Download PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL
Transcript
PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL Bulletin AE01B-A0552-001 © 2009 - 2012 CommScope, Inc. All rights reserved. Rev: L (12/12) PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL Table of Contents Section 1 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.1Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1.4Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Figure 1 — Terminal Strip Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Figure 2 — Terminal Strip Discrete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Figure 3 — Pin and Jumpers Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Section 2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.1 Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 2.1.1 Installation Kit Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.2 Controls and Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 2.2.1 Event Log Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 2.3 Installing the Dehydrator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.3.1 Wall Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 2.4 Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.4.1 AC Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 2.4.2 DC Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.5 Connecting the Alarm Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.6 Connecting Dehydrator to the Transmission Line . . . . . . . . . . . . . . . . . . . . . . . . . . .8 2.7 Checking Individual Line Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 2.8 Purging the Transmission Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 2.9 Adjusting Output Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 Section 3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.0Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.1 Regular Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.2 Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.3 Dehydrator Filter Element Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.4 Annual Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.4.1 Check the ground wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.4.2 Check the hour meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3.5 Parts Replacement and Dehydrator Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3.5.1 In Case Of Difficulty: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3.5.2Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3.5.3 Overhaul Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3.5.4 Unit Shutdown and Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3.5.5 Remove the compressor for overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3.6 Service Restoration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Section 4 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Section 5 Figure 4 — Wire Schematic with Summary Alarm . . . . . . . . . . . . . . . . . . . . . . . . . 14 Figure 5 — Wire Schematic with Discrete Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Figure 6 — PMT200B Pneumatic Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Overhaul Kit PMT200B–KIT–OVRHL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Filter Element Replacement Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 PMT200B–KIT–ELMNT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 2 PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL Filter Bowl Assemble Replacement Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 PMT200B–KIT–FLTRS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Filter Bowl Assemble and Dryer Tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Replacement Kit PMT200B–KIT–DRYER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Solenoid Replacement Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 PMT200B–KIT–SOLND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Section 6 Customer Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 6.0Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 6.1 In Case of Trouble . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 6.2 Initial Steps by CommScope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 6.3 Repair Center Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 6.4 RoHS Inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Section 7 DC Inverter Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 7.1Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 7.2 Installing the 24 Vdc to AC inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 7.3 Installing the 48 Vdc to AC inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 3 PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL The PMT200B maintains transmission line pressures at 21 kPa (3.0 psig). It is intended for standard microwave antenna applications and any other transmission line pressurization requirement that supports a medium pressure limit. The output pressure is adjustable from 13.8 kPa (2.0 psig) to 41.4 kPa (6.0 psig). Section 1 General Information 