Download Chromalox
Transcript
O UT3 P A GE RESET AUX ▲ This setup PAGE appears only if the controller is equipped with Outputs #3 and #4. ▼ Output #3 Page MENU Description Available Settings T Y P3 Output #3 Type 47 A LR3 Alarm #3 Type 48 RLY3 Alarm #3 Relay Action 49 Security OFF = Disabled C ALR = Alarm Output ENT = Event Output (Setup Event Output parameters on Ramp/Soak Page) NONE = Disabled (off) Hi = High Alarm Lo = Low Alarm HiLo = High-Low Alarm PDE = Plus Deviation Alarm -DE = Minus Deviation Alarm DE = Plus/Minus Deviation Alarm LooP = Control Loop Protection Alarm NDE = NE = NDEL = NEL = Normally de-energized non-latching Normally energized non-latching Normally de-energized latching Normally energized latching Low Setpoint is used for low and -deviation setpoints AL O3 LO3 Alarm #3 Low Setpoint Instrument Sensor Span High Setpoint is used for high and +deviation setpoints AH I3 HI3 Alarm #3 High Setpoint Instrument Sensor Span DB3 Output #3 Dead Band (Alarm Hysteresis) 0 to 100°F INH3 Alarm #3 Inhibit 50 48 OFF ON Chromalox 2104 Technical Manual