1) Enable compressor 1 off for compressor inverter warning (line 1) Type of compressor inverter warning reset (line 1) Compressor inverter warning activation delay (line 1) Type of compressors (line 1) Low superheat alarm differential (line 1) Enable compressor off for low superheat alarm (line 1) Type of low superheat alarm reset (line 1) Low superheat alarm delay (line 1) Time of semi-automatic alarm evaluation for screw compressors out of envelope (line 1) Number of retries before alarm becomes manual (line 1) Threshold for low superheat alarm (line 1) Enable Digital Scroll discharge temperature alarm (line 1) Low suction pressure/temperature alarm threshold Low suction pressure/temperature alarm differential Low suction pressure/temperature alarm delay Enable Digital Scroll oil temperature alarm (line 1) Description High suction pressure/temperature alarm differential Display Description Alarm diff. 0 0 0 0 ms ms ms ms --- s 360 DIRECT s s --30 120 R404A ----- --- ALTERNATIVI 2/3 (*) DIS ----s NO MANUALE 0 --- min 2 3 K ----s K --- 1.0 NO MANUALE 30 3.0 NO --- NO --- ASSOLUTO … … s … s …(**) 120 …(**) …(**) 30 UOM Default DIRECT PART WINDING STAR DELTA 0…9999 0…9999 0…9999 0…9999 0…999 NO / YES MANUAL / AUTO 0…999 RECIPROCATING SCROLL SCREW 1…6/12 (*) DIS / EN R22 - R134a - R404A - R407C R410A - R507A - R290 - R600 R600a - R717 -R744 - R728 R1270 - R417A - R422D 0…999 0…999 0…9 0…999 0.0…9,9 NO / YES MANUAL / AUTO 0…999 0.0…99,9 NO / YES NO / YES …(**) …(**) 0…999 ABSOLUTE / RELATIVE …(**) 0…999 Values 53 Caf21 Caf20 Caf19 Caf18 Caf17 Caf16 Caf15 Caf14 Caf13 Caf12 Caf11 Caf10 Caf09 Mask index Compressor series Number of valves Stages configuration Cycle time Oil dilution Disch.temper. Compr.Manufacturer Min. frequency Max. frequency Min on time Min off time Min time to start same compressor Digital Scroll comp. valve regulation Compressor series Number of valves used for capacity control Stage configuration for screw compressor 1 Cycle time value (line 1) Digital Scroll, enable oil temperature alarm (line 1) Digital Scroll, enable discharge temperature alarm (line 1) Compressor manufacturer for screw compressors Minimum inverter frequency Maximum inverter frequency Compressor controlled by inverter minimum ON time (line 1) Compressor controlled by inverter minimum OFF time (line 1) Compressor controlled by inverter minimum time between same compressor starts (line 1) Digital Scroll comp. valve control type (line 1) Compressor driver type (line 1) Order of switch OFF for compressor custom rotation ----% …(***) 3 25/50/75 /100 --- Generico --- OPTIMISED CONTROL s ----- s 180 13 ENABLE ENABLE Hz Hz s s --- --- --- s s s --- --- UOM --s 30 60 30 60 NONE 1 1 10 0 0 Delay between different compressor starts Delay between different compressor stops Delay between stages Order of switch ON for compressor custom rotation Load up time Load down time Unloader delay Custom rotation Switch ON order Custom rotation Switch OFF order Modulate speed device FIFO Default NO 0 Unloader sequence in relation to compressor activation (C=compressor, p=unloader) CpppCppp Description Enable compressors equalization at start up Equalization duration Type of rotation Dev. unload sequence Display Description Equalization Equalizat.time Devices rotation type 100; 50/100; 50/75/100; 25/50/75/100; 33/66/100 OPTIMISED CONTROL VARIABLE CYCLE TIME FIXED CYCLE TIME 12…20 DISABLE/ENABLE DISABLE/ENABLE GENERIC BITZER REFCOMP HANBELL …(***) 1…4 0…999 NONE INVERTER DIGITAL SCROLL CONTINUOUS SCREW 0…150 0…150 0…999 0…999 1…16 1…16 Values NO / YES 0…999 -----FIFO LIFO TIME / CUSTOM -------CCpppppp CpppCppp 0…999 0…999 0…999 54 Caf90 … Caf36 Caf29 Caf28 Caf27 Caf26 Caf25 Caf24 Caf23 Caf22 Mask index Description Enable common delay time (from one stage to the following) for screw compressor 1 Common delay time (from one stage and the following) for screw compressor 1 Minimum compressor delay time in order to reach each capacity stage from previous for screw compressor 1 Intermittent on/off time for capacity control valves for screw compressor 1 Configuration of the behaviour of the valves during start/stop and stages for screw compressor 1 … Different sizes Different number of valves Number of valves Stages configuration … Enable compressors of different sizes (line 1) Enable compressor capacity control (line 1) Number of control capacity valves for screw compressor 2 Stage configuration for screw compressor 2 Limit comp.permanence Enable time limit at minimum capacity for screw compressor 1 at min power Max.perman.time Max time for compressor operation at minimum capacity for screw compressor 1 Limitat.on for Time to return to minimum after the compressor was forced to second stage after staying at minimum for maximum time for screw compressor 1 Min.output power Minimum compressor capacity in case of high capacity range (usually 25%), only for continuous compressors Compressor start-up Start-up phase time (after electric start-up) phase duration Maximun time to reach Maximum time in order to reach maximum compressor capacity (con-maximum power tinuous capacity control) -minimum power Minimum time in order to reach minimum compressor capacity (continuous capacity control) Intermittent Intermittent on/off time for capacity control valves Pulse period Pulsing period for valves (for continuous compressors) Min.Puls.Incr. Minimum pulse time for increase capacity (valves control) Max.Puls.Incr. Maximum pulse time for increase capacity (valves control) Min.Puls.Decr. Minimum pulse time for decrease capacity (valves control) Max.Puls.Decr. Maximum pulse time for decrease capacity (valves control) Valve conf. Configuration of the behaviour of the valves during start/stop, incr.min% to 100%, decr.100% to min%, standby, decr.100% to 50% Valve conf. Intermittent valve time Common time/time between steps From…to… Display Description Common time s % 0 25 s s s s s s 10 3 0,5 1.0 0,5 1.0 NO 3 25/50/ 75/100 … NO --- … --- % --- --- s 120 … s 120 s s 60 10 --- --- Enable … s s … 10 s --- ENABLE 0 UOM Default NO/SI 0…99 1…10 0.0…9,9 0.0…9,9 0.0…9,9 0.0…9,9 O (ON) X (OFF) I (Intermittent) P (Pulsing) 1…4 100; 50/100; 50/75/100; 25/50/75/100; 33/66/100 … NO / YES 0…999 0…999 0…999 0…100 0…9999 0…9999 O (ON) X (OFF) I (Intermittent) P (Pulsing) DISABLE ENABLE 0…99 0…999 0…999 DISABLE/ENABLE Values 55 Enable compressor modulation inside neutral zone Enable suction press. backup probe Request in case of regulat.probe fault Enable anti liquid return valve Enable compressor envelop management (*) Falling time Rising time Enable compressor envelope management (screw only). For details on configuration contact Carel. Enable liquid non return function (line 1) Compressor forcing value in case of suction probes fault (line 1) Enable screens for suction pressure backup probe configuration (line 1) Voltage corresponding to the minimum capacity of the inverter (line 1) Voltage corresponding to the maximum capacity of the inverter (line 1) Nominal frequency (nominal capacity at nominal frequency) (line 1) Nominal capacity for compressor managed by inverter at nominal frequency (line 1) Time to pass from min capacity to max capacity for modulating device (line 1) Time to pass from max capacity to min capacity for modulating