LK-SM-101
Single Packaged
Air Conditioner
SERVICE MANUAL
MODELS: LK-0329CH/AH
LK-0429CH/AH
LK-0529CH/AH
Contents
Model Number Nomenclature...............................................................................................3
General Data ..........................................................................................................................4
Dimensions ............................................................................................................................5
Refrigerant Circuit Diagram..................................................................................................6
Wiring Diagram ......................................................................................................................7
Troubleshooting Guide .........................................................................................................8
Features of Controller .........................................................................................................14
Exploded View and Replacement Parts List .....................................................................15
Specification of Components.............................................................................................18
—2—
Model Number Nomenclature
LK-0529CH
H: Horizontal Flow
C: Cooling Only
A: Gold Fin + Cooling Only
Development Sequence
2 : 220V, 60Hz, 1Ø
03 : 3 ton
Nominal cooling capacity
04 : 4 ton
05 : 5 ton
LG
Single Package Air Conditioner
—3—
General Data
Table-1
Nominal ton
Models
ARI Net Cooling Capacity
(Ton)
3
4
5
LK-0329CH/AH
LK-0429CH/AH
LK-0529CH/AH
Capacity
(BTU/hr)
35,000
47,000
57,000
(Kcal/h)
8,821
11,845
14,364
Electrical Data Voltage
(V,PH)
208~230V,1PH
208~230V,1PH
208~230V,1PH
M.C.A(with standard motor) Cooling
(Amps)
29
31
48
Power Input
Cooling
(Watt)
3,740
4,350
6,000
Performance Air Circulation
Nominal CFM CFM
1,050
1,590
1,750
SEER
Cooling
(BTU/hr.W)
10.0
11.0
10.0
Sound Rating
Cooling
dB(A)
8
8.4
8.4
Features LG Electronic Thermostat
Option
Option
Option
¥
¥
¥
Time Delay Safety Function
Cooling Operation Mode
¥
¥
¥
Heating Operation Mode(with E/Heater)
¥
¥
¥
Soft Dry Operation
Timer Setting (24-Hour on/off)
Auto restart mode
Humidifier function
Test function
Self-Diagnosis Function
Filter type
Compressor Type
Scroll
Scroll
Scroll
Quantity
1
1
1
Outdoor Coil Type
High efficiency
High efficiency
High efficiency
Tube size(O.D)
(inch)
9/32
9/32
9/32
(mm)
7.00
7.00
7.00
Row/FPI
1R/18FPI
2R/18FPI
2R/18FPI
Lengh
(inch)
55 1/8
55 1/8
55 1/8
(mm)
1,400
1,400
1,400
Face area
(sq.ft)
10.72
10.72
10.72
(m2)
1.00
1.00
1.00
Indoor Coil Type
High efficiency
High efficiency
High efficiency
Tube size(O.D)
(inch)
3/8
3/8
3/8
(mm)
9.52
9.52
9.52
Row/FPI
2R/18FPI
3R/18FPI
3R/18FPI
Lengh
(inch)
21 5/8
21 5/8
21 5/8
(mm)
550
550
550
Face area
(sq.ft)
4.51
4.51
4.51
(m2)
0.42
0.42
0.42
Outdoor Fan Type
Propeller
Propeller
Propeller
No. Used/Diameter(in.)
1EA/22"
1EA/22"
1EA/22"
Drive Type
Direct
Direct
Direct
CFM
3,500
3,500
3,500
No. Motor/Motor output(Hp)
1/0.33
1/0.33
1/0.33
Motor RPM
1,060
1,060
1,060
Indoor Fan Type
Centrifugal Blower Fan Centrifugal Blower Fan Centrifugal Blower Fan
No. Used
1EA
1EA
1EA
Diameter/Width(in.)
11"/11"
11"/11"
11"/11"
Drive Type/Motor Step
Direct/3
Direct/3
Direct/3
No.motors
1EA
1EA
1EA
Motor output(standard/oversized)
0.5Hp/N.A
0.75Hp/N.A
0.75Hp/N.A
Motor rpm(Standard/oversized)
840N.A
1,020/N.A
1,090/N.A
Drain Connection Size(in.)