1.1Introduction This manual contains the information you need to install, operate and maintain your PMT200B Series DryLine® dehydrator. Please take the time to read this manual before attempting to operate or service the unit. 1.3Operation PMT200B Theory of operation. The PMT200B series of DryLine® dehydrators, while similar in moisture removal technology, operates differently than some of the DryLine® series of dehydrators. In order to provide a constant supply of dry air to small air volume systems, and to maintain an acceptable dryness level in the product air stream, a highpressure reservoir tank is utilized. This reservoir tank is connected to a pressure regulator and orifice to yield a fixed output pressure of 21 kPa (3.0 psig) and a nominal flow rate of 5.7 SLPM (0.2 SCFM). In addition to supplying the output air, the reservoir tank also provides the dry air for the feedback loop. The feedback loop is necessary to maintain the dryness of the membrane cartridge. This appliance is not intended for access by the general public. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. During normal operation, the bleed air in the feedback loop will cause the pressure to slowly drop in the internal reservoir tank, and the PMT200B compressor will cycle automatically. These cycles will take place regardless of the system volume or condition of the transmission line the dehydrator is connected to. The rate of these cycles, however, will vary. 1.2Description When connected to a very tight system, or the output is capped, the dehydrator will cycle approximately every 60 minutes and maintain 21 kPa (3.0 psig) system pressure. When open to atmosphere, the dehydrator will cycle approximately every 3 minutes while providing close to 5.7 SLPM (0.2 SCFM) of dry air. A system that leaks will have a cycle time somewhere in between, depending on the severity of the leaks. PMT200B Series DryLine dehydrators provide dry air for pressurizing small (up to 1700 liters (60 ft3), in volume) antenna and transmission line systems. The dehydrators produce –45º C (–50º F) dewpoint dry air at an output rate of 5.7 SLPM (0.2 SCFM). ® Each dehydrator consists of an electricallydriven air compressor, a membrane dryer assembly, an automatic transmission line pressure sensing system and alarm outputs housed in a rigid metal chassis. It is designed to mount directly to the wall or as a free-standing unit. The front panel features a control interface with display for alarms and pressure. For easy serviceability, power connections, alarm output connections and all filter elements are accessible from the top or front of the unit. The display will also reflect a pressure between 0 and 21 kPa (3.0 psig) while the output flow is between 0 and 5.7 SLPM (0.2 SCFM). The pressure sensor tracks the pressure beyond the flow control orifice and will show the actual pressure in the transmission lines (or to the distribution manifold). 4 PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL During the initial pressurization of the transmission line, the dehydrator will cycle every 2 to 4 minutes with the system at 0 psig pressure. As the dehydrator pressurizes the system, the cycle times will increase and the pressure will rise until the dehydrator output is balanced with the system leak, at which point the cycle times will stabilize. DISCRETE Alarm WIRE WIRE ALARM TERMINALCOLOR FUNCTION 1.4Alarms The PMT200B offers Low Pressure and Excess Run alarms as a standard feature; a summary alarm connection is provided on all units. Alarm conditions are indicated on the display. The alarms are Form C dry contacts and have connection options for normally open (NO) or normally closed (NC) configurations. The external alarm monitoring system (supplied by others) is connected to the terminal strip located on top of the cabinet. A small slotted screwdriver is necessary to make the connections. Pin 1 SUMMARY NO SUMMARY COM SUMMARY NC Pin 1 Activates when the Excess Run, and/ or Low Pressure alarms are triggered. It will also report High Humidity if unit is equipped with full alarms. The summary alarm does not report Power Fail. Power Fail: Activates when power is removed from the dehydrator. This includes turning the power off at the switch. Factory run time set in accordance with the normal run time for the dehydrator application. Selectable times are 1, 10, 30, 120 and 240 minutes, with the 10 minute selection used on the PMT200B as the default setting. Low Pressure: If system pressure falls below the low–pressure trigger point (6.9 kPa (1.0 psig) on the PMT200B), the lowpressure alarm sensor will activate an alarm contact. This alarm is an indication of a significant system leak or a dehydrator failure. Summary Alarm WIREWIRE ALARM TERMINAL COLORFUNCTION RED WHITE BLACK Summary: Excess Run: Figure 1 — Terminal Strip Summary 1 2 3 EXCESS RUN NO EXCESS RUN COM EXCESS RUN NC HIGH HUMIDITY NO HIGH HUMIDITY COM HIGH HUMIDITY NC POWER FAIL NO POWER FAIL COM POWER FAIL NC LOW PRESSURE NO LOW PRESSURE COM LOW PRESSURE NC High Humidity: Activates when system or