device (line 1) Enable compressor 1 modulation inside Neutral zone (line 1) Digital ScrollTM compressor start-up procedure reactivation time (line 1) Size group for compressor 1 (line 1) or presence of inverter … Size group for compressor 6 (line 1) Minimum Digital ScrollTM compressor On time (line 1) Minimum Digital ScrollTM compressor Off time(line 1) Minimum time between starts for Digital ScrollTM compressor (line 1) C01 … C12 Min on time Min off time Min time to start same compressor Reactivate start-up procedure after Minimum voltage Maximum voltage Nominal freq. Nominal power Enable stages and stages for compressor group 1 (line 1) S1 … Enable stages and stages for compressor group 4 (line 1)) … Enable size and size for compressor group 4 (line 1) … S4 … S4 Description Enable size and size for compressor group 1 (line 1) Display Description S1 The following parameters refer to line 2, for details see the corresponding parameters for line 1 above Cag07 Cag06 Cag05 Cag04 Cag03 Cag02 Cag01 Caf95 Caf93 Caf92 Caf91 Mask index NO NO 50.0 NO SI 30 --- --- % --- --- s s Kw 10.0 90 V V Hz 0.0 10.0 50 min s 360 480 … --kW --… --s s --% UOM --kW … ----kW … NO --S1 … S1 60 180 Si 100 NO Default Si 10.0 … NO / YES NO / YES 0.0…100.0 NO / YES NO / YES 0…600 0…600 0.0…500.0 0.0…10.0 0.0…10.0 0…150 0…9999 0…999 Values NO/SI 0.0…500.0 … --NO/SI 0.0…500.0 NO/SI 100; 50/100; 50/75/100; 25/50/75/100; 33/66/100 … NO/SI S1…S4 S1…S4/INV … S1…S4 0…999 0…999 56 … Daa01 dix A.5) Logic Function (display only) DI Status (display only) … Description Default UOM … Kw 10.0 … … ----… Hz Hz Hz --- … … RECIPROCATING 2/3 (*) … 0.0 10.0 50 1 … --- --- NO NO … --- … --- --… --- --- UOM ----- … --- … Neutral zone --… PRESSURE NC Default 03 --- Values … 0.0…500.0 … RECIPROCATING / Scroll 1…12 … 0.0…10.0 0.0…10.0 0…150 0…4 … NO / YES NO / YES … 0…999999 Values ---, 01…18, B1…B10 (****) Closed / Open NC NO Not active / active … PRESSIONE TEMPERATURA Proportional band Neutral zone … … Logic of fan 1 overload DI (line 1) Fan 1 overload function status (line 1) Fan 1 overload DI position (line 1) Status of fan 1 overload DI (line 1) … … ----- NC --- ----- --- … ---, 01…18, B1…B10 (****) Closed Open NC / NO Not active Active … (The I/Os available depend on the selected configuration, the following are just some examples. For the complete list of I/O positions available see Appen- Display Description Mask index D.Condensers … … Type of compressors (line 2) Number of compressors (line 2) … Voltage corresponding at the minimum capacity of the inverter (line 2) Voltage corresponding at the maximum capacity of the inverter (line 2) Nominal frequency (nominal capacity at nominal frequency) (line 2) Nominal capacity for compressor managed by inverter at nominal frequency (line 2) … … Number of alarms for each compressor (line 2) Enable setpoint compensation by probe (suction line 2) … Enable setpoint compensation (suction line 2) … Compressor 1 max operating hours (line 2) Alarm 1 for compressor 1 function status (line 2) … Compressor control by temperature or pressure (line 2) Compressor control type (line 2) Function (display only) … Regulation by Regulation type … Working hours Compressor 1 … Enable suction setpoint compensation Enable compensation by analog IN … Number of alarms for each compressor … Compressors type Compressors number … Minimum voltage Maximum voltage Nominal freq. Nominal power Description Alarm 1 for compressor 1 DI position (line 2) Status of alarm 1 for compressor 1 DI (line 2) Logic of alarm 1 for compressor 1 DI (line 2) Display Description DI Status (display only) Logic … Cbg01 … Cbf02 … Cbe01 … Cbd01 … Cbc01 … Cbb01 … Cba01 Mask index 57 Dab14 Dab12/Dab13 (**) Dab10/Dab11 (**) Dab7/ Dab9 (**) Dab6/ Dab8 (**) Dab05 Dab04 Dab03 Dab02 Dab01 … Daa38 … Daa21 … Daa18 Mask index Condensing pressure backup probe value (line 1) Cond. pressure backup probe max. limit (line 1) Cond. pressure backup probe min. limit (line 1) Cond. pressure backup probe adjustment (line 1) … Fan 1 DO position (line 1) Status of fan 1 DO (line 1) Logic of fan 1 DO (line 1) Fan 1 function status (line 1) … Inverter fan AO position (line 1) Inverter fan output value (line 1) … Condenser control by temperature or pressure (line 1) Condenser control type (line 1) Condenser setpoint lower limit (line 1) Condensers setpoint higher limit (line 1) Condenser setpoint (line 1) Enable fan operation linked to compressor operation Enable fan cut-off function Cut-off value Cut-off differential Cut-off hysteresis Type for proportional control (condenser line 1) Integral time for prop. control (cond. line 1) Differential for proportional control (cond. line 1) Neutral zone control differential (line 1) Neutral zone control differential for device activation (line 1) Neutral zone control differential for device deactivation (line 1) Enable capacity immediate decreasing to 0 (line 1) Threshold for capacity decreasing to 0 (line 1) Minimum time to increase capacity request to 100%, Neutral zone control (condenser line 1) Maximum time to increase capacity request to 100%, Neutral zone control (condenser line 1) Minimum Maximum Setpoint Fans work only when at least one compressor works Cut_Off enable Cut-Off request Diff. Hysteresis Reg.type Integral time Differential NZ diff. Activ.diff. Deact.diff. En.force off power Setp.for force off Power load to 100% min time Power load to 100% max time Description Condensing pressure backup probe position (line1) Condensing pressure backup probe type (line 1) --- (display only) Upper value Lower value Calibration … DO Status (display only) Logic Function (display only) … AO Status (display only) … Regulation by Regulation type Display Description ----- s s 15 90 --% … … --s … … … … --… --- … … … NO 0.0 …(**) …(**) PROPORT. 300 …(**) …(**) …(**) …(**) NO …(**) NO …(**) …(**) …(**) … … … … … --------… --% … ----- --- 4...20mA --30.0 barg 0.0 barg 0.0 barg … 03 --NC --… 0 0 … PRESSURE PROPORTI. BAND UOM --- Default B1 0…9999 0…9999 NO / YES 0.0…100.0 …(**) …(**) PROPORT. / PROP.+INT. 0…999 …(**) …(**) …(**) …(**) NO / YES …(**) NO / YES Values ---, B1…B10 (****) ---0-1V 0-10V 4...20mA 0-5V …(**) …(**) …(**) …(**) … ---, 01…29 (****) Closed / Open NC / NO Not active / active … ---, 01…06 (****) 0.0…100.0 … PRESSURE/TEMPERATURE PROPORTIONAL BAND NEUTRAL ZONE …(**) …(**) …(**) 58 Dae05 Dae04 Dae03 Dae02 Dae01 Dad07 Dad06 Dad05 Dad04 Dad03 Dad02 Dad01 Dab15 Mask index Type of common fan overload alarm reset Reset High condensing pressure/temperature alarm delay (line 1) Type of low condensing pressure/temperature alarm threshold (line 1) Low condensing pressure/temperature alarm threshold (line 1) Low condensing pressure/temperature alarm differential (line 1) High condensing pressure/temperature alarm threshold (line 1) High condensing pressure/temperature alarm differential (line 1) Enable setpoint compensation by digital input (suction/condensing line 1) Type of high condensing pressure/temperature alarm threshold (line 1) Enable floating condensing from digital input Temperature delta for floating setpoint (condenser line 1) Low condensing pressure/temperature alarm delay (line 1) Common fan overload (line 1) Common fan overload alarm activation delay Enable floating setpoint (condenser line 1) Copy settings to other days Day of the week Time band 1 enabling and definition: start hour and minute, end hour and minute (suction line 1) … Time band 4 enabling and definition: start hour and minute, end hour and minute (suction line 1) Time band changes action Enable setpoint compensation (condenser line 1) Offset applied for Winter period Enable scheduler setpoint compensation (condenser line 1) … 1.0 barg 0 s s ----- … 7.0 barg 30 YES AUTOMATIC s --- 60 … 1.0 barg ABSOLUTE … --- ABSOLUTE 24.0 barg --- --- … --- --- NO NO 0.0 NO 0 --- … --- … --- … --… --- --- … … --- 0…999 NO / YES AUTOMATIC MANUAL 0…500 …(**) …(**) ABSOLUTE / RELATIVE 0…999 …(**) …(**) ABSOLUTE / RELATIVE NO / YES NO / YES -9,9…9,9 NO/ YES --CONFIRM&SAVE LOAD PREVIOUS CLEAR ALL MONDAY…SUNDAY; MON-FRI; MON-SAT; SAT&SUN; ALL DAYS … … … MON, ...SUN NO / YES -999,9…999,9 -999,9…999,9 NO / YES 0…9999 0…9999 s s Values UOM --- NO 0.0 0.0 Description Default Minimum time to decrease capacity request to 0%, Neutral zone control 30 (condenser line 1) Maximum time to decrease capacity request to 0%, Neutral zone control 180 (condenser line 1) Enable setpoint compensation (condenser line 1) NO Enable floating condensing setpoint Offset for external temperature Controlled by: -Digital input Change set by digital input Cond.pressure/temperature high alarm Threshold Cond.pressure/temperature alarm diff. Alarm delay Cond.pressure/temperature low alarm Threshold Cond.pressure/temperature alarm diff. Alarm delay Common fan overload Delay Copy to Changes … TB4: --:-- -> --:-- Display Description Power unload to 0% min time Power unload to 0% max time Enable condensing setpoint compensation Winter offset Closing offset Enable setpoint compensation by scheduler Activ.Time Bands TB1: --:-- -> --:-- 59 Dag04 Dag06 --- Est. Temp.Diff. Type Num.control.fans Split Condenser Controlled by: -Digital input -External temp. -Scheduler Est. Temp.Thr. Dag05 Falling time Neutral zone reg. Min.out value Max.out value Min. power refer. Max. power refer. Rising time Custom rotation Switch ON order Custom rotation Switch OFF order Modulate speed device Devices rotation type Display Description Number of present fans Fan1, Fan2, … Fan13, Fan14, … Refrigerant type Dag03 Dag02 Dag01 Daf09, Daf10 Daf07, Daf08 Daf05 Daf04 Mask index Daf01 Daf02 Daf03 Only when enabling type is GREATER THAN or LESS THAN, number of fans to consider for splitting (line 1) Split Condenser controlled by outside temperature (line 1) Split Condenser controlled by scheduler (line 1) Split condenser by outside temperature management setpoint (line 1) Split condenser by outside temperature management differential (line 1) Fans enabled with split condenser (line 1) Fan control also inside Neutral zone (line 1) Minimum voltage for compressor inverter (line 1) Maximum voltage for compressor inverter (line 1) Minimum capacity of fan modulating device (line 1) Maximum capacity of fan modulating device (line 1) Time to pass from min capacity to max capacity for fan modulating device (line 1) Time to pass from max capacity to min capacity for fan modulating device (line 1) Number of fans under inverter (only for alarm enabling) Enable split condenser (line 1) Split Condenser controlled by digital input (line 1) Fan driver type (line 1) Switch OFF order for fans with custom rotation (condenser line 1) Switch ON order for fans with custom rotation (condenser line 1) Type of rotation devices (condenser line 1) Description Number of fans (line 1) Enable fans 1 to 12 (line 1) Enable fans 13 to 16 (line 1) Type of refrigerant (condenser line 1) 0 --- … --- … 10.0 °C 2,5 °C CUSTOM ----- --- ------- ----- 1 NO s s 1200 1200 --V V % % --- --- --- --- --- UOM ------- NO 0.0 10.0 60 100 NONE 1 1 FIFO R404A Default 3 AB AB 0…16 -99,9…99,9 CUSTOM ODD EVEN GREATER THAN LESS THAN -99,9…99,9 NO / YES NO / YES NO / YES 0…16 NO / YES 0…32000 0…32000 NONE INVETER PHASE CONTROL NO / YES 0.0…9,9 0.0…99,9 0…100 0…999 1…16 1…16 Values 0…16 DIS / AB DIS / AB R22 - R134a - R404A - R407C - R410A - R507A - R290 - R600 - R600a - R717 - R744 - R728 R1270 - R417A - R422D -----FIFO LIFO TEMPO CUSTOM 60 Copy settings to other days Silencer controlled by scheduler (condenser line 1) Day of the week Time band 1 enabling and definition: start hour and minute, end hour and minute (condenser line 1) … Time band 4 enabling and definition: start hour and minute, end hour and minute (condenser line 1) Time band changes action Duration of split condenser deactivation for high condensing pressure prevent (line 1) Enable silencer (line 1) Maximum request allowed when silencer function is active (line 1) Silencer controlled by digital input (condenser line 1) DI Status (display only) Logic Function (display only) … Regulation by Regulation type … Dbb01 … … Dba01 … Fan 1 overload DI position (line 2) Status of fan 1 overload DI (line 2) Logic of fan 1 overload DI (line 2) Fan 1 overload function status (line 2) … Condenser control by temperature or pressure (line 2) Condenser control type (line 2) … --NC --… PRESSURE PROPORTIONAL BAND … 50.0 … --- --------… --- % --- … 2,5 °C NO … --s --- --- --- 25.0 °C YES 5 DIS 0 --- … --- … … --… ----- --- --% ---, 01…18, B1…B10 (****) Closed / Open NC / NO Not active / active … PRESSURE TEMPERATURE Proportional band Neutral zone … 0.0…100.0 NO / YES -99,9…99,9 -99,9…99,9 --CONFIRM&SAVE LOAD PREVIOUS CLEAR ALL MONDAY…SUNDAY; MON-FRI; MON-SAT; SAT&SUN; ALL DAYS NO / YES 0…60 DIS / AB … … … NO / YES MON, ..., SUN NO / YES DISABLE / ENABLE 0.0…100.0 0…24 NO / YES --h Values UOM NO --- NO DISAB. 75.0 % 0 Description Default Disable split condenser when high condensing pressure prevent occurs (line 1) NO Enable speed up (condenser line 1) Speed up time (condenser line 1) Enable speed up management by outside temperature (conden. line 1) Outside temperature threshold for speed up management (condenser line 1) Ext.Temp.Diff. Outside temperature differential for speed up management (condenser line 1) Enable condensing press. Enable the screens for condensing pressure backup probe backup probe configuration (condenser line 1) Request in case of egulat. Value of fans forcing in case of condensing probes fault (line 1) probes fault Speed Up Speed Up time Ext.Temp.Manage Ext.Temp.Thresh. Copy to Changes … TB4: --:-- -> --:-- Anti-noise Max output Controlled by: -Digital input -Scheduler Activ.Time Bands TB1: --:-- -> --:-- Display Description Disable split condenser as first stage of HP pressostat for The following parameters refer to line 2, for details see the corresponding parameters for line 1 above Dag15 Dag14 Dag13 Dag12 Dag10 Dag09 Mask index 61 Eaab07 Eaab06 Eaab05 Eaab04 Eaaa45 … UOM … Values …(**) … 0…16 … NONE INVETER PHASE CONTROL … ABSOLUTE / RELATIVE … NO / YES Values Enable Aout pump Screw compressors: enable AO for oil cooler pump (line 1) Common oil cooler setpoint (line 1) Common oil cooler differential (line 1) Time delay before the start-up of pump 2 after pump1 turns on (line 1) Screw compressors: number of oil cooler pumps enabled (line1) Setpoint Differential Pump start delay Oil pumps number Enable AO of common oil cooler pump (line 1) Enable Aout pump Oil temperature probe value (line 1) Oil temperature probe max. limit (line 1) Oil temperature probe min. limit (line 1) Oil temperature probe adjustment (line 1) … Oil level valve DO position, compressor 6 (line 1) Oil level valve DO status, compressor 6 (line 1) Oil level valve DO logic, compressor 6 (line 1) Oil level function status, compressor 6 (line 1) Enable common oil cooling (line 1) Number of oil pumps for common oil cooler (line 1) Upper value Lower value Calibration … DO Status (display only) Logic Function (display only) Common oil cooler Oil pumps number Oil temperature probe type (line 1) --- --- (display only) Oil temperature probe position (line1) --- SI --- --- s 0 0 … … 0.0 °C 0.0 °C --- --- 0 SI … … … … ----------- … --- --- 30.0 barg 0.0 barg 0.0 barg … 03 --NC --SI --- 4...20mA B1 0 to 1 (Analog output) 0 to 2 (Digital outputs) NO (Digital outputs) YES (Analog output) … (**) … (**) … (**) … ---, 01…29 (****) Closed / Open NC / NO Not active / Active NO / YES 0 to 1 (Analog output) 0 to 2 (Digital outputs) NO (Digital outputs) YES (Analog output) … (**) -9.9…9.9 0…999 --NTC - PT1000 - 0-1V - 0-10V 4...20mA - 0-5V - HTNTC … (**) ---, B1…B10 (****) E.Other funct. (The I/Os available depend on the selected configuration, the following are just some examples. For the complete list of I/O positions available see Appendix Eaaa04 A.5) Description Display description Mask index Default … … … … --… 24.0 barg … 3 … … --- ABSOLUTE --- … --- UOM … NO Default … … Type of high condensing pressure/temperature alarm threshold (line 2) High condensing pressure/temperature alarm threshold (line 2) … Number of fans (line 2) … Fan driver type (line 2) Description Enable setpoint compensation (condenser line 2) NONE Display Description Enable condensing setpoint compensation … Cond.temperature/pressure high alarm Threshold … Number of present fans … Modulate speed device Dbg01 … Dbf01 … Dbe01 … Dbd01 Mask index 62 Ecab05 (*) Ecab04 (*) Ecaa12 … Ecaa01 Ebab01 Ebaa01 Eaab11 Eaab10 Eaab09 Eaab08 Mask index Differential --- (display only) Upper value Lower value Calibration … DO Status (display only) Logic Function (display only) Economizer Compr.Power Thr. Press.Lim. Disch.T.Thr. Economizer Setpoint Threshold Subcool.value (display only) ----- Display description Setpoint Differential Threshold Differential Delay En.oil lev.manag. Num.Alarm oil level Time open Time close DO Status (display only) Logic Function (display only) Subcooling control --- Discharge temperature value, compressor 1 (line 1) Maximum discharge temperature value, compressor 1 (line 1) Minimum discharge temperature value, compressor 1 (line 1) Discharge temperature probe calibration, compressor 1 (line 1) … Economizer valve DO position, compressor 6 (line 1) Economizer valve DO status, compressor 6 (line 1) Economizer valve DO logic, compressor 6 (line 1) Economizer valve function status, compressor 6 (line 1) Enable economizer function (line 1) Capacity percentage threshold for economizer activation (line 1) Condensing temperature threshold for economizer activation (line 1) Discharge temperature threshold for economizer activation (line 1) Enable economizer function for screw compressor 1 (line 1) Setpoint for economizer function with discharge temperature for screw compressor 1 Differential for economizer function with discharge temperature for screw compressor 1 Discharge temperature probe position, compressor 1 (line 1) Type of discharge temperature probe, compressor 1 (line 1) Threshold for subcooling control (line 1) Subcooling value (line 1) Description Screw compressors: oil temperature setpoint (line 1) Screw compressors: oil temperature differential (line 1) Common oil high temperature alarm threshold (line 1) Common oil high temperature alarm differential (line 1) Common oil high temperature alarm delay (line 1) Enable oil level management (line 1) Number of compressor alarm associated with oil level (line 1) Oil level valve opening time (line 1) Oil level valve closing time (line 1) Subcooling valve DO position (line 1) Status of subcooling valve DO (line 1) Logic of subcooling valve (line 1) Subcooling valve function status (line 1) Enable subcooling function (line 1) Subcooling control type (line 1) … … … … …(**) …(**) … … … … … ----------% … … --- --- 4...20mA --30.0 barg 0.0 barg 0.0 barg … … --NO --NO 0 0.0 °C 0.0 °C NO --- B1 --- 0.0 °C UOM °C/°F °C/°F °C/°F °C/°F s ----s s ----------- Default 0.0 0.0 100.0 °C 10.0 °C 0 NO 0 0 0 … --NO --NO BY COND. & LIQUID TEMP. 0.0 °C … (**) ---, B1…B10 (****) --NTC - PT1000 - 0-1V - 0-10V4...20mA - 0-5V - HTNTC … (**) … (**) … (**) … (**) … ---, 01…29 (****) Closed / Open NC / NO Not active / Active NO / YES 0…100 -999.9…999.9 -999.9…999.9 NO / YES … (**) Values … … … … 0 to 32767 NO / YES 0 to 4/7 (*) 0…999 0…999 ---, 01…29 (****) Closed / Open NC / NO Not active / Active NO / YES BY COND.& LIQUID TEMP. ONLY BY LIQUID. TEMP. -9999.9…9999.9 -999.9…999.9 63 Eeab04 Eeab03 Eeab02 Eeab01 Eeaa05 Eeaa04 Eeaa03 Eeaa02 Edab01/Edab03 (*) Edaa12 … Edaa01 Setpoint Ecab06 (*) --- (display only) Upper value Lower value Calibration Enable Heat Reclaim Condensing pressure Lower Limit Modulation by temperature Setpoint Differential --- (display only) Upper value Lower value Calibration … DO Status (display only) Logic Function (display only) Liquid Injection Threshold Differential DI Status (display only) Logic Function (display only) DO … Function (display only) AO … Status ----- ----- Differential Display description Min.power activ. Cond.press.check Mask index Heat recovery: discharge temperature setpoint (line 1) Heat recovery: discharge temperature differential (line 1) Enable heat recovery control by discharge temperature (line 1) Heat recovery outlet temperature value (line 1) Maximum heat recovery outlet temperature value (line 1) Minimum heat recovery outlet temperature value (line 1) Heat recovery outlet temperature probe calibration (line 1) Enable heat recovery function (line 1) Condensing pressure lower limit for heat recovery (line 1) Compressor 1 discharge temperature probe type (line 1) Compressor 1 discharge temperature probe value (line 1) Compressor 1 discharge temperature probe max. limit (line 1) Compressor 1 discharge temperature probe min. limit (line 1) … Injection valve DO position, compressor 6 (line 1) Injection valve DO status, compressor 6 (line 1) Injection valve DO logic, compressor 6 (line 1) Injection valve function status, compressor 6 (line 1) Enable liquid injection function (line 1) Liquid injection set point (line 1) Liquid injection differential (line 1) Heat recovery from digital input DI position (line 1) Status of heat recovery DI (line 1) Logic of heat recovery DI (line 1) Status of heat recovery from digital input DI function (line 1) Heat recovery pump DO position (line 1) … Status of heat recovery pump (line 1) Heat recovery damper DO position (line 1) … Heat recovery damper DO status (line 1) Heat recovery outlet temperature probe position (line 1) Type of heat recovery outlet temperature probe (line 1) Description Minimum screw compressor 1 capacity for economizer activation Enable economizer function with condensing temperature for screw compressor 1 Setpoint for economizer function with condensing temperature for screw compressor 1 Differential for economizer