3/4"
3/4"
3/4"
Refrigerant
(kg)
1.7
2.2
2.3
Refrigerant Charge
(lbs)
3.75
4.85
5.07
Type
R-22
R-22
R-22
Refrigerant Control
Capillary Tube
Capillary Tube
Capillary Tube
Dimensions Indoor unit (WxHxD)
(inch)
43 3/8*28 9/16*32 11/16 43 3/8*28 9/16*32 11/16 43 3/8*28 9/16*32 11/16
(mm)
1102*725*830
1102*725*830
1102*725*830
Weight
Net
(kg)
110
120
140
(lbs)
242.5
264.6
308.6
—4—
Dimensions
LK-0329CH/AH, LK-0429CH/AH, LK-0529CH/AH
CLEARANCE 34"
CLEARANCE 48"
(HORIZONTAL)
Unit : Inch(mm)
A
289/16 (725)
B
3211/16 (830)
C
433/8 (1102)
D
2011/16 (525)
E
27/8 (73)
CLEARANCE 34"
E
A
Center line of hole
D
B
1.5" Dia. hole power wires
C
1.5" Dia. hole other purpose
CLEARANCE 18"
Unit : Inch(mm)
1 1/2 (38)
C
9 1/2 (242)
3/4
G
(19)
E
55/8 (143)
F
24 1/4 (622)
G
11 9/16 (294)
H
9 1/16 (230)
F
H
D
E
B
RETURN
13 3/16 (335)
SUPPLY
A
A
—5—
B
C
D
Refrigerant Circuit Diagram
LK-0329CH/AH, LK-0429CH/AH, LK-0529CH/AH
PRESSURE LOW-PRESSURE
PORT
SWITCH
SUCTION
LINE
OUTDOOR
COIL
PRESSURE
PORT
S
DISCHARGE
LINE
D
CAPILLARY
TUBE
—6—
INDOOR
COIL
: REFRIGERANT FLOW
Wiring Diagram
LK-0329CH/AH, LK-0429CH/AH, LK-0529CH/AH
DIAGRAM WIRING(WITH LG'S THERMOSTAT)
1Ø 208~230V,60Hz
POWER SUPPLY
1Ø 208~230V,60Hz
POWER SUPPLY
(L)
USING
ELECTRIC
HEATER
NOTES
FACTORY WIRING BK:BLACK OR:ORANGE YL:YELLOW
OPTIONAL WIRING BR:BROWN RD:RED
FIELD WIRING
BL:BLUE
WH:WHITE
(N)
T/B : TERMINAL BLOCK
TRANS
(AC 24V)
BK
BK
BL
FUSE
(250V, 10A)
BK
T/B
#4
YL
LOW PRESSUTRE
SWITCH
TERMINAL BLOCK
RD
L1
L2
T1
T2
L1
L2
A
MAGNETIC
CONTACT
(For comp)
BK
WH
EH
4
0
6
1
CAPACITOR
ELECTRIC HEATER
H
C
RD
WH
F
OR
C
S
BL
R
YL
1
WH
2
AC 24V
3
Fan
4
Comp
5
Heater
BK
COMP
OR BK
THERMISTER
FOR EVA
(OPTION)
"X"
B
POWER RELAY
(For I/motor)
B
T2
MAGNETIC
CONTACT
(For E/heater)
BL
T1
A
CUT "X"POINT OF WIRE
AND CONNECT THERMISTER
WIRE ON THE EVAPORATOR(OPTION)
YL
T/B
#1
CAPACITOR
T/B
#2
BK
RD
b
AC 24V
L
(R)
N
(C)
1
(G)
2
(Y1)
3
(W1)
6
RD
LG'S THERMOSTAT
YL
BR
OR
RD
c
OR BK YL
T/B
#3
a
MOTOR
(IN)
MOTOR
(OUT)
RD
MODEL
a
b
c
3RT/4RT
BLACK
BLUE
RED
5RT
BLUE
BLACK
RED
P/NO:3854A30047S
DIAGRAM WIRING(WITH LOCALLY PURCHASED THERMOSTAT)
1Ø 208~230V,60Hz
POWER SUPPLY
NOTES
1Ø 208~230V,60Hz
POWER SUPPLY
(L)
USING
ELECTRIC
HEATER
FACTORY WIRING BK:BLACK OR:ORANGE YL:YELLOW
OPTIONAL WIRING BR:BROWN RD:RED
FIELD WIRING
WH:WHITE
BL:BLUE
(N)
T/B : TERMINAL BLOCK
TERMINAL BLOCK
TRANS
BK
TIME DELAY P.C.B
BL
BK
BL
CUT "X"POINT OF WIRE
AND CONNECT THERMISTER
ON THE EVAPORATOR(OPTION)
BL
FUSE
(250V, 10A)
BK
BL
L2
T1
T2
L1
L2
BK
A
B
WH
EH
CAPACITOR
ELECTRIC HEATER
H
C
RD
WH
F
"X"
MAGNETIC
CONTACT
(For comp)
AC 24V
C
OR BK
4
0
6
1
YL
2
Heater
THERMISTER
FOR EVA
(OPTION)
BL
T/B
#1
CAPACITOR
1
Comp
R
COMP
N
Fan
OR
S
L
AC 24V
POWER RELAY
(For /Imotor)
T2
LOW PRESSUTRE S/W
L1
YL
T/B
#2
RD
1
AC 24V
WH
2
Fan
BK
3
Comp
YL
4
Heater
BK
RD
b
3
ELECTRO-MECHANICAL
THERMOSTAT
RD
5
R
G
Y
W
MECHANICAL
THERMOSTAT
6
RD
YL
BR
OR
B
T1
MAGNETIC
CONTACT
(For E/heater)
A
RD
c
OR BK YL
MOTOR
(OUT)
MOTOR
(IN)
a
T/B
#3
MODEL
a
b
c
3RT/4RT
BLACK
BLUE
RED
5RT
BLUE
BLACK
RED
P/NO:3854A30047S
—7—
Troubleshooting Guide
In general, possible trouble is classified in two causes.
The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but ineffective cooling
Ineffective Cooling or Heating
Check of cold (warm) air circulation for smooth flow.
Check of outdoor coil
(heat exchanger) & the fan
operation.
Dirty indoor coil
(heat exchanger.)
Check gas leakage.
Malfunction of fan.
Repair gas leak.
Clogging of air filter.
Replacement of unit if the
unit is beyond repair.
Check heat load increase in
cooling operation.
Unexpected residue
Added electrical utencil
Obstruction at air outlet.
Check of inside gas
pressure.
Adjust refrigerant
charge.
Countermeasure against
above trouble.
Malfunction of compressor.
Check clogging in refrigeration circuit.
Repair clogging in refrigeration circuit.
Satisfactory operation with
temperature difference of
inlet & outlet air ;
COOLING : 7~10°C
HEATING : 15~17°C
—8—
Replacement of
compressor
Troubleshooting Guide
Fails to Start
Check power source.
Check of circuit breaker
and fuse.
Check control switch
setting.
Check control switch.
Compressor only fails to
start.
Fan only fails to start.
Electric heater is not energized
Improper wiring.
Drop of power voltage.
Defect of compressor
capacitor.
Loose terminal connection.
Improper wiring
Defect of fan motor
capacitor.
Irregular motor resistance
(Ω)
Capacitor check.
Irregular motor insulation
(Ω)
Replacement of capacitor.
Replacement of fan motor.
Improper electric heater
Irregular motor resistance ( Ω )
Regular but fails to start.
Replacement of electric
heater.
Irregular motor insulation ( Ω )
Replacement of compressor.
Replacement of compressor
—9—
Troubleshooting Guide
PACKAGE AIR CONDITIONER VOLTAGE LIMITS
NAME PLATE RATING
MINIMUM
MAXIMUM
208~230V
187V
253V
1. No cooling and heating operation performed
1) Both the blower and the compressor do not work
WHAT TROUBLED
Other parts except the
unit
COMPLAINTS
HOW TO CHECK
REMEDY
• Electric supply interrupted
• Defective power wiring
• Cut off power fuse
Measure power supply
with a tester in case that
the same power source is
supplied to other equipment except the unit,
what and where troubled
can be discovered by
checking the operation of
other equipment.
Too low voltage
Measure it with a tester.
Check the power source.
Use a thick cable if necessary.
Magnetic switch for compressor & fan motor
Control point is on condition of "OFF" due to trouble.
Make short-circuit, then
measure it with tester.
Replace it if necessary.
Operating switch
Troubled or defective
contactor
Check it with the eyes or
tester.
Repair or replace it.
• Repair a switch box and
relative instrument.
• Replacement of fuse
• Request a power
supplier to repair.
2) Only Indoor blowers do not work
WHAT TROUBLED
Motor
Capacitor
Electric wiring
COMPLAINTS
HOW TO CHECK
REMEDY
• Over heated
• Wiring short
Check it with tester
Repair or replace it.
Defected
Check it with a tester.
Replace it.
• Cut- OFF of wiring
• Short circuited on
operation
Check it with a tester.
Rewiring or Repair.
— 10 —
Troubleshooting Guide
3) Only outdoor fan does not work
WHAT TROUBLED
COMPLAINTS
HOW TO CHECK
REMEDY
Motor
• Over-heated
• Wire short
Check how it is insulated.
Repair or replace it.
Electric Wiring
Cut off of wiring
Check it with a tester.
Rewiring or repair.
Short circuited on
operation
4) Only compressor does not work
WHAT TROUBLED
COMPLAINTS
HOW TO CHECK
REMEDY
Magnetic switch for
compressor motor
Defective contact,
magnetic coil troubled.
Check it with the eyes on
with a tester.
Repair or replace it.
Compressor motor
Troubled over-heated
(layer short)
Check how it is insulated.
Replace or repair the
compressor.
High pressure switch
(Option part)
Troubled or defective
contact or operating
Check it with a tester.
Replace it if necessary.
Electric circuit
Defective connection or
disconnection of the circuit
for compressor.
Check it with a tester.
Rewiring or push reset
button.
— 11 —
Troubleshooting Guide
2. The Units discontinue after the operation started
WHAT TROUBLED
COMPLAINTS
HOW TO CHECK
REMEDY
Outdoor coil
Coil is dirty *1
Checking
Wash it by means of
something like chemical
washing.
In-condensable gas
blended.
Air intruded into the
refrigerant pipe line *1
In the event that
difference between the
saturating temperature
corresponding to high
pressure and the
temperature of air
discharged from the
outdoor coil is more than
15°C, incondensable gas
may be blended.
Extract air by vacuum
pump, then replenish
(charge) the refrigerant.
Improper adjustment
Check it with a pressure
gauge.
Read just it to normal
operating pressure.
(Note)
Don't alternate the
specified adjusting
pressure. If the adjusted
pressure exceed the
specified range, it will
cause a great accident.
A shortage of refrigerant
amount. * 2
Check pressure
Replenish the
refrigerant. Repair the
spot where it is leaked.
Reverse rotation of fan
Obstacle
Confirm the wind blowing
out upward.
Air short circuit *1
Check it with eyes.
If reversed, connect
interchanged wires to
each terminal.
Power wirings.
High pressure switch
(Option part)
Refrigerant
Outdoor Fan
Note: Use an appropriate measuring instrument for readjustment.
*1: High-pressure switch moves.
*2: Low- pressure switch moves.
— 12 —
Troubleshooting Guide
3. The unit is working, but not cooling and heating sufficiently
(Both blower and compressor are working)
WHAT TROUBLED
COMPLAINTS
HOW TO CHECK
REMEDY
Load
Much Cooling or Heating
load
Heat load increased.
Window or door has many
cracks or gaps.
Do necessary disposal
respectively.
Air flow
Obstacle disturbs Intake
of uniform airflow.
Checking
Correct it.
Short air volume
Reverse rotation of
blower.
Checking
Correct it.
Refrigerant
Shortage in the charged
refrigerant.
Coil inlet pipe is frosted
Recharge it.
(Repair the leakage spot).
Air passage
Improper or foreign bodies
Checking
Correct or clear the
foreign bodies.
Air filter
Clogged with dust
Checking
Cleaning
4. All the functions are performed as specified, but very noisy and vibrant
WHAT TROUBLED
Compressor
Blower
COMPLAINTS
HOW TO CHECK
REMEDY
Liquid refrigerant flooding
back from the evaporator.
• Check for refrigerant over-charge.
• Check to see if the intake air temperature is
extremely cold.
• Check for insufficient air flow quantity.
Faulty Discharge valve
and suction valve.
• Checking
• Replace the
compressor
Fan broken.
Checking
Repair or replace it.
Clear the foreign bodies.
Foreign matters intruded.
Screws
Looseness or fail-off of
screws
Checking
Correct
Electric troubles
(Magnetic contactor)
Defective contact.
Defective contact point.
Rusting and foreign matters in the iron core contact face. Defective contact of the
operating switch.
Checking
Repair and clean or
replace it.
Others
Improper installation
Checking
Correct it.
— 13 —
Features of Controller
1. Timer PCB Circuit Diagram
12V
R03M
220K
8
R01M
47K
3
2
C01M
3.3uF
+
R06M
1K
+
-
R02M
47K
DO1M
1N4148
Q01M
KRC107K
1
12V
AC220V
60Hz
RY01M
JQ1a-12V
IC01M
KA393
4
L1
D02D~D05D
1SR139-600
12V
0
IC01D
1
7812
C04D
104
C01D
470uF
25V
ZNR
INR14D471
D04D
+
D02D
D05D
L2
D03D
L3
C02D
104
RY01M
JQ1a-12V
TRANS
2. Timer PCB ASSY
C1
CN2
R10
Q2
D6
RY1
— 14 —
CN3
C4
R9
IC3
PCB: 2Q01062A
CN1
D2
D3
D5
IC2
C8
C6
R6
R8
R5
C7
D1
D4
Q1
C5
R4
D7 C2
R3
R2
R7
IC1
R1
C3
Magnetic
Relay
Exploded View and Replacement Parts List
1. LK-0329CH/AH, 0429CH/AH, 0529CH/AH
• Exploded View
249950
268716
W0CZZ-1
261704
W0CZZ-2
669200
666000
— 15 —
Exploded View and Replacement Parts List
346810
546810
554160
359012
559010
354210
554031
330870
552111
— 16 —
Exploded View and Replacement Parts List
Replacement Parts List
LOCATION
NO.
DESCRIPTION
249950
261704
268716
346810
354210
359012
546810
554031
554160
559010
566000
666000
669200
W0CZZ-1
W0CZZ-2
CONTROL BOX ASSY, SINGLE
TRANSFORMER, POWER
TIMER
MOTOR ASSY, INDOOR
EVAPORATOR ASSY, FIRST
FAN ASSY, BLOWER
MOTOR ASSY, OUTDOOR
CONDENSER ASSY, BENT
COMPRESSOR ASSY, FINAL
FAN ASSY, PROPELLER
SWITCH, PRESSURE
SWITCH, MAGNET
RELAY
CAPACITOR, DRAWING
CAPACITOR, DRAWING
552111
TUBE ASSY, CAPILLARY
330870
DRAIN PAN ASSY
738290
OWNERS MANUAL
738281
SERVICE MANUAL
REMOTE CONTROLLER
ASSEMBLY
REMOTE CONTROLLER
ASSEMBLY(WIRELESS)
267110
267110
P/NO.
REMARKS
LK-0329CH LK-0329AH LK-0429CH LK-0429AH LK-0529CH LK-0529AH
4995A10060B 4995A10060B
6170A10001E 6170A10001F
3Q010117C 3Q010117C
4681A20057C 4681A20057C
5421A10002T 5421A10002T
2A00578V
2A00578V
4681A20039B 4681A20039B
5403A10021A 5403A10021B
2520UFDK1AA 2520UFDK1AA
5901A10010A 5901A10010A
6600A20004D 6600A20004D
2A00771F
2A00771F
6920AP3194B 6920AP3194B
0CZZA20001B 0CZZA20001B
6120AR2194K 6120AR2194K
5211A10268A
5211A10268B(WITH TROPICAL CYCLE)
4995A10060A 4995A10060A 4995A10060E 4995A10060E
6170A10001E 6170A10001F 6170A10001E 6170A10001F
3Q010117C 3Q010117C 3Q010117C 3Q010117C
4681A20057B 4681A20057B 4681A20057B 4681A20057B
5421A10002S 5421A10002S 5421A10002S 5421A10002S
2A00578V
2A00578V
2A00578V
2A00578V
4681A20039B 4681A20039B 4681A20039B 4681A20039B
5403A10019A 5403A10019B 5403A10019A 5403A10019B
2520UFJK1AA 2520UFJK1AA 5416A10002B 5416A10002B
5901A10010A 5901A10010A 5901A10010A 5901A10010A
6600A20004D 6600A20004D 6600A20004D 6600A20004D
2A00771F
2A00771F
2A00771F
2A00771F
6920AP3194B 6920AP3194B 6920AP3194B 6920AP3194B
0CZZA20001B 0CZZA20001B 0CZZA20001B 0CZZA20001B
6120AR2359U 6120AR2359U 0CZZA10001A 0CZZA10001A
521110250A
5211A10270A
5211A10268B(WITH TROPICAL CYCLE)
3087A10017A
3828A20228A(SPANISH WITH NOM)
3828A20228B(ENGLISH)
3828A20228C(SPANISH + ENGLISH)
3828A20228G(ENGLISH +ARABIC)
3828A20228L(SPANISH FOR MIRAGEL)
3828A20220B 3828A20220B 3828A20220B 3828A20220B 3828A20220B 3828A20220B
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
6711A20063A(OPTION PART)
R
6711A20041R(OPTION PART)
R
— 17 —
Specification of Components
LK-0329CH/AH
COMP
INDOOR MOTOR
OUTDOOR MOTOR
OUTDOOR FAN
INDOOR BLOWER
LOW PRESSURE SWITCH
CAPACITOR for COMP.
CAPACITOR for ***IDM.
CAPACITOR for ****ODM.
CAPILLARY TUBE
P/No.
Model name
*RLA
**LRA
Q'ty
P/No.
Output
Shaft Dia.
RPM
P/No.
Output
Shaft Dia.
RPM
Q'ty
P/No.
Diameter
P/No.
Diameter*Width
P/No.
Spec.
Rated volt.
Maker
P/No.
Spec.
P/No.
Spec.
P/No.
Spec.
P/No.
Spec.
Q'ty
TRANSFORMER
CONTACTOR for COMP.
RELAY for IDM.
RELAY for ODM.
P/No.
Spec.
P/No.
Spec.
P/No.
Spec.
P/No.
Spec.
LK-0429CH/AH
LK-0529CH/AH
2520UFJK1AA
5416A10002B
SQ032KAA
SQ042KAA
H20R583ABCA
14.0
17.1
28
74
102
165
1
1
1
4681A20057C
4681A20057B
4681A20057B
0.5Hp
0.5Hp
0.5Hp
15 mm
15 mm
15 mm
840(Hi)
1,020(Hi)
1,090(Hi)
4681A20039B
4681A20039B
4681A20039B
0.33 Hp
0.33 Hp
0.33 Hp
15 mm
15 mm
15 mm
1,050
1,050
1,050
1
1
1
5901A10010A
5901A10010A
5901A10010A
O.D. 560mm
O.D. 560mm
O.D. 560mm
2A00578V
2A00578V
2A00578V
280(mm) × 280(mm)
280(mm) × 280(mm)
280(mm) × 280(mm)
6600A20004D
6600A20004D
6600A20004D
OFF:2.0kgf/cm2/ON:3.5kgf/cm2 OFF:2.0kgf/cm2/ON:3.5kgf/cm2 OFF:2.0kgf/cm2/ON:3.5kgf/cm2
AC 24
AC 24
AC 24
SAGINOMIYA
SAGINOMIYA
SAGINOMIYA
6120AR2194K
6120AR2359U
0CZZA10001A
45µF/400VAC
60µF/400VAC
55µF/400VAC
0CZZA20001B
0CZZA20001B
0CZZA20001B
15µF/450VAC
15µF/450VAC
15µF/450VAC
6120AR2194K
6120AR2359U
0CZZA10001A
6µF/400VAC
6µF/400VAC
6µF/400VAC
3E92334G
3E92334M
3H02633K
ID 1.4 × L1200(mm)
ID 1.4 × L1000(mm)
ID 1.4 × L750(mm)
5
8
8
6170A10001E
AC220V, 450mA
2A00771F
40A, 24V CONTROL
6920AP3194B
AC 24V, 25A
2A00771F
40A, 24V CONTROL
*RLA : RATED LOAD AMPERE
**LRA : LOCKED ROTOR AMPERE
***IDM : INDOOR MOTOR
****ODM : OUTDOOR MOTOR
— 18 —
6170A10001E
AC220V, 450mA
2A00771F
40A, 24V CONTROL
6920AP3194B
AC 24V, 25A
2A00771F
40A, 24V CONTROL
6170A10001E
AC220V, 450mA
2A00771F
40A, 24V CONTROL
6920AP3194B
AC 24V, 25A
2A00771F
40A, 24V CONTROL
P/No.: 3828A20220B
May, 2002
Printed in Korea