dehydrator output humidity rise above 7.5% relative humidity. At initial installation, this alarm will continue to alarm until the system has been properly purged. The connections to the alarm strip are as follows; refer to Figure 1 for correct locations and colors of the wires on the terminal strip WHITE TAN BLUE BROWN PINK GREEN BLACK VIOLET RED ORANGE YELLOW GRAY Alarm Definitions: Additionally, a discrete alarm option is available with discrete connection for Low Pressure, Excess Run, High Humidity and Power Fail alarms. The discrete alarm version also includes a summary alarm contact. Pin 3 1 2 3 4 5 6 7 8 9 10 11 12 Pin 12 Note: All of the alarms clear and reset automatically, but can be manually reset in the display menus. However, if the alarm condition still exists, the alarm will return immediately after being reset. Figure 2 — Terminal Strip Discrete 5 PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL NOT IN USE USB P1 HIGH PRESSURE SENSOR U2 Vdc INPUT P2 (MR050B ONLY) HUMIDITY SENSOR P3 115 Vac COMP OUTPUT P4 LOW PRESSURE SENSOR U2 (MT/PMT SERIES) SOLENOID (FILTER DRAIN MT/PMT SERIES) P6 AC MAIN [ [ SUM ALARM P8 NOT IN USE P7 1.5 KEYPAD J4 (NO/NC) DISCRETE ALARMS P9 Figure 3 — Pin and Jumpers Location Specifications PMT200B Dehydrator Output Pressure Constant, kPa (psig) Output capacity Height, cm (in) Width, cm (in) Depth, cm (in) 45.7 (18) 44.45 (17.5) 17.8 (7) 16.55 (36 1/2) Alarms –45° C (-50° F) or better Operating Temperature Range Output Connector Dimensions Net weight, kg (lb) 340 SLPH (12.0 SCFH) 5.6 SLPM (0.2 SCFM) (total, approx.) Output Dew Point, Electrical Input 21 (3.0) Power Fail Alarm -10° to +50° C (+14° to +122° F) High Humidity Alarm Set Point 115 ±10% Vac, 60 Hz 240 ±10% Vac, 50 Hz 24 or 48 Vdc with Inverter Excess Run Alarm Low Pressure Alarm, kPa (psig) 3/8” polytube, compression 6 loss of input power 7.5% RH, factory set 10 minutes, factory set 6.9 (1.0) PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL Keypad Controls: Section 2 Installation 2.1 Advances display (scrolls ahead) to the next display or program mode with out changing the values in the microprocessor memory. Unpacking and Inspection Open carton. Enters into the microprocessor memory the values displayed in the window and advances display (scrolls ahead) to the next program or display mode. Numerically increase displayed settings in display window. When depressed longer than 1/2 second scrolling will occur at a faster rate. Numerically decrease displayed settings in display window. When depressed longer than 1/2 second scrolling will occur at a faster rate. Used to allow the user quick access to the system event log. Check the dehydrator for shipping damage such as dents or loose parts. 2.1.1 Installation Kit Items Polyethylene Tubing Kit, (25 FT) PTFE Tape, 1/4 Wide (1 Roll) Ball Valve, 3/8 Poly To 3/8 Poly (1) Male Conn, 3/8" Poly To 1/8 NPT Male (2) Street Elbow Fitting, 1/8 NPT (M-F) (2) Power Cord, w/Nema 515p Plug (North America)(1) Power Cord, IEC, Harm, (Stripped Leads) (1) Screw Pan Head, 10-32 X .50, w/Plastic Washer (8) 2.2 2.2.1 Event Log Codes EV= 0 Event = Power Up EV= 1 Event = High Humidity Alarm EV= 2 Event = Excessive Run Time Alarm EV= 3 Event = Low Pressure Alarm EV= 4 Event = High Pressure Alarm Controls and Displays Default password is 1111 EV= 5 Event = Compressor Fault Familiarize yourself with the controls and displays prior to installing or testing the dehydrator. EV= 6 Event = Log Cleared EV= 7 Event = Powering Down EV= 8 Event = Compressor Lifetime Eeprom Fail 2.3 Installing the Dehydrator 2.3.1 Wall Mounting See drill template AE01B-D0526-001 included with installation kit. 7 PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL 1.00 8.00 Proper electrical connection is required. It is suggested a licensed electrician be contracted to connect the AC wiring to the unit, if it is connected directly to the mains. Failure to properly connect the power wires could result in a dangerous electrical shock hazard. PMT200A WALL DRILL TEMPLATE AE01B-D0526-001 CAUTION: This unit is designed for connection to a single phase power source. Connection to a 3 phase power source will cause significant damage to internal components. REV: B INSTRUCTIONS: 1. Tape template to wall. 2. Use marked holes as drill template. 3. Use appropriate screws (minimum size #10) and anchors for wall material, and dehydrator weight. 2.4.2 9.50 For details see section 7. Test the Dehydrator To insure that all internal dehydrator components are properly dried, operate the DryLine® unit for at least 45 minutes prior to connecting the output air line to the transmission line system. Turn the dehydrator ON there is about a 4 second delay and check the output ports on top of the unit to make sure air is flowing. To do this, make sure that corresponding shut-off valve is open and the plugs are removed from the ports. Power Connections Confirm your dehydrator electrical input matches the available power. 