function with condensing temperature for screw compressor 1 Discharge temperature probe position, compressor 1 (line 1) Compressor 1 discharge temperature probe position (line1) 0.0 °C 0.0 °C NO 0.0 barg … … --- … … … … … --- --- 4...20mA --30.0 barg 0.0 barg 0.0 barg NO … … … … … ----------… … ----------… ----… ----- --- 4...20mA --30.0 barg 0.0 barg 0.0 barg … … --NO --DIS 70.0 °C 5.0 … --NC ----… ----… --B1 --- °C/°F B1 5.0 °C/°F --- DIS 60.0 UOM % Default 75 … (**) 0.0…99,9 NO / YES … (**) ---, B1…B10 (****) --NTC - PT1000 - 0-1V - 0-10V4...20mA - 0-5V - HTNTC … (**) … (**) … (**) … (**) … ---, 01…29 (****) Closed / Open NC / NO Not active / Active DIS / AB … (**) … (**) ---, 01…18, B1…B10 (****) Closed / Open NC / NO Not active / active ---, 01…29 … Not active / active ---, 01…29 … Not active / active ---, B1…B10 (****) --NTC - PT1000 - 0-1V - 0-10V 4...20mA - 0-5V - HTNTC …(**) …(**) …(**) …(**) NO / YES … … Values 0; 25; 50; 75; 100 DIS / EN 64 Efb08 Efb07 Efb06 Efb05 … Efa09 Efa08 Efa07 Efa06 Efa05 Eeab07 Eeab06 Eeab05 Mask index Copy settings to other days Enable generic stage function 1 .. Enable generic stage function 5 Control variable for generic stage function 1 Direct or reverse control Enabling variable for generic stage function 1 Enable description change Description Setpoint for generic stage function 1 Differential for generic stage function 1 High alarm enabling for generic stage function 1 High alarm threshold for generic stage function 1 High alarm delay for generic stage function 1 Low alarm enabling for generic stage function 1 Low alarm threshold for generic stage function 1 Low alarm delay for generic stage function 1 Low alarm delay for generic stage function 1 Type of low alarm for generic stage function 1 … Enable generic modulating function 1 management Enable generic modulating function 2 management Control variable for generic modulating function 1 Direct or reverse modulation Enabling variable for generic modulating function 1 Enable description change Description Setpoint for generic modulating function 1 Differential for generic modulating function 1 Copy to Gen.Funct.1 … Gen.Funct.5 Regulation variable Mode Enable Description --------------Setpoint Differential High alarm High alarm Delay time Alarm type Low alarm Low alarm Delay time Alarm type … Gen.Modulat.1 Gen.Modulat.2 Regulation variable Mode Enable Description --------------Setpoint Differential Display description Description Disable floating conden- Disable floating condensing pressure when heat reclaim is active sing pressure Setpoint offset Offset that must be applied to the condensing setpoint instead of floating condensing when heat reclaim is active Enable activation by Enable heat recovery control by scheduler (line 1) scheduler Active.Time Bands Week of the day TB1: --:-- -> --:-Time band 1 enabling and definition: start hour and minute, end hour and minute (condenser line 1) … … TB4: --:-- -> --:-Time band 4 enabling and definition: start hour and minute, end hour and minute (condenser line 1) Changes Time band changes action --… … … ----… --- 0 DISAB. … DISAB. --DIRECT --SKIP --0.0 °C 0.0 °C Disab. 0.0 °C 0 LIGHT Disab. 0.0 °C 0 LIGHT … DISAB. DISAB. --DIRECT --SKIP --0.0 °C 0.0 °C --… ------------… … --… s ----… s --… --------------… … --- --- --- NO --- … --- NO --- UOM Default --CONFIRM&SAVE LOAD PREVIOUS CLEAR ALL MONDAY…SUNDAY; MON-FRI; MON-SAT; SAT&SUN; ALL DAYS DISABLE / ENABLE … DISABLE / ENABLE … DIRECT / REVERSE … SKIP / CHANGE … … (**) … (**) DISABLE / ENABLE … (**) 0…9999 Light / Serious DISABLE / ENABLE … (**) 0…9999 Light / Serious … DISABLE / ENABLE DISABLE / ENABLE … DIRECT / REVERSE … SKIP / CHANGE … … (**) … (**) … … … MON, ..., SUN NO / SI -99.9…99.9 NO / YES Values 65 Efe05 Efd07 Efd06 Efd05 … Efc07 Efc06 Efc05 … Efb20 Efb010 Efb09 Mask index --- DISAB. Copy settings to other days Generic analogue input A unit of measure selection … Gen.A Measure … Enabling variable for generic scheduler function Day of the week Time band 1 enabling and definition: start hour and minute, end hour and minute (suction line 1) … Time band 4 enabling and definition: start hour and minute, end hour and minute (suction line 1) Time band changes action °C … 0 --- --… --- --- … --- … … --… ----- ----- --- UOM --… s --% % --… … --… s --… --------------s … Default DISAB. 0.0 °C 0 LIGHT 100.0 0.0 NO 0.0 °C 0.0 °C Disab. 0.0 °C 0 LIGHT … DISAB. DISAB. ----SKIP --LIGHT 0 … Generic scheduler function considers the same special days and periods of global scheduler NO Description High alarm enabling for generic modulating function 1 High alarm threshold for generic modulating function 1 High alarm delay for generic modulating function 1 Low alarm enabling for generic modulating function 1 Output upper limit for generic modulating function 1 Output lower limit for generic modulating function 1 Enable cut off function for generic modulating function 1 Cut off differential for generic modulating function 1 Cut off hysteresis for generic modulating function 1 Low alarm enabling for generic modulating function 1 Low alarm threshold for generic modulating function 1 Low alarm delay for generic modulating function 1 Low alarm type for generic modulating function 1 … Enable generic alarm function 1 management Enable generic alarm function 2 management Monitored variable for generic alarm function 1 Enabling variable for generic alarm function 1 Enable description change Description Alarm type for generic alarm function 1 Delay for generic alarm function 1 … Enable generic scheduler function Copy to Changes … TB4: --:-- -> --:-- Display description High alarm High alarm Delay time Alarm type Out upper limit Out lower limit Enable cutoff Cutoff diff. Cutoff hys. Low alarm Low alarm Delay time Alarm type … Gen.alarm 1 Gen.alarm 2 Regulation variable Enable Description --------------Alarm type Delay time … Generic Function Scheduler Gen.funct.scheduling connected to global scheduling Enable Activ.Time Bands TB1: --:-- -> --:-- --CONFIRM&SAVE LOAD PREVIOUS CLEAR ALL MONDAY…SUNDAY; MON-FRI; MON-SAT; SAT&SUN; ALL DAYS °C; °F; barg; psig; %; ppm … … … … … MON, ..., SUN NO / YES DISABLE / ENABLE Values DISABLE / ENABLE … (**) 0…9999 Light / Serious 0…100 0…100 NO / SI … (**) … (**) DISABLE / ENABLE … (**) 0…9999 Light / Serious … DISABLE / ENABLE DISABLE / ENABLE … … SKIP / CHANGE … Light / Serious 0…9999 … 66 Ehb03 Ehb01 Egab04 Egab03 Egab02 Egab01 Egaa02 Egaa01 … Efe29 … Efe21 … Efe16 … Efe06/Efe07 (**) Mask index Display description ------- (display only) Upper value Lower value Calibration ... DI Status (display only) Logic Function (display only) ... DO Status (display only) Logic Function (display only) … Modulating.1 Status (display only) … DI Status (display only) Logic Function (display only) DO Status (display only) Logic Function (display only) Device present Deactivation when fanspower falls under Before the activation fans at max for Ext.Temp.Thr. Sanitary proc. start at Duration Ext.temp.thr ChillBooster requires maintenance after Reset maintenance time Avoid simultaneous pulses betw.lines Delay Force off L2 Comp.s for line 1 fault Delay Delay for line 2 compressor switch off after serious alarm on line 1 compressors Delay between start up for compressors on