Download HPD2, HPD 5, HPD8, HPD16 User Manual
Transcript
Parker Hannifin S.p.A. - Divisione S.B.C. HPD User’s Manual 2.7 Power connections For the motor cable consider Choice between cable for fixed or floating installation. Cable must be shielded and suitably sized in terms of insulation and wire sections. Reticulated polypropylene is the preferred insulation material. Length (max 100 m); note that conductor-conductor capacitance must not exceed 8 nF. If cable length exceeds 50 m install a triple 1 mH inductance between drive and motor with rated current identical to HPD rated current. Minimum conductor size is 1.5mm2 for HPD2 and HPD5 , 2.5mm2 for HPD8 and 4mm2 for HPD16. For the mains power cable Power cables must not be shielded. Minimum conductor size is 1.5mm2 for HPD2 and HPD5, 2.5mm2 for HPD8 and 4mm2 for HPD16. Input fuses must be rated as follows: MODEL HPD2 HPD5 HPD8 HPD16 Slow blow fuses (A) 6 10 16 20 Resolver cable The cable must comprise 4 twisted pairs with individual shields and one common shield. Capacitance for the length of cable must not exceed 10 nF; wire size must be no less than 0.35mm2. Maximum length is 100 m. EMI filter connection The connection between filter and drive must never exceed 30 cm. If the distance is less than 15 cm unshielded cables are possible, otherwise a shielded cable must be used. Earth connections To reduce the length of individual conductors that must be connected to earth we recommend using an earth busbar located as near as possible to the drive. The busbar must be made of copper to Length (m) width (mm) thickness ensure low inductance. It must also be (mm) mounted on insulated fixings. The adjacent 0.5 20 6 table shows minimum dimensions according to 1 40 6 length. 1.5 50 6 23