Download CFW11 - PLC11-02 Module Programming Manual

Transcript
Parameter Settings
P1220 – CAN Status
Adjustable
Range:
Proprieties:
0 = Inactive
1 = Auto-baud
2 = CAN Active
3 = Warning
4 = Error Passive
5 = Bus Off
6 = No Bus Power
Factory
Setting:
-
RO
Access groups via HMI:
01 PARAMETER GROUPS..
∟ 51 PLC11
l
∟ 130 System Parameters
l
Description:
It informs the CAN network current status.
P1221 – Received CAN Telegrams
Adjustable
Range:
Proprieties:
0 to 65535
Factory
Setting:
-
RO
Access groups via HMI:
01 PARAMETER GROUPS..
∟ 51 PLC11
l
∟ 130 System Parameters
l
Description:
It informs the number of telegrams received through the CAN network.
P1222 – Transmitted CAN Telegrams
Adjustable
Range:
Proprieties:
0 to 65535
Factory
Setting:
-
RO
Access groups via HMI:
01 PARAMETER GROUPS..
∟ 51 PLC11
l
∟ 130 System Parameters l
Description:
It informs the number of telegrams transmitted through the CAN network.
21