different lines Enable line 2 compressor switch OFF due to line 1 compressor fault ChillBooster maintenance time reset (line 1) Enable simultaneous compressor start up inhibition Fans work at maximum capacity at least for this time before ChillBooster activation (line 1) Outside temperature threshold for ChillBooster activation (line 1) Enable hygiene procedure (line 1) Hygiene procedure starting time (line 1) Hygiene procedure duration (line 1) Outside temperature threshold for hygiene procedure activati. (line 1) ChillBooster maximum running time (line 1) Description Generic probe A position Generic probe A type Generic probe A value Generic probe A max. limit Generic probe A min. limit Generic probe A adjustment ... Generic digital input F DI position Status of generic digital input F DI Logic of generic digital input F DI Status of generic digital input F DI ... Generic stage 1 DO position Status of generic stage 1 DO Logic of generic stage 1 DO Generic stage 1 DO function status … Generic modulating 1 AO position Generic modulating 1 output value … ChillBooster fault DI position (line 1) Status of ChillBooster fault DI (line 1) Logic of ChillBooster fault DI (line 1) Status of ChillBooster fault (line 1) ChillBooster DO position (line 1) Status of ChillBooster DO (line 1) Logic of ChillBooster DO (line 1) Status of ChillBooster function (line 1) Enable ChillBooster function (line 1) Fan capacity under which ChillBooster is deactivated (line 1) 0 s s --- 0 NO --- NO h 200 --- … ----min … NO min 30.0 °C DISAB. 00:00 0 5.0 °C % UOM ----… … … … … --------… --------… --% … ------------------- 5 95 Default B1 4...20mA --30.0 barg 0.0 barg 0.0 barg … ----NC --… … --NO --… 0 0 … ----NC --… --NO --NO 0…999 NO / YES 0…999 NO / YES NO / YES 0…999 …(**) DISABLE / ENABLE … 0…30 …(**) 0…300 0…100 Values ---, B1…B10 (****) …(**) …(**) …(**) …(**) …(**) … ---, 01…18, B1…B10 (****) Closed / Open NC / NO Not active / active … ---, 01…29 (****) Closed / Open NC / NO Not active / active … ---, 01…06 (****) 0.0…100.0 … ---, 01…18, B1…B10 (****) Closed / Open NC / NO Not active / active ---, 01…29 (****) Closed / Open NC / NO Not active / active NO / YES 67 Display description Switch on L1 Comp.s for L2 activation Switch on period Force off line 2 if line 1 is off Enable min threshold for L1 activation Threshold Enable L1 activation by DSS only when suction pressure is greater than a minimum threshold Minimum threshold for line 1 activation by DSS Description Enable line 1 compressor switch ON due to line 2 compressor switch ON Delay for line1 compressor switch on for line 2 compressor switch on Enable line 2 compressor switch OFF due to line 1 switch OFF … Ecbb04 … Ebbb01 … Ebba01 … Eabb04 … Eaba04 Threshold Subcool.value (display only) … Economizer Compr.Power Thr. Press.Lim. Disch.T.Thr. … … Subcooling control --- … DO Status (display only) Logic Function (display only) Enable Aout pump --- (display only) Upper value Lower value Calibration … Oil pumps number ----- … Enable economizer function (line 2) Capacity percent threshold for economizer activation (line 2) Condensing temperature threshold for economizer activation (line 2) Discharge temperature threshold for economizer activation (line 2) … Threshold for subcooling control (line 2) Value of subcooling (line 2) … Enable subcooling function (line2) Subcooling control type (line 2) … Subcooling valve DO position (line 2) Status of subcooling valve DO (line 2) Logic of subcooling valve (line 2) Subcooling valve function status (line 2) Enable AO of common oil cooler pump (line 2) Oil temperature probe value (line 2) Oil temperature probe max. limit (line 2) Oil temperature probe min. limit (line 2) Oil temperature probe adjustment (line 2) … Number of oil pumps for common oil cooler (line 2) Oil temperature probe position (line 2) Oil temperature probe type (line 2) The following parameters refer to line 2, for details see the corresponding parameters for line 1 above Ehb05 Ehb04 Mask index … NO 0 0.0 °C 0.0 °C … … --% … … … … … 0.0 °C 0.0 °C --- COND&LIQUID TEMP. --… --- --… NO … ------- … … --NO --- --- 0 YES … … … … … --- 4...20mA --30.0 barg 0.0 barg 0.0 barg … --- … B1 --- --- --- NO NO s --- NO 30 UOM Default … NO / SI 0…100 -999,9…999,9 -999,9…999,9 … -999,9…999,9 -9999,9…9999,9 ---, B1…B10 (****) --NTC - PT1000 - 0-1V - 0-10V 4...20mA - 0-5V - HTNTC …(**) …(**) …(**) …(**) … 0 to 1 (digital input) 0 to 2 (Digital outputs) NO (Digital outputs) YES (digital input) … ---, 01…29 (****) Closed / Open NC / NO Not active Active … NO / YES COND&LIQUID TEMP. LIQUID TEMP. ONLY … (**) NO / YES NO / YES 0…999 NO / YES Values 68 Faaa05 Faaa03 … Faaa04 Faaa02 Faaa01 F.settings Mask index … Egbb01 … Egba01 Eebb01 … Eeba02 … Edbb01 … Edba01 Edba01 Mask index Summer/Winter Special days Holiday periods Begin End Day 01 … Day 10 P1 --… P5 --- Display description --- (display only) Upper value Lower value Calibration … Liquid Injection Threshold Differential … DI Status Logic Function Enable Heat Reclaim … DI Status Logic Function … Device present Deactivation when fanspower falls under … Display description ----- Enable Summer/Winter period management (line 1) Enable special days management (line 1) Enable holiday period management (line 1) Summer period beginning date (line 1) Summer period end date (line 1) Special day 1 date (line 1) … Special day 10 date (line 1) Holiday period P1 beginning date (line 1) Holiday period P1 end date (line 1) … Holiday period P5 beginning date (line 1) Holiday period P5 end date (line 1) Description … Compressor 1 discharge temperature probe value (line 2) Compressor 1 discharge temperature probe max. limit (line 2) Compressor 1 discharge temperature probe min. limit (line 2) Compressor 1 discharge temperature probe adjustment (line 2) … Enable liquid injection function (line 2) Liquid injection setpoint (line 2) Liquid injection differential (line 2) … Heat recovery from digital input DI position (line 2) Status of heat recovery DI (line 2) Logic of heat recovery DI (line 2) Status of heat recovery from digital input DI function (line 2) Enable heat recovery function (line 2) … ChillBooster fault DI position (line 2) Status of ChillBooster fault DI (line 2) Logic of ChillBooster fault DI (line 2) Status of ChillBooster fault DI (line 21) … ChillBooster function enable (line 2) Fans capacity under which ChillBooster is deactivated (line 2) Description Compressor 1 discharge temperature probe position (line 2) Compressor 1 discharge temperature probe type (line 2) NO NO NO ------… ------… ----- Default … 95 --30.0 barg 0.0 barg 0.0 barg … DIS 70.0 °C 5.0 … … --NC --NO … ----NC --… NO 4...20mA Default B1 ------------… ------… ----- UOM … % … … … … … --… … … ----------… --------… --- --- UOM --- NO / SI NO / SI NO / SI 01/Gen…31/Dic 01/Gen…31/Dic 01/Gen…31/Dic … 01/Gen…31/Dic 01/Gen…31/Dic 01/Gen…31/Dic … 01/Gen…31/Dic 01/Gen…31/Dic Values … 0…100 Values ---, B1…B10 (****) --NTC - PT1000 - 0-1V - 0-10V 4...20mA - 0-5V - HTNTC …(**) …(**) …(**) …(**) … DIS / AB … (**) … (**) … ---, 01…18, B1…B10 (****) Closed / Open NC / NO Not active / active NO / SI … ---, 01…18, B1…B10 (****) Closed / Open NC / NO Not active / active … NO / SI 69 Supervisor communication protocol (line 1) Supervisor communication baud rate (line 1) Password Current password level Logout User password Service password Manufacturer password Protocol Baudrate Insert password Logged as (display only) Logout User Service Manufacturer Address of the controller in a supervisory system network (line 1) Fcb01 Baudrate Address Protocol Enable holiday period management (line 2) Enable summer/winter period management (line 2) Enable special days management (line 2) The following parameters refer to line 2, for details see the corresponding parameters for line 1 above Fd03 Fd02 Fd01 Fca01 Fb03 Address 60 Starting value for countdown, time change language screen active. Main screen selection YES Disable the change language screen at start-up Fb02 Fb01 Faab05 Main mask selection … … … DISAB. 