2.5 Pin 1 PMT200B-81015 and PMT200B-81315 115 ±10% Vac, 60 Hz 24 or 48 Vdc with Inverte Pin 12 Place alarm connection wires in proper terminals and tighten the screw on the terminal block. PMT200B-81026 and PMT200B-81326 240 ±10% Vac, 50 Hz (See Section 1.4 for alarm location) The relay contacts are rated at 2 A (noninductive), 30 Vdc. AC Power 2.6 AC units should be connected into a standard 15 A power receptacle of the proper voltage. Make sure the power circuit is properly grounded. Two power cords are supplied, one 115 Vac American and one 240 Vac International. Connecting the Alarm Outputs To connect the alarms, locate the terminal block (TB–1) on top of the unit. Ensure an electrical safety ground is installed on the ground stud located adjacent to the power input connector. (It is intended to be customer installed in the field to your halo grounding system.) 2.4.1 DC Power The PMT200B can operate on 24 Vdc or 48 Vdc with the addition of an optional inverter. Caution: Check the system pressure rating before connecting the dehydrator to the transmission line system. 2.4 CAUTION: 8 Connecting Dehydrator to the Transmission Line CAUTION: Check the antenna and transmission line system pressure rating before connecting the dehydrator to the system. PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL Using supplied PTFE tape screw one of the included 3/8” compression fittings into the output bulkhead. There is an elbow and a straight compression fitting included with the unit. 2. Wait 15 minutes while the air absorbs moisture in the system, then disconnect the dehydrator from the transmission line and allow the air to vent. 3. Repeat steps 1 and 2 twelve times to purge the system. Insert one end of the 3/8 in, polytube feed line tubing into the compression fitting on the dehydrator output port. Tighten securely with a 9/16 in, wrench. Be careful not to over tighten. Connect the other end of the polytube to the transmission line. 2.9 Output pressure can be adjusted between 13.8 kPa (2.0 psig) and 41.4 kPa (6.0 psig) - adjustment outside this range will have a negative impact on the performance of the dehydrator. Four air outputs are provided, with individual shut–off valves on the unit. Make sure that the valve is in the open position for each transmission line connection. If one of the output connections is not used, close the valve and leave the port capped. 2.7 Checking Individual Line Pressures In order to check individual line pressures with the PMT200B, you will need to close the valves on all of the lines except for the one that you are checking. With the keypad, scroll to the “System Pressure” screen and the reading is the pressure on the isolated line. Repeat with each additional line and don’t forget to re-open all of the valves when finished. NOTE: Some components have been removed for clarity to see the regulator. 1. Locate regulator Note: If the transmission lines have not been purged, continue with section 2.8. Otherwise proceed to section 3. 2.8 Adjusting Output Pressure 2. Loosen lock nut Purging the Transmission Line 3. With unit running turn stem CW to increase. CCW to decrease output pressure. Air in the transmission line system must be replaced with dry air to ensure satisfactory operation of the transmitted signal. 4. Place finger on output to verify pressure setting on the front display. 5. Repeat step 3 and 4 until desired pressure is set. 1. Determine the total system volume. 6. Tighten lock nut and return unit to service. 2. Divide the system volume by the flow rate of the dehydrator 340 SLPH (12 SCFH) to determine the number of hours needed for the purge cycle. 3. Open the far end of the transmission line. 4. Operate the dehydrator for a minimum three purge cycles. If possible, operate for 12 purge cycles to completely dry the line. If it is not possible to open the far end of the transmission line, follow these steps: 1. Connect the dehydrator to the transmission line and pressurize the system. The system pressure should reach 21 kPa (3.0 psig). 9 PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL Section 3 Operation 3.4 Warning: Electrical Hazard! Unplug power cord before servicing unit. 3.0Maintenance The PMT200B DryLine® Dehydrator requires relatively little maintenance to ensure satisfactory operation over long periods of time. This section outlines the recommended annual preventive maintenance for the unit and the suggested overhaul for every 6000 hours of compressor operation. 3.1 Inspection includes checking for loose or damage hoses, fittings and electrical connections. Open the top panel or front door and verify that there is no water build-up in the two filter bowls located inside the front cover of the dehydrator. There may be some droplets of water in the filter bowls (the lower portion of each bowl), but there should be only a small amount of liquid in either bowl. Regular Maintenance The PMT200B DryLine® Dehydrator performs at its optimum if it is routinely checked for correct performance. This checking generally consists of an annual inspection of the condition of the air intake filter and an overhaul after every 6000 hours of compressor operation. Performance of these measures is sufficient to ensure continued reliable operation. 3.2 Annual Inspection Preventive Maintenance The annual maintenance of a PMT200B consists of a preventative maintenance inspection of the dehydrator and cleaning (or replacement) of the foam air intake filter. These tasks can easily be performed in the field with the unit connected to the transmission line system and with only the front access door opened for maintenance. 3.3 If there is excessive water, refer to the troubleshooting section. Replacement of the filter elements in the water filter and coalescing filter is covered in the overhaul section of this manual.Check the electrical connections. Dehydrator Filter Element Replacement Check the screw at the power input connector to ensure that the AC power cord is securely terminated. Check the screw-in alarm terminals to ensure that all wire connections are tight. Replace the air intake filter The air intake filter protects the compressor from contamination and dust. Periodic replacement extends the life of the compressor. To gain access to the element, push in on the cover and rotate the house approximately 1/4 turn CCW. The filter is made of a fibrous material. It should be replaced once a year (or more frequently, if the operating environment is very dusty.) A loose or damaged connection may result in erratic operation and unnecessary downtime. Refer to the troubleshooting section if an electrical problem is encountered. 3.4.1 CAUTION: Ensure an electrical safety ground is installed on the ground stud located adjacent to the power input connector. (It is intended to be customer installed in the field to your halo grounding system.) Do not apply oil or other chemicals to the filter element. Make sure the element is seated completely in the housing and then replace the cover. If a new element is used, discard the old element. Check the ground wire. 10 PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL 3.4.2 3.5.4 Check the hour meter In order to perform an overhaul on the PMT200B, the unit must be turned off and removed from service. As this is being done, the low pressure alarm may active through a reporting alarm system. Personnel monitoring such an alarm should be notified in advance so that they are aware of the fact that service is being performed. It is also necessary to disconnect the dehydrator dry air output from the waveguide system during the overhaul. Check the hour meter in the display to help to determine the duty cycle of the dehydrator. If the dehydrator has been running for more than 20% of its installed time, check the systems for leaks. Also check the time on the meter to determine if it is time to perform the 6000–hour overhaul. 3.5 Parts Replacement and Dehydrator Overhaul 3.5.5 CommScope PMT200B DryLine® Dehydrators are designed to give many years of trouble-free service and require very minimal maintenance. The dehydrator contains, as a standard feature, an electronic hour meter that records compressor run hours. To ensure continuous and reliable operation, the dehydrator must be overhauled every 6000 hours of compressor operation. The overhaul kit, listed below, contains all of the necessary parts to perform this overhaul. The dehydrator overhaul kit includes parts to overhaul the compressor and critical components in the dehydrator that often become worn over time. 3.5.1 Remove the compressor for overhaul. In Case Of Difficulty: If the dehydrator is not operating, refer to Section 2 on Installation and Section 4 on Troubleshooting the unit. 1. To remove the compressor, open the upper front panel of the unit.. 3.5.2Tools The following tools are used in the maintenance and overhaul procedures. 3.5.3 Unit Shutdown and Removal • Adjustable open—end wrench • Allen wrench 5/32 • #2 Phillips screwdriver • Small flat-blade screw-driver Overhaul Procedure When the PMT200B compressor run time reaches 6000 hours (or a multiple of 6000 hours) it is time to replace certain items in the compressor and the air path of the dehydrator. These include the piston cups, piston seals and head gaskets of the compressor, the filter elements in the water and coalescing filters, and the tube section connecting the compressor output to the coalescing filter input. 11 PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL Follow the instructions included in the compressor overhaul kit. When the overhaul is complete, reinstall. 3.6 Service Restoration RECOMMENDATION: If the dehydrator overhaul process has taken more than a few hours, it is recommended that the unit be run for one hour into the room, to purge the membrane dryer and tank of any acquired moisture, before reconnecting to the transmission line system.. 2. Disconnect compressor wiring from control board. (Board is shown pulled out for clarity) 3. Disconnect tubing from filter bowl assembly input. 4. Remove screws from the bottom of chassis holding the rubber isolators. 