Task Code Definition (continued)
TC35
Execute Complete
(Warm) Start
Command:
Response:
35 [xx]
35
Field xx is added for multi-PLC/multi-application systems (e.g., TI575) and
has the following characteristics:
If xx is not coded or xx = 00, then the restart is for this application only.
If xx = 01, then the restart is coordinated across locked applications.
If xx = 02, then the restart is coordinated across all applications
independent of dependencies.
If xx is not specified then 00 is assumed unless the TI575 is in the
FAULT mode, then 02 is assumed.
If the PLC is in the fault mode and xx is specified, it must be 02 or the
restart is disallowed.
If the PLC is in the fault mode, xx = 02, and the battery is bad, then
the PLC memory is cleared.
TC36
Execute Partial
(Hot) Start
Command:
Response:
36 [xx]
36
Field xx is added for multi-PLC/multi-application systems (e.g., TI575) and
has the following characteristics.
If xx is not coded or xx = 00, then the restart is for this application only.
If xx = 01, then the restart is coordinated across locked applications.
If xx = 02, then the restart is coordinated across all applications
independent of dependencies.
If xx is not specified then 00 is assumed unless the TI575 is in the
FAULT mode, then 02 is assumed.
If the PLC is in the fault mode and xx is specified, it must be 02 or the
restart is disallowed.
If the PLC is in the fault mode, xx = 02, and the battery is bad, then
the PLC memory is cleared.
2-8
Task Code Definitions
TI575 Task Code