60 … … ENGLISH Hour and minute Date Day of the week calculated from current date Enable daylight saving time Offset time Starting week, day and month and hour for daylight saving time End week, day and month and hour for daylight saving time Current language Hour Date Day (display only) Daily saving time Transition time Start, ... End, ... Language Disable language mask at start-up Countdown Faab02/Faab03/ Faab04 --- --- pRACK MANAGER 19200 --- --------------- --- --- --- s --- … … … ----… … --- --- UOM 196 19200 0000 --NO 0000 1234 1234 pRACK MANAGER 196 LINE 1 DD/MM/YY Date format Date format Default Faab01 Description Display description Mask index 0…207 -CAREL SLAVE LOCAL CAREL SLAVE REMOTE MODBUS SLAVE pRACK MANAGER CAREL SLAVE GSM 1200…19200 0…60 LINE 1 LINE 2 DOUBLE SUCTION DOUBLE CONDENSER 0 to 207 -CAREL SLAVE LOCAL CAREL SLAVE REMOTE MODBUS SLAVE pRACK MANAGER CAREL SLAVE GSM 1200 to 19200 0…9999 User, Service, Manufacturer NO / SI 0…9999 0…9999 0…9999 NO / SI Values ---DD/MM/YY MM/DD/YY YY/MM/DD … … Monday… Sunday DISABLE / ENABLE 0…240 … … … 70 G.Safety Prevent max.number evaluation time Reset automatic prevent Common HP type Common HP delay Common LP start delay Common LP delay Time of semi-automatic alarm evaluation N° of reties before alarm becomes manual Liquid alarm delay Oil alarm delay Output alarms relays activation with Condensing pressure prevent threshold (line 1) Condensing pressure prevent differential (line 1) Decreasing capacity time (line 1) Setpoint Differential Decrease compressor power time Enable Heat Reclaim as first prevent step Offset HeatR. Enable ChillBooster as first prevent step Offset Chill. Prevent max.num Number of LP in period after which the alarm becomes manual (line 1) Liquid level alarm delay (line 1) Common oil alarm delay (line 1) Select alarm relay output activation for active alarms or alarms not reset Reset number of prevent (line 1) Type of reset for common HP alarm (line 1) Common high pressure delay (line 1) Low common condensing pressure delay at start up (line 1) Low common condensing pressure delay during operation (line 1) Period of LP evaluation (line 1) Offset between ChillBooster and prevent setpoint (line 1) Maximum number of prevent allowed before locking compressor (line 1) Prevent maximum number evaluation time Enabling heat recovery as first stage for condensing HP prevent (line 1) Offset between heat recovery and prevent setpoint (line 1) Enable ChillBooster as first stage for condensing HP prevent (line 1) Enable condensing pressure prevent (line 1) Description Prevent enable Display description … Gcb01 Gbb01 … Prevent enable … Common HP type Common HP delay … Enable condensing pressure prevent (line 2) … Type of reset for common HP alarm (line 2) Common high pressure delay (line 2) … The following parameters refer to line 2, for details see the corresponding parameters for line 1 above Gca05 Gca04 Gca03 Gca02 Gca01 Gba05 Gba04 Gba03 Gba02 Gba01 Mask index --… --s … s s 0 0 Active alarms NO … AUTO 10 … --- 5 min 120 h ----s s s NO AUTO 10 60 20 60 … --- 0.0 barg … --- 0.0 barg NO 3 --- s 0 NO … … --- UOM 0.0 barg 0.0 barg NO Default NO / SI … AUTO / MAN 0…999 … 0…999 0…999 Active alarms Alarms not reset 0…999 0…999 NO / SI AUTO / MAN 0…999 0…999 0…999 0…999 1…5 NO SI 0.0…99,9 NO SI 0.0…99,9 0…999 NO SI … (**) 0.0…99,9 Values 71 Number of cycles per second and software cycle time Main cycle Ib01 Ia05 (display only) Number of compressors featured in the pre-configuration (line 2) Type of compressors featured in the pre-configuration (line 2) Number of alarms for compressor featured in the pre-configuration Enable common condenser alarm Enable common HP pressure switch Enable common LP pressure switch Type of system Comp.type L2 Num.alarms per comp. Cond.Gen.Alarm HP comm.pressostat LP comm.pressostat Type of Installation Type of compressors featured in the pre-configuration (line 1) Comp.type L1 Ia04 (display only) Num.Comp. L2 pLAN boards required for the selected pre-configuration Number of suction lines featured in the pre-configuration Number of condenser lines featured in the pre-configuration Number of compressors featured in the pre-configuration (line 1) Boards necessary Suction line Condenser line Num.Comp. L1 Ia02 (solo visua.) Ia03 (solo visua.) Pre-configuration Pre-configuration selected Description RAM size Type of built-in display RAM Built-In type Display description Software version and date Bios version and date Boot version and date Type of hardware Hardware size Flash memory size Description Ver. Bios Boot Board type Board size Total flash Display description Ia01 I.Setup Mask index H02 (display only) H01 (display only) H.Info Mask index ----------- --- UM cicli/s ms kB --- ----------kB UOM 1/4 (*) EN EN EN SUCTION + CONDENSER ----------- … --RECIPROCATING --- ------… RECIPROCATING 01. RS2 Default --- ----- … … … … … --- Default --NOT USED— 08. SL5d 01. RS2 09. SW1 02. RS3 10. SW2 03. RS3p 11. SW3 04. RS3i 12. d-RS2 05. RS4 13. d-RS3 06. RS4i 14. d-RS4 07. SL3d --0…2 0…2 1…12 RECIPROCATING SCROLL SCREW 1…12 RECIPROCATING SCROLL 0…4/7 (*) EN/DIS EN/DIS EN/DIS SUCTION CONDENSER SUCTION + CONDENSER Values … … None / PGD1 … … … … … … Values 72 --C01 … C06 Ib17 --- Size group for compressor 1 (line 1) or presence of inverter … Size group for compressor 12 (line 1) … Enable size and size for compressor group 4 (line 1) Enable size and size for compressor group 1 (line 1) S1 … S4 Compressor series Compressor sizes (line 1) Compressor series Compressors sizes Size group for compressor 1 (line 1) or presence of inverter … Size group for compressor 12 (line 1) Compressor manufacturer for screw compressors C01 … C12 Compr.Manufacturer Enable stages and stages for compressor group 1 (line 1) S1 … Enable stages and stages for compressor group 4 (line 1)) … Enable size and size for compressor group 4 (line 1) … S4 … S4 Enable size and size for compressor group 1 (line 1) Compressors sizes (line 1) Modulating speed device for first compressor (line 1) Number of compressors (line 1) Number of alarms for each compressor (line 1) Description Unit of measure Type of compressors (line 1) S1 Compressors sizes Compressors number Number of alarms for each compressor Modulate speed device Display description Measure Units Compressors type Ib16 Ib11 Ib10 Ib36 Ib35 Ib34 Ib30 Ib05 Ib04 Ib03 Mask index Ib02 S1 … --- …(***) SAME CAPACITY SI --… NO --- … NO --S1 … S1 Generic YES 100 SAME CAPACITY & SAME STAGE CONF. YES 10.0 … NO --- --… --- --kW … --kW ----- … --kW --… ----- --% --kW … --kW --- S1…S4/INV … S1…S4 NONE INVERTER ---/DIGITAL SCROLL(*) ---/STEPLESS*) SAME CAPAC.