12 PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL Section 4 Troubleshooting If you experience difficulty with your dehydrator, use the troubleshooting procedures described below. Caution: Electrical troubleshooting requires access to potentially dangerous voltages and should only be performed by a licensed electrician. Problem/Condition Solution If the display light falls to light, make sure the unit is plugged in and power outlet is operating. Dehydrator display does not light, unit does not run. If you still have no light, unplug the unit, remove the unit cover and check for loose connections. Refer to the wiring diagram for proper connections. Figure 4 for summary alarm unit or figure 5 for discrete alarm unit Check to ensure that proper AC voltage is being supplied to the input. Turn shut-off valve to the off position and observe pressure gauge. The pressure gauge line should read approximately 21 kPa (3.0 psig) and the alarm should clear. If alarm does not clear, remove cover and verify tubing and wiring connections are secure. Low-pressure alarm activated. If the pressure does not stay constant after shutting off the valve, apply leak detector to isolate the leak in the dehydrator (exercise care when applying solution not to wet wiring or electronics). With dehydrator isolated from transmission line, observe pressure in transmission line. If pressure drops, use a leak detector solution to locate leaks in the transmission line. Repair leaks if possible. If the problem persists contact CommScope Customer Service. (see section 6.0) Check the display on the controller. Toggle the ON/OFF switch (attached to power connection). Compressor does not turn. Check input voltage per wiring diagram If the problem persists contact CommScope Customer Service. (see section 6.0) Ensure that the drain line tubing (exiting the bottom of the drain solenoid) is not clogged. When the compressor cycles off, air and moisture should flow out of the drain line (into drain pan). Filter bowls show excessive water. If solenoid does not vent, verify proper voltage is present when compressor is running and absent when compressor is off. If proper voltage is present and solenoid does not shift, replace solenoid. (See section 5 for replacement parts.) 13 DISCRETE ALARMS P9 THERE IS A GROUND STUD ON THE DOOR A GREEN/YELLOW STRIP WIRE FROM THE DOOR GROUND STUD TO THE CHASSIS GROUND STUD. SUM ALARM P8 RED WHITE BLACK BLACK ORANGE WHITE 6 14 1 BROWN BLUE GREEN LIGHTNING ARRESTOR GROUND WHITE BLACK BLACK WHITE GREEN WITH YELLOW STRIP GROUND Figure 4 — Wire Schematic with Summary Alarm EMI FILTER FACTURY INSTALLED JUMPER HARNESS ON -81026 AND -81326 DETAILS. 240 VAC JUMPER HARNESS WHITE BLACK POWER SWITCH SOLENOID Compressor PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL THERE IS A GROUND STUD ON THE DOOR A GREEN/YELLOW STRIP WIRE FROM THE DOOR GROUND STUD TO THE CHASSIS GROUND STUD. } GRAY YELLOW ORANGE RED VIOLET BLACK GREEN PINK BROWN BLUE TAN WHITE HUM Senior PURPLE YELLOW BLANK HUM P3 DISCRETE ALARMS P9 BLACK ORANGE WHITE 6 15 1 BROWN BLUE GREEN GROUND LIGHTNING ARRESTOR EMI FILTER WHITE BLACK BLACK WHITE GREEN WITH YELLOW STRIP GROUND Figure 5 — Wire Schematic with Discrete Alarm SUM ALARM P8 RED WHITE BLACK FACTORY INSTALLED JUMPER HARNESS ON -81326 AND -81026 DETAILS. 240 VAC JUMPER HARNESS WHITE BLACK POWER SWITCH SOLENOID Compressor PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL TANK ASSEMBLY 16 SOLENOID DRAIN REGULATOR ASSEMBLY Figure 6 — PMT200B Pneumatic Diagram COMPRESSOR CONTROL BOARD REAR VALVE ASSEMBLY DRYER AND FILTER BOWLS FRONT VALVE ASSEMBLY PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL Section 6 Customer Service Section 5 Replacement Parts 6.0Introduction Go to commscope.com eCatalog for the most current parts available for your dehydrator. CommScope provides in-warranty and outhttp://ZZZ.commscope.com/SURGXFWcatalog/#market-wireless of-warranty repairs as well as dehydrator and compressor overhauls from several Repair Centers. Coordination of these services is provided through the nearest Sales Office or Customer Service Center. The Center is also prepared to help you with the following: Overhaul Kit PMT200B–KIT–OVRHL 6.1 Filter Element Replacement Kit PMT200B–KIT–ELMNT • Technical Assistance • Troubleshooting • Repairs • Loaner Units • Spare Parts • Installation Materials • System Accessories In Case of Trouble The first step you should take if trouble develops using a dehydrator is to read the operators manual and follow the trouble isolating procedures given in it. If the steps in the manual do not identify and remedy the problem, then contact an CommScope Customer Service Center for 24– hour telephone assistance. Record the Model Number (e.g. PMT200B) and Serial Number from the product label, as you will be asked for these when you call. Two main locations are currently available to help: Filter Bowl Assemble Replacement Kit PMT200B–KIT–FLTRS From North America Telephone: 1-800-255-1479 Fax (U.S.A.): 1-800-349-5444 International Telephone: +1-779-435-6500 Fax Number: +1-779-435-8579 Filter Bowl Assemble and Dryer Tube Replacement Kit PMT200B–KIT–DRYER Web Access Internet: www.commscope.com email: #[email protected] Solenoid Replacement Kit PMT200B–KIT–SOLND 17 PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL 6.2 Initial Steps by CommScope account. Damages to loaner will be deducted from the P.O. When your call or fax communication is received, the CommScope staff will work with you to pinpoint the possible cause of trouble. If the pressurization equipment is suspect, they will: 6.3 • ask for your unit Model Number and Serial Number • check the warranty status of the unit • advise the availability of a loaner unit • provide an estimate of the cost for inspection and repairs, if the unit is out–of–warranty • fax a Return Material Authorization Sheet to you. PACKING INSTRUCTIONS: Pack your unit securely for shipment to the Repair Center. If you received a loaner unit, we suggest you use the box and packing materials to return your unit. Otherwise we have factory packing materials available for a nominal fee. Enclose a completed copy of this form inside the box and clearly mark your Company Name and RMA: XXXXXXX on outside of the box. Address the box to the following Ship–To Address: CommScope PESSURIZATION SERVICE CENTER RMA# XXXXXXX 11312 S. PIPELINE RD. EULESS, TX. 76040-6629 Repair Center Process A method of Payment must be provided prior to issuing of RMA regardless of warranty status. Please note, Units received with Biological/ animal contamination will be returned unrepaired or scraped after notification and you will be invoiced for inspection and freight. IN–WARRANTY REPAIR: Most CommScope pressurization products carry a warranty of one to three years, depending upon model number. Warranty details are available on our web page. If your unit falls within its warranty period, inspection and repairs will be performed at no charge and the unit will be promptly returned to you. If a warranty unit is deemed no problem found an inspection fee and freight will be charged to the customer. CONTACT NUMBERS: If you have any questions about the repair process or status of your unit, please contact us directly through one of the following methods – Telephone (below) TEL:817-864-4150 817-864-4155 FAX:817-864-4179 OUT–OF–WARRANTY REPAIR: We will inform you with the cost of repair and obtain your approval to proceed with repairs or, if you elect not to have the unit repaired, your instructions on disposition of your unit. When repairs are complete, we will return your unit and invoice you for the inspection charge, materials used for the repair and labor applied to complete the repair. If you elected not to repair the unit, we will invoice you for the inspection and freight charge if unit is to be returned. LOANER UNITS: Loaner units are available from the repair center to maintain your system while repairs are being performed. If you feel you need a loaner, please contact us at at one of the numbers listed under contact numbers. A P.O. for the full value of the unit must be issued prior to shipment. Also contact us when the loaner is ready to be returned so that we can issue a NEW RMA number to identify your return and create the appropriate credit to your 6.4 RoHS Inquiries For inquiries on RoHS please contact the following: CommScope Inc. Corke Abbey, Bray Co., Dublin, Ireland Attn: Legal Department 18 PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL Section 7 DC Inverter Option 7.1Introduction The standard 115 Vac unit can be run on an inverter with the input of 24 or 48Vdc inverter. The inverters are available in either 24 or 48 Vdc. Due to the induction of a dc motor in the compressor pulling so many amps and the cost of a dc compressor we choose to power the units with an inverter to keep the cost down and reduce the induction load on your battery systems. 7.2 Turn inverter on. Only green LED’s should be illuminated. Turn on Dehydrator. Installing the 24 Vdc to AC inverter Remove the inverter from its packaging and install in desired location. The inverter can be placed on a flat surface or mounted to a wall via the flanges and slots on the bottom of the inverter. Verify power switch is turned off on the inverter. Connect the power cord from the dehydrator to the AC receptacle located on the left side of the inverter. Connect the DC power to the lugs located on the right side of the inverter to the battery system. Ensure the polarity is correct. Improper connection can damage inverter and void warranty. 19 PMT200B SERIES DryLine® DEHYDRATOR USER MANUAL 7.3 Installing the 48 Vdc to AC inverter Remove the inverter from its packaging and install in desired location. The inverter can be placed on a flat surface or mounted to a wall via the flanges and slots on the bottom of the inverter. Turn inverter on. Only green LED’s should be illuminated. Turn on Dehydrator. Verify power switch is turned off on the inverter. Connect the power cord from the dehydrator to the AC receptacle located on the left side of the inverter. Connect the DC power to the lugs located on the right side of the inverter to the battery system. Ensure the polarity is correct. Improper connection can damage inverter and void warranty. 20