&SAME STAGE CONF. SAME CAPAC.&DIFF. STAGE CONF. DEFINE SIZES NO / YES 0.0…500.0 … NO / YES 0.0…500.0 NO/SI. 100; 50/100; 50/75/100; 25/50/75/100; 33/66/100 … NO / YES S1…S4 S1…S4/INV … S1…S4 GENERIC BITZER REFCOMP HANBELL …(***) SAME CAPACITY DEFINE SIZES NO/SI 0.0…500.0 … NO/SI 0.0…500.0 0…4/7 (*) --- ----- 2/3 (*) 1 None Values °C/barg / °F/psig RECIPROCATING SCROLL SCREW 1…6/12 (*) Default UM °C/barg --RECIPROCATING --- 73 Ib75 Ib74 Ib70 Ib52 Ib51 Ib50 Ib45 Ib43 Ib42 Ib41 Ib40 Ib40 Ib22 Ib21 Ib20 Mask index … Enable stages and stages for compressor group 4 (line 1)) Enable stages and stages for compressor group 1 (line 1) S1 … S46 … Enable size and size for compressor group 4 (line 1) Enable size and size for compressor group 1 (line 1) Compressors sizes (line 1) Modulating speed device for first compressor (line 2) Type of compressors (line 2) Number of compressors (line 2) Number of alarms for each compressor (line 2) Suction lines on different boards Setpoint without compensation (suction line 1) Differential (suction line 1) Second suction line configuration Enable integral time for proportional suction line control (line 1) … S4 S1 Compressors sizes Enable integral time action Setpoint Differential Configure another suction line Dedicated pRack board for suction line Compressors type Compressors number Number of alarms for each compressor Modulate speed device Compressor control type (line 1) Size group for compressor 1 (line 1) or presence of inverter … Size group for compressor 6 (line 1) Compressor control by temperature or pressure (line 1) Unit of measure (line 1) Type of refrigerant (suction Line 1) C01 … C12 Regulation by Measure unit Refrigerant Regulation type … Enable size and size for compressor group 4 (line 1) Enable size and size for compressor group 1 (line 1) S1 … S4 Description Compressors sizes (line 1) Display description Compressors sizes … NO --- SI 100 SI --… NO --- SAME CAPACITY NONE 1 RECIPROCAT. 3 NO NO 3.5 barg 0.3 barg NO Neutral zone R404A Default SAME CAPACITY SI --… NO --S1 … S1 PRESSURE barg … --kW --% --kW … --kW --- --- --- ----- --- --- …(**) …(**) --- --- --- --kW … --kW --… ------- UM --- NONE INVERTER ---/DIGITAL SCROLL(*) SAME CAPAC.&SAME STAGE CONF. SAME CAPAC.&DIFF. STAGE CONF. DEFINE SIZES NO/YES 0.0…500.0 … NO/YES 0.0…500.0 NO/YES 100; 50/100; 50/75/100; 25/50/75/100; 33/66/100 … NO/YES S1…S4 0…4 RECIPROCATING / SCROLL 1…12 NO / YES NO / YES …(**) …(**) NO / YES Values SAME CAPACITY DEFINE SIZES NO/YES 0.0…500.0 … NO/YES 0.0…500.0 S1…S4/INV … S1…S4 PRESSURE / TEMPERATURE … R22 - R134a - R404A - R407C - R410A - R507A - R290 - R600 - R600a - R717 - R744 - R728 R1270 - R417A - R422D Proportional band Neutral zone 74 Compressor control type (line 1) Regulation type Ib1a Ib96 Ib95 Ib94 Ib93 Ib93 Ib54 Ib91 Ib90 Ib82 Ib81 Ib80 Enable integral time action Setpoint Differential Configure another condensing line Fans number Regulation type Regulation by Measure unit Refrigerant Number of fans (line 2) Setpoint without compensation (condenser line 1) Differential (condenser line 1) Second condenser line configuration Enable integral time for proportional band control Fan control type (line 1) Fans control by temperature or pressure value (line 1) Unit of measure (line 1) Type of refrigerant (condenser line 1) Setpoint without compensation (suction line 2) Differential (suction line 2) Suct.line(s) and cond.line(s) on different boards, that is, condenser line(s) on dedicated board Number of fans (line 1) Fan modulating speed device (line 1) Enable integral time for proportional suction line control (line 2) Size group for compressor 1 (line 1) or presence of inverter … Size group for compressor 6 (line 1) Compressor control by temperature or pressure (line 1) Unit of measure (line 1) Type of refrigerant (suction Line 1) C01 … C12 Regulation by Measure unit Refrigerant Ib62 Enable integral time action Setpoint Differential Dedicated pRack board for condenser line Fans number Modulate speed device … Enable size and size for compressor group 4 (line 1) … S4 Ib61 Ib60 Ib76 Description Size group for compressor 1 (line 1) or presence of inverter … Size group for compressor 6 (line 1) Compressors sizes (line 1) Enable size and size for compressor group 1 (line 1) Display description C01 … C12 Compressors sizes S1 Mask index 3 NO 12.0 barg 2.0 barg NO Proportional band R404A PRESSURE barg NONE 3 NO 3.5 barg 0.3 barg NO Neutral zone R404A Default S1 … S1 SAME CAPACITY SI --… NO --S1 … S1 PRESSURE barg --- --- …(**) …(**) --- --- --- ----- --- --- --- …(**) …(**) --- --- --- UM --… ------kW … --kW --… ------- 0…16 NO/YES …(**) …(**) NO/YES 0…16 NESSUNO INVERTER CONTR. TAGLIO DI FASE PRESSIONE / TEMPERATURA … R22 - R134a - R404A - R407C - R410A - R507A - R290 - R600 - R600a - R717 - R744 - R728 R1270 - R417A - R422D Proportional band Neutral zone NO/YES …(**) …(**) NO / SI Values S1…S4/INV … S1…S4 SAME CAPACITY / DEFINE SIZES NO/YES 0.0…500.0 … NO/YES 0.0…500.0 S1…S4/INV … S1…S4 PRESSURE / TEMPERATURE … R22 - R134a - R404A - R407C - R410A - R507A - R290 - R600 - R600a - R717 - R744 - R728 R1270 - R417A - R422D Proportional band Neutral zone 75 Compressors number Number of condensing lines Line 1 Line 2 Dedicated pRack board for condenser line Boards necessary Save configuration Load configuration Restore Carel default Compressors number Compressors type Measure Units Number of suction lines Dedicated pRack board for suction line Compressors type Display description … Differential Type of Installation pLAN boards required for the selected pre-configuration Save Manufacturer configuration Manual installation of Manufacturer configuration Manual installation of Carel default values Number of fans (line 1) Number of fans (line 2) Condenser lines are on different boards Number of compressors (line 2) Number of condenser lines in the system Number of compressors (line 1) Type of compressors (line 2) Type of compressors (line 1) Unit of measure Number of suction lines Suction lines are on different boards Description … Differential (condenser line 2) Type of plant (*) Depending on the type of compressor (**) Depending on the unit of measure selected (***) Depending on the compressor manufacturer, see relative paragraph (****) Depending on the hardware size Id02 Id01 Ic10 (solo visual.) Ic09 Ic08 Ic07 Ic06 Ic05 Ic04 Ic02 Ic03 Ic01 Mask index … Ib1e UM … …(**) --- ----- --NO NO NO NO 4 0 1 0 --------- --- ----- --- --- 4 --RECIPROCATING --- RECIPROCATING --- NO °C/barg 1 ASPIRAZ+ CON--DENSAZ. Default … 2.0 barg --NO/YES NO/YES NO/YES NO/YES 0…16 0…16 0…2 RECIPROCATING SCROLL SCREW 1…6/12 (*) RECIPROCATING SCROLL SCREW 1…6 NO/YES Values … …(**) ASPIRAZIONE CONDENSAZIONE ASPIRAZ. + CONDENSAZ. °C/barg / °F/psig 0…2 76 NOTE:_______________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ 77 NOTE:_______________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ CAREL INDUSTRIES - Headquarters Via dell’Industria, 11 - 35020 Brugine - Padova (Italy) Tel. (+39) 049.9716611 - Fax (+39) 049.9716600 e-mail: [email protected] - www.carel.com pRack +040000071 rel. 1.1 - 14.10.2011 Agenzia / Agency: