Download Operation

Transcript
WEBSITE
http://lgservice.com
Room Air Conditioner
SERVICE MANUAL
CAUTION
-BEFORE SERVICING THE UNIT, READ THE SAFETY
PRECAUTIONS IN THIS MANUAL.
-ONLY FOR AUTHORIZED SERVICE PERSONNEL.
MODEL: LS-135GB/GM/GR
LS-1351GB/GM/GR
LS-1352GB/GC/GD/GM/GR/GW
LS-1202GB/GC/GD/GM/GR/GW
LS-1262GB/GC/GD/GR/GW
C142CM/CR
Contents
LG Model Name ...................................................................................................................... 3
Functions ................................................................................................................................ 4
Product References .............................................................................................................. 7
Dimensions ............................................................................................................................. 8
Refrigeration Cycle Diagram ............................................................................................... 10
Wiring Diagram..................................................................................................................... 11
Operation Details ................................................................................................................. 12
Display Function .................................................................................................................. 19
Installation ............................................................................................................................ 20
Operation .............................................................................................................................. 33
Disassembly of the parts (Indoor Unit) .............................................................................. 34
2-way, 3-way Valve................................................................................................................ 37
Cycle Troubleshooting Guide.............................................................................................. 45
Electronic Parts Troubleshooting Guide............................................................................ 46
Electronic Control Device.................................................................................................... 55
Schematic Diagram .............................................................................................................. 59
Exploded View and Replacement Parts List...................................................................... 60
-2-
LG Model Name
2003~
1
Code
2
-
3
Type
4
5
6
Code of Model
7
8
9
10
Meaning
1
Producing Center,
Refrigerant
A~Z
L: Chang-won R22
A: Chang-won R410A
C: Chang-won R407C
T: China
K: Turkey R22
E: Turkey R410A
H: Thailand
N: India
Z: Brazil
D: Indonesia
M: Mexico
V: Vietnam
S: Out Sourcing
2
Product Type
A~Z
S: Split Type Air Conditioner
3
Cooling/Heating/Inverter
A~Z
C: Cooling only
H: Heat pump
X: C/O + E/Heater
Z: H/P + E/Heater
4, 5
Capacity
0~9
Cooling/Heating Capacity
Ex. "09" → 9,000 Btu/h
6
Electric Range
1~9
A~Z
1: 115V/60Hz,
2: 220V/60Hz
3: 208-230V/60Hz
5: 200-220V/50Hz
6: 220-240V/50Hz
7: 110V, 50/60Hz
8: 380-415V/50Hz
9: 380-415V/60Hz
7
Chassis
A~Z
Name of Chassis of Unit
Ex. LSP → SP Chassis
8
Look
A~Z
Look,
Color (Artcool Model)
9
Function
A~Z
10
Serial No.
1~9
V: AC Inverter C/O
N: AC Inverter H/P
Q: DC Inverter C/O
W: DC Inverter H/P
A: 220V, 50Hz, 3Phase
B: 208~230V, 60Hz, 3Phase
C: 575V, 50Hz, 3Phase
D: 440~460, 60Hz, 3Phase
E: 265V, 60Hz
F: 200V, 50/60Hz
Basic
Basic+4Way
Plasma Filter
Plasma Filter+4 Way
Tele+LCD
Tele+LCD+Nano plasma+4Way
Nano Plasma F+(A/changeove)+A/clean+Low A
Nano Plasma F+(A/changeove)+A/clean+4way+Low A
Tele+LED+4way
Internet
Plasma F+4Way+Oxy generator
Nano Plasma F+(A/changeove)+A/clean
Nano Plasma F+(A/changeove)+A/clean+4way
Nano Plasma F+(A/changeove)+A/clean+PTC
Nano Plasma F+(A/changeove)+Autoclean+4way+PTC
Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC
Negative ION+A/Clean
(Nano)Plasma+Negative ION+A/Clean
4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean
Nano Plasma F+4Way+(A/changeove)+A/clean+
LG Model Development Serial No.
* ARTCOOL COLOR
R
Mirror
W
White
B
Blue
D
Wood
M
Metal
C
Cherry
-3-
A
B
C
D
E
F
G
H
I
J
K
L
M
N
P
Q
R
S
T
U
Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor. (THERMISTOR)
Room temperature control
• Maintains the room temperature in accordance with the Setting Temp.
Starting Current Control
• Indoor fan is delayed for 5 sec at the starting.
Time Delay Safety Control
• Restarting is inhibited for approx. 3 minutes.
Indoor Fan Speed Control
• High, Med, Low, CHAOS, JET COOL
Soft Dry Operation Mode
PLASMA
• Intermittent operation of fan at low speed.
Sleep Mode Auto Control
• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Natural Air Control by CHAOS Logic
• The function will be operated while in any
operation mode with selecting the function.
• The function is to be stopped while it is
operating with selecting the function.
Defrost(Deice) control (Heating)
• The fan is switched to intermittent or irregular operation
• The fan speed is automatically switched from high to low speed.
Airflow Direction Control
• Both the indoor and outdoor fan stops during defrosting.
Hot-start Control (Heating)
• The louver can be set at the desired position or swing
up and down automatically.
-4-
• The indoor fan stops until the
evaporator pipe temperature will be reached
at 28°C.
Signal Receptor
Each Icon turns on when the unit is operated, then the only Icon outline to be operated is bright.
Cooling Mode
Lights up during Cooling operation. (Outline)
Auto Operation Mode
Lights up during Auto operation. (Outline)
Healthy Dehumidification
Lights up during Healthy Dehumidification operation. (Outline)
Mode
Heating Mode
Lights up during Heating operation.
(Heat Pump model only) (Outline)
Defrost Mode
Lights up during Defrost control or
Hot Start in Heating operation. (Outline)
Air circulation Mode
Lights up during Air Circulation operation. (Outline)
Sleep Mode
Lights up during Sleep Mode operation.
Timer Mode
Lights up during Timer operation.
Auto Cleaning Mode
Lights up during Auto Cleaning reservation.
Jet Cool Mode
Lights up during Jet Cool Operation.
Plasma
Lights up during Plasma operation.
Fan Speed (Low)
Lights up when Fan speed is low.
Fan Speed (Medium)
Lights up when Fan speed is Medium.
Fan Speed (High)
Lights up when Fan speed is High.
Fan Speed (Chaos)
Lights up when Fan speed is Chaos.
Desire temperature For cooling,dehumidification,heating modes it display Desired temperature
indicator
• Cooling
: 18~30°C
• AI : Auto Operation
• Dehumidification : 18~30°C
• Po : Jet Cool
• Heating
: 16~30°C
• Lo : Test Mode
• C1 : Indoor pipe sensor error
Desire temperature Icon
Indoor temperature Icon
-5-
Remote Control
Operation ON/OFF
Operation Mode Selection
Cooling Operation Mode.(
(Cooling
(Heating
model only) model only)
)
Healthy Dehumidification Operation Mode.(
Auto Operation Mode.(
) Heating Operation Mode.(
)
)
Fan Speed Selection
(Low)
(Med)
(High)
Room, Temperature Checking
: (High:39°C
Low:11°C)
Temperature Setting
TEMPERATURE
LOW
HIGH
Cooling
Down to 18°C
Up to 30°C
Heating
Down to 16°C
Up to 30°C
JET COOL
PLASMA(Optional)
Setting the Time or Timer
Timer Selection
ON
OFF
: OFF, ON, OFF
ON
Timer Setting
SET
Timer Cancel
CANCEL
: Cancel Sleep Mode, Timer ON or Timer OFF
Sleep Operation
: 1, 2, 3, 4, 5, 6, 7, Off Timer
2nd F
Airflow Direction Control
Reset
Air Circulation
AUTO CLEAN
: Fan Operates without cooling or heating.
AUTO CLEAN
Horizontal Airflow Direction Control Button(Optional)
LED LUMINOSITY
-6-
Product References
Model Name
Item
LS-135GB/GM/GR
LS-1351GB/GM/GR
Unit
Cooling Capacity
14,000
Btu/h
-
Heating Capacity
Moisture Removal
Power Source
1.5
Ø, V, Hz
1Ø, 220-240V, 50Hz
9.5
Indoor
Air Circulation
Outdoor
m3/min
26
36
Indoor
Noise Level
Outdoor
Input
l/h
Cooling
Heating
Running
Cooling
Current
Heating
E.E.R.
Cooling
C.O.P
Heating
dB (A)±3
48
1,140
W
5.3
A
12.28
Btu/hW
-
Indoor
Motor Output
Dimensions
(W x H x D)
Outdoor
10.8
W
30
Indoor
Outdoor
1,030 x 290 x 153
mm
770 x 540 x 245
Indoor
Net. Weight
Outdoor
Refrigerant
9.5
kg
34
R-410A, 730
g
O
Airflow Direction Control (Up & Down)
L.C.D Wireless
Remocon Type
Liquid
Service Valve
Gas
1/4" (6.35)
inch(mm)
1/2"(12.7)
Sleeping Operation
O
Drain Hose
O
Connecting Cable
1.0mm2
Power Cord
1.0mm2
NOTE: Please refer to Label Quality on the product since this specification may be changed for improving
performance
-7-
Dimensions
(1) Indoor Unit
H
D
W
Installation plate
MODEL
DIM
14K Btu Series
Unit
W
mm
1030
H
mm
290
D
mm
153
-8-
(2) Outdoor Unit
L2
D
L1
W
H
L3
L5
Gas side
(3-way valve)
L4
Liquid side
(2-way valve)
DIM
MODEL
unit
14K Btu Series
W
mm
770
H
mm
540
D
mm
245
L1
mm
287
L2
mm
64
L3
mm
518
L4
mm
10
L5
mm
100
-9-
Refrigeration Cycle Diagram
(1) Cooling Only Models
INDOOR UNIT
OUTDOOR UNIT
LIQUID SIDE
CAPILLARY TUBE
HEAT
EXCHANGE
(CONDENSER)
HEAT
EXCHANGE
(EVAPORATOR)
GAS SIDE
COMPRESSOR
(2) Cooling & Heating Models
INDOOR UNIT
OUTDOOR UNIT
CHECK VALVE
(Heating Model only)
LIQUID SIDE
VALVE
CAPILLARY TUBE
HEAT
EXCHANGE
(EVAPORATOR)
HEAT
EXCHANGE
(CONDENSER)
GAS SIDE
VALVE
REVERSING
VALVE
(Heating Model Only)
ACCUMU
LATOR
COMPRESSOR
-10-
COOLING
HEATING
Wiring Diagram
(1) Indoor Unit
CN-MOTOR
OR
BR
MOTOR
MAIN PCB
ASM
TRIAC
CN-U/D CN-VFD CN-TH1
GN/YL
POWER
CN-GND
LS-135GB/GM/GR/LS-1351GB/GM/GR
BK
SH-CAPA.
BL
BL
DISPLAY
STEP
MOTOR
CN-L/R
CN-TAB2 CN-TAB1
YL
BR
ZNR
THERMISTOR
STEP
MOTOR
OPTION
4
3
FUSE
AC250V/T2A
CN-HVB
BR
RY-COMP.
RD
RD
BK
BK
H.V.B
A/CL
GN/YL
GN/YL
BL
BR
CN-MAIN
FORCED
OPERATON
S/W
TO OUTDOOR UNIT
CONNECTOR
PWB ASM
CN-STEP1
CN-STEP2
SUC
STEP
MOTOR-1
SUC
STEP
MOTOR-2
INDOOR WIRING DIAGRAM
CN-SW/2 CN-SW/3
TERMINAL
BLOCK
1(L) 2(N)
CN-SW/1
BL
BR
OPTION
LIMIT S/W-1
LIMIT S/W-2
3854A20238Y
(2) Outdoor Unit
FAN
MOTOR
COMP
RD
BL
YL
RD
BL
YL
BL
BL
BL
PTC
RD
BR
OLP
BR
C S R
CAPACITOR
H
C
F
GN/YL
BL
BR
1
PILLAR
TERMINAL
GN/YL
BL
BR
1(L) 2(N)
BLACK
TO INDOOR UNIT
OUTDOOR WIRING DIAGRAM
3854A30077E
-11-
LS-1352GB/GC/GD/GM/GR/GW
LS-1202GB/GC/GD/GM/GR/GW
LS-1262GB/GC/GD/GR/GW
C142CM/CR
Operation Details
1. MAIN UNIT FUNCTION
• DISPLAY
1) C/O Model
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Sleep Timer Indicator
• ON while in sleep timer mode, OFF when sleep timer cancel or appliance operation pause.
Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Comp. Running Incidator
• While in appliance operation, ON while in outdoor unit compressor running, OFF while in compressor off.
2) H/P Model
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Sleep Timer Indicator
• ON while in sleep timer mode, OFF when sleep timer cancel or appliance operation pause.
Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Defrost Indicator
• OFF except when hot start during heating mode operation or while in defrost control.
■ Cooling Mode Operation
• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan
stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp
➲ Setting Temp+0.5°C
Compressor OFF Temp
➲ Setting Temp-0.5°C
• While in compressor running, operating with the airflow speed set by the remote control. While in compressor
not running, operating with the low airflow speed regardless of the setting.
■ Healthy Dehumidification Mode
• When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C ≤ Intake Air Temp
➲ 25°C
24°C ≤ Intake Intake Air Temp<26°C
➲ Intake Air Temp-1°C
18°C ≤ Intake Intake Air Temp<24°C
➲ Intake Air Temp-0.5°C
Intake Air Temp<18°C
➲ 18°C
-12-
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification operation and 4-min compressor off repeat.
Compressor ON Temp.
➲ Setting Temp+0.5°C
Compressor OFF Temp. ➲ Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
■ Heating Mode Operation
• When the intake air temp reaches +3°…above the setting temp, the compressor is turned off. When below
the setting temp, the compressor is turned on.
Compressor ON Temp.
➲ Setting Temp.
Compressor OFF Temp. ➲ Setting Temp.+3°C
• While in compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 28°C , it
operates with the low or setting airflow speed. When the indoor pipe temp is between 20°C and 28°C, it operates with Super-Low(while in sleep mode, with the medium airflow speed).
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it
operates with the low airflow speed.
• If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the
outdoor fan is turned on/off according to the indoor pipe temp.
• While in defrost control, both of the indoor and outdoor fans are turned off.
■ Defrost Control
• While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing,
reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit.
• After 40 min heating mode operation, at 4 min interval, whether to carry out defrost control or not and the time
of defrost control are determined according to the following conditions.
1) While in heating mode operation, the maximum of the indoor pipe temperature is measured and it is compared with the present indoor pipe temperature to get the difference of the indoor pipe temperatures (=the
maximum temperature of indoor pipe ? the present temperature of indoor pipe), according to which, whether
to carry out defrost control or not is determined.
2) According to the need of defrost control shown above and the elapsed time of heating mode operation at that
moment, the defrost control time is determined.
3) When the determined time of defrost control is below 7 min, heating mode operation continues without carrying out defrost control. According to the procedure stated above, the determination is made again. When the
defrost control time is 7 min or longer, defrost control is then carried out.
• While in defrost control, the minimum temp of the indoor pipe is measured and it is compared with the present
temp of the indoor pipe to get the difference of the indoor pipe temperatures (=the present temperature of the
indoor pipe ? the minimum temperature of the indoor pipe). When the difference is 5°C or higher, defrost control is completed and heating mode operation is carried out.
• While in defrost control, if the defrost time determined before the start of defrost control is completed, defrost
control stops and heating mode operation is carried out regardless of the above condition.
• When the indoor pipe temp is 42°C or above, defrost control is not carried out even if the condition is one of
the defrost conditions above.
• While in defrost control, the compressor is on and the indoor fan, the outdoor fan, and the 4 way valve are off.
-13-
■ Fuzzy Operation (C/O Model)
• According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting
temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp
➲ Setting Temp + 0.5°C
Compressor OFF Temp
➲ Setting Temp + 0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp
➲ 25°C
24°C ≤ Intake Air Temp < 26°C
➲ Intake Air Temp + 1°C
22°C ≤ Intake Air Temp < 24°C
➲ Intake Air Temp + 0.5°C
18°C ≤ Intake Air Temp < 22°C
➲ Intake Air Temp
Intake Air Temp<18°C
➲ 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the
temperature.
■ Fuzzy Operation (H/P Model)
• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C ≤ Inatake Air Temp
➲ Fuzzy Operation for Cooling
21°C ≤ Inatake Air Temp<24°C
➲ Fuzzy Operation for Dehumidification
Inatake Air Temp<21°C
➲ Fuzzy Operation for Heating
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor
is turned on.
Compressor ON Temp
➲ Setting Temp +0.5°C
Compressor OFF Temp
➲ Setting Temp + 0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C≤ Intake Air Temp
➲ 25°C
24°C≤ Intake Air Temp<26°C
➲ Intake Air Temp + 1°C
22°C≤ Intake Air Temp<24°C
➲ Intake Air Temp + 0.5°C
18°C≤ Intake Air Temp<22°C
➲ Intake Air Temp
Intake Air Temp<18°C
➲ 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
-14-
2) Fuzzy Operation for Dehumidification
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor
is turned on.
Compressor ON Temp
➲ Setting Temp + 0.5°C
Compressor OFF Temp
➲ Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C ≤ Intake Air Temp
➲ 25°C
24°C ≤ Intake Air Temp<26°C
➲ Intake Air Temp+1°C
22°C ≤ Intake Air Temp<24°C
➲ Intake Air Temp+0.5°C
18°C ≤ Intake Air Temp<22°C
➲ Intake Air Temp
Intake Air Temp<18°C
➲ 18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.
3) Fuzzy Operation for Heating
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above
the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp
➲ Setting Temp
Compressor OFF Temp
➲ Setting Temp + 3°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
20°C≤Intake Air Temp
➲ Intake Air Temp + 0.5°C
Intake Air Temp<20°C
➲ 20°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the
intake air temperature and the setting temperature.
■ Airflow Speed Selection
• The airflow speed of the indoor fan is set to high, medium, low, or chaos (auto) by the input of the airflow
speed selection key on the remote control.
■ On-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.
-15-
■ Off-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.
■ Off-Timer ↔ On-Timer Operation
• When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is
carried out according to the set time.
■ Sleep Timer Operation
• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appliance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C. After another 30 min elapse, it increases by 1°C again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to the
low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to
the medium.
■ Chaos Swing Mode
• By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are
fixed to the desired direction.
• While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.
< Cooling Mode >
< Heating Mode >
CLOSED
CLOSED
7°
7°
OPEN
OPEN
■ Chaos Natural Wind Mode
• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the airflow mode is operated for 2~15 sec. randomly by the Chaos Simulation.
-16-
■ Jet Cool Mode Operation (C/O Model)
• If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
■ Jet Cool Mode Operation (H/P Model)
• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other
mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
■ Forced Operation
• Operation procedures when the remote control can't be used.
• The operation will be started if the power button is pressed.
• If you want to stop operation, re-press the button.
Cooling Model
Operating mode
Indoor FAN Speed
Setting Temperature
Cooling
High
22°C
Heat pump Model
Room Temp. ≥ 24°C 21°C ≤ Room Temp. < 24°C Room Temp. < 21°C
Cooling
High
22°C
Healthy Dehumidification
High
23°C
Heating
High
24°C
• While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to
indicate the forced operation.
■ Test operation
• During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room temperature and resets in 18±1 minutes.
• During test operation, if remote controller signal is received, the unit operates as remote controller sets.
If you want to use this operation, open the front panel upward and Press the power button let it be pressed for
about 3 seconds.
• If you want to stop the operation, re-press the button.
■ Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
■ Air Cleaner Operation
• When an air cleaner function is selected during Air Conditioner operation
- Plasma air cleaner function will be operated while in any operation mode with selecting the function.
- The function is to be stopped while it is operating with selecting the function.
• When an air cleaner function is selected during operation off
- The function will be only operated.
• When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be
stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B)
will be operated again.
-17-
■ Remote Control Operation Mode
• When the remote control is selected by the slide switch on the main unit, the appliance operates according to
the input by the remote control.
■ Protection of the evaporator pipe from frosting
• If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cooling cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor
evaporator pipe from frosting.
• When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the
outdoor fan is turned on according to the condition of the room temperature.
■ Auto Clean
• Open the door on the remote control. Press the Auto Clean Button.
Close the door on the remote control. Now each time that you press the start/stop button, the Air conditioner
operates clean function automatically.
■ Display Luminosity
• The Display Luminosity can be adjusted by using the remote control.
Press the start/stop button to start the unit. Open the door on the remote control, press the 2ndF button and,
press display luminosity button. Display will be dark. Press the button again to set bright display.
■ Buzzer Sounding Operation
• When the appliance-operation key is input by the remote control, the short "beep" sounds.
• When the appliance-pause key is input by the remote control, the long "beep—" sounds.
• When an except operation and pause key is input by the remote control, the short "beep" sounds.
-18-
Display Function
Signal Receptor
Each Icon turns on when the unit is operated, then the only Icon outline to be operated is bright.
Cooling Mode
Lights up during Cooling operation. (Outline)
Auto Operation Mode
Lights up during Auto operation. (Outline)
Healthy Dehumidification
Lights up during Healthy Dehumidification operation. (Outline)
Mode
Heating Mode
Lights up during Heating operation.
(Heat Pump model only) (Outline)
Defrost Mode
Lights up during Defrost control or
Hot Start in Heating operation. (Outline)
Air circulation Mode
Lights up during Air Circulation operation. (Outline)
Sleep Mode
Lights up during Sleep Mode operation.
Timer Mode
Lights up during Timer operation.
Auto Cleaning Mode
Lights up during Auto Cleaning reservation.
Jet Cool Mode
Lights up during Jet Cool Operation.
Plasma
Lights up during Plasma operation.
Fan Speed (Low)
Lights up when Fan speed is low.
Fan Speed (Medium)
Lights up when Fan speed is Medium.
Fan Speed (High)
Lights up when Fan speed is High.
Fan Speed (Chaos)
Lights up when Fan speed is Chaos.
Desire temperature For cooling,dehumidification,heating modes it display Desired temperature
indicator
• Cooling
: 18~30°C
• AI : Auto Operation
• Dehumidification : 18~30°C
• Po : Jet Cool
• Heating
: 16~30°C
• Lo : Test Mode
• C1 : Indoor pipe sensor error
Desire temperature Icon
Indoor temperature Icon
-19-
Installation
1. Installation of indoor, Outdoor unit
1) Selection of the best location
• Select a place so that the warm air and noise from the
air conditioner do not disturb neighbors.
1. Indoor unit
• Do not have any heat or steam near the unit.
• Select a place where there are no obstacles in front of
the unit.
• Make sure that condensation drainage can be conveniently routed away.
Do not install near a doorway.
• Ensure that the space around the left and right of the
unit is more than "A". The unit should be installed as
high on the wall as possible, allowing a minimum of
"B" from ceiling.
• Use a stud finder to locate studs to prevent unnecessary damage to the wall.
More than "B"
More than 60cm
More than 10cm
More than 10cm
More
than 60cm
More than 70cm
2) Piping length and elevation
7k~14k
More than "A"
Max. Additional
Standard Max.
Length Elevation Length Refrigerant
A (m)
(g/m)
(m)
B (m)
Pipe Size
Capacity
(Btu/h)
GAS
LIQUID
3/8"(Ø9.52) 1/4"(Ø6.35)
4 or 7.5
7
15
20
1/2"(Ø12.7) 1/4"(Ø6.35)
4 or 7.5
7
15
20
Indoor unit
Outdoor unit
More than "B"
More than 2.3m
A
A
Indoor unit
B
B
Outdoor unit
CAUTION
Install the indoor unit on the wall where the height
from the floors more than 2.3 meters.
Grade
7K~14K
Outdoor unit
Clearance(cm)
A
B
10
5
Oil trap
A
Indoor unit
B
2. Outdoor unit
• If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation
from the condenser is not restricted.
• Ensure that the space around the back and sides is
more than 10cm. The front of the unit should have
more than 70cm of space.
• Do not place animals and plants in the path of the
warm air.
• Take the air conditioner weight into account and select
a place where noise and vibration are minimum.
If case more than 5m
CAUTION
• Capacity is based on standard length and maximum
allowance length is on the basis of reliability.
• Oil trap should be installed every 5~7 meters.
-20-
I
3) How to fix installation plate
4) Drill a hole in the wall
The wall you select should be strong and solid enough
to prevent vibration
• Drill the piping hole with a ø70mm hole core drill. Drill
the piping hole at either the right or the left with the
hole slightly slanted to the outdoor side.
1. Mount the installation plate on the wall with four
type A screws. If mounting the unit on a concrete
wall, use anchor bolts.
• Mount the installation plate horizontally by aligning
the centerline using a level.
WALL
Outdoor
5-7mm
Installation Plate
Type "A" screw
2. Measure the wall and mark the centerline. It is
also important to use caution concerning the
location of the installation plate-routing of the
wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping
connections must be done safely.
(SU)
C
B
D
Installation plate
A
Ø70mm
Left rear piping
Ø70mm
Right rear piping
(SZ)
B
D
Installation plate
C
A
Left rear piping
CHASSIS
(Grade)
Right rear piping
Distance (mm)
A
B
C
D
SU
(11k~14k)
92
44
67
44
SZ
(7k~9k)
35
33
156
33
-21-
(3/16"~5/16")
Indoor
2. Flaring Work and Connection of Piping
1) Flaring work
• Carry out flaring work using flaring tool as shown
below.
Main cause for refrigerant leakage is due to defect in the flaring
work. Carry out correct flaring work using the following procedure.
Outside diameter
mm
inch
Ø6.35
1/4
Ø9.52
3/8
Ø12.7
1/2
Ø15.88
5/8
Ø19.05
3/4
1. Cut the pipes and the cable.
• Use the piping kit accessory or pipes purchased locally.
• Measure the distance between the indoor and the
outdoor unit.
• Cut the pipes a little longer than the measured distance.
• Cut the cable 1.5m longer than the pipe length.
Copper
pipe
5. Check
• Compare the flared work with figure below.
• If flare is noted to be defective, cut off the flared section and re-flare it.
Slanted Uneven Rough
90°
A
mm
0~0.5
0~0.5
0~0.5
0~1.0
1.0~1.3
Smooth all round
Inside is shiny without scratches
2. Burr removal
• Completely remove all burrs from the cut cross section of pipe/tube.
• Put the end of the copper tube/pipe in a downward
direction as you remove burrs in order to avoid dropping burrs into the tubing.
= Improper flaring =
Even length
all round
Inclined Surface Cracked Uneven
damaged
thickness
Pipe
Reamer
2) Connection of piping Indoor
• Preparing the indoor unit's piping and drain hose for
installation through the wall.
• Remove the plastic tubing retainer(see illustration
below) and pull the tubing and drain hose away from
chassis.
• Replace the plastic tubing holder in the original position.
(Optional)
Point down
3. Putting nut on
• Remove flare nuts attached to indoor and outdoor unit, then
put them on pipe/tube having completed burr removal.
(not possible to put them on after flaring work)
Flare nut
Copper tube
4. Flaring work
• Firmly hold copper pipe in a die in the dimension
shown in the table above.
"A"
Bar
Handle
Bar
Yoke
Cone
Copper pipe
Clamp handle
Red arrow mark
-22-
For right rear piping
4. Connecting the pipings to the indoor unit and drain
hose to drain pipe.
• Align the center of the pipes and sufficiently tighten
the flare nut by hand.
1. Route the indoor tubing and the drain hose in the
direction of rear right.
Drain hose
Indoor unit tubing
Flare nut
Pipes
• Tighten the flare nut with a wrench.
Open-end wrench (fixed)
2. Insert the connecting cable into the indoor unit
from the outdoor unit through the piping hole.
• Do not connect the cable to the indoor unit.
• Make a small loop with the cable for easy
connection later.
3. Tape the tubing, drain hose, and the connecting
cable. Be sure that the drain hose is located at the
lowest side of the bundle. Locating at the upper
side can cause drain pan to overflow inside the
unit.
Flare nut
Connection pipe
Wrench
Indoor unit tubing
Outside diameter
mm
inch
Ø6.35
1/4
Ø9.52
3/8
Ø12.7
1/2
Torque
kg.m
1.8
4.2
5.5
• When extending the drain hose at the indoor unit,
install the drain pipe.
Drain pipe
Tape
Connecting
pipe
Indoor unit drain hose
Drain hose
Adhesive
Connecting cable
Vinyl tape(narrow)
5. Wrap the insulation material around the connecting
portion.
• Overlap the connection pipe insulation material and
the indoor unit pipe insulation material. Bind them
together with vinyl tape so that there is no gap.
NOTE: If the drain hose is routed inside the room,
insulate the hose with an insulation material* so that
dripping from "sweating"(condensation) will not damage
furniture or floors.
*Foamed polyethylene or equivalent is recommended.
Plastic bands Insulation material
4. Indoor unit installation
• Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the rear
top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.
• Wrap the area which accommodates the rear piping
housing section with vinyl tape.
Indoor
unit pipe
Connection
pipe
Connecting
cable
Vinyl tape
Wrap with vinyl tape
(wide)
Connecting cable
Drain hose
Pipe
Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots(clicking sound).
Vinyl tape(narrow)
-23-
6. Connecting the pipings to the indoor unit and the
drain hose to drain pipe.
• Align the center of the pipes and sufficiently tighten
the flare nut by hand.
• Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where
they fit into the rear piping housing section.
Wrap with vinyl tape
Pipe
Indoor unit tubing
Flare nut
Pipes
Vinyl tape(wide)
Drain hose
• Tighten the flare nut with a wrench.
For left rear piping
Open-end wrench (fixed)
1. Route the indoor tubing and the drain hose to the
required piping hole
position.
Flare nut
Connection pipe
Wrench
Indoor unit tubing
Outside diameter
mm
inch
Ø6.35
1/4
Ø9.52
3/8
Ø12.7
1/2
2. Insert the piping, drain hose, and the connecting
cable into the piping hole.
Torque
kg.m
1.8
4.2
5.5
• When extending the drain hose at the indoor unit,
install the drain pipe.
Connecting cable
Drain pipe
Drain hose
3. Insert the connecting cable into the indoor unit.
• Don't connect the cable to the indoor unit.
• Make a small loop with the cable for easy connection later.
Indoor unit drain hose
4. Tape the drain hose and the connecting cable.
• Connecting cable
Adhesive
Vinyl tape (narrow)
7. Wrap the insulation material around the connecting portion.
• Overlap the connection pipe heat insulation and the
indoor unit pipe heat insulation material. Bind them
together with vinyl tape so that there is no gap.
5. Indoor unit installation
• Hang the indoor unit from the hooks at the top of the
installation plate.
• Insert the spacer etc. between the indoor unit and the
installation plate and separate the bottom of the
indoor unit from the wall.
Plastic bands Insulation material
Indoor unit
Spacer
Installation plate
8cm
-24-
10. Indoor unit installation
• Remove the spacer.
• Ensure that the hooks are properly seated on the
installation plate by moving it left and right.
• Wrap the area which accommodates the rear piping
housing section with vinyl tape.
Indoor
unit piping
Connection
pipe
Vinyl tape
(wide)
Wrap with vinyl tape
Connecting
cable
Pipe
Vinyl tape(narrow)
Connecting cable
Drain hose
Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots(clicking sound).
• Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which
they fit into the rear piping housing section.
CAUTION
Installation Information (For left piping)
• Good case
For left piping. Follow the instruction below.
• Press on the upper side of clamp. ( )
Pipe
Drain hose
Vinyl tape(narrow)
Wrap with
vinyl tape(wide)
8. Reroute the pipings and the drain hose across the
back of the chassis.
• Bend the tubing to the left side of chassis.
Piping for
passage through
piping hole
9. Set the pipings and the drain hose to the back of
the chassis with the tubing holder.
• Hook the edge of tubing holder to tap on chassis and
push the bottom of tubing holder to be engaged at the
bottom of chassis.
• Bend the tubing to the left side of chassis.
Tubing holder
-25-
3) Connection of the pipes-Outdoor
CAUTION
• Bad case
■ Following bending type from right to left could cause problem
of pipe damage.
1. Align the center of the pipings and sufficiently
tighten the flare nut by hand.
2. Finally, tighten the flare nut with torque wrench
until the wrench clicks.
• When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow on
the wrench.
Outside diameter
mm
inch
Ø6.35
1/4
Ø9.52
3/8
Ø12.7
1/2
Ø15.88
5/8
Ø19.05
3/4
Torque
kg.m
1.8
4.2
5.5
6.6
6.6
Outdoor unit
Gas side piping
(Bigger diameter)
Liquid side
piping
(Smaller
diameter)
Torque wrench
-26-
3. Connecting The Cable Between Indoor Unit and Outdoor Unit
1) Connect the cable to the Indoor unit.
• Connect the cable to the indoor unit by connecting the wires to the terminals on the control board in
dividually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and
the terminal No. are the same as those of the indoor unit.)
The earth wire should be longer than the common wires.
CAUTION
• When installing, refer to the circuit diagram on the
Control Box of Indoor Unit.
• When installing, refer to the wiring diagram on the
Control Cover Inside Outdoor Unit.
The power cord connected to the "A" unit should be
complied with the following specifications
(Type "B" approved by HAR or SAA).
CAUTION
(mm2)
• The above circuit diagram is subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that not to be pulled out
easily.
• Connect the wires according to color codes by referring the wiring diagram.
Grade
NORMAL CROSS
-SECTIONAL AREA
5k~9k
12k~14K
0.75
1.0
Unit(A)
Indoor
Indoor
Cable Type(B)
H05VV-F
H05VV-F
The power connecting cable connected to the indoor
and outdoor unit should be complied with the following
specifications
(Type "B" approved by HAR or SAA).
CAUTION
If a power plug is not to be used, provide a circuit breaker
between power source and the unit as shown below.
Main power source
(mm2)
Grade
Air
Conditioner
NORMAL CROSS
-SECTIONAL AREA
Circuit Breaker
Use a circuit
breaker or time
delay fuse.
7k~14k
1.0
Cable Type(B)
-27-
H07RN-F
NORMAL
CROSS-SECTIONAL
AREA 0.75mm2
2) Connect the cable to the outdoor unit
Outdoor Unit
1. Remove the control cover from the unit by loosening the screw.
Connect the wires to the terminals on the control
board individually.
Terminal block
Over 5mm
2. Secure the cable onto the control board with the
cord clamp.
Connecting cable
Connecting cable
3. Refix the control cover to the original position
with the screw.
Cover control
4. Use a recognized circuit breaker "A"
between the power source and the unit.
A disconnecting device to adequately disconnect
all supply lines must be fitted.
Circuit
Breaker
(A)
Grade
7k~14k
18k
15
20
24k~28k 30k, 32k 36k, 38k
30
30
40
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of
wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make
sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on
the name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness. (Refer to page 27))
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal
function of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an
air gap contact separation of at least 3mm in each active(phase) conductors.
-28-
4. Checking the Drainage and Forming the Pipings
1) Checking the drainage
2) Form the piping
1. To remove the front panel from the indoor unit.
• Set the air direction louvers up-and-down to the position(horizontally) by hand.
• Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille
toward you and lift it off.
1. Form the piping by wrapping the connecting portion of the indoor unit with insulation material and
secure it with two kinds of vinyl tapes.
• If you want to connect an additional drain hose, the
end of the drain outlet should be routed above the
ground. Secure the drain hose appropriately.
2. In cases where the outdoor unit is installed below
the indoor unit perform the following.
• Tape the piping, drain hose and connecting cable from
down to up.
• Secure the tapped piping along the exterior wall using
saddle or equivalent.
Air
filter
Inlet Grille
Seal small openings
around pipings with a
gum type sealer.
2. To check the drainage.
• Pour a glass of water on the evaporator.
• Ensure the water flows through the drain hose of the
indoor unit without any leakage and goes out the drain
exit.
Taping
Drain
hose
Connecting area
drain hose
Pipings
Connecting
cable
Leakage
checking
Drain pan
Trap is required to prevent water
from entering into electrical parts.
Drain
hose
3. In cases where the Outdoor unit is installed above
the Indoor unit perform the following.
• Tape the piping and connecting cable from down to up.
• Secure the taped piping along the exterior wall. Form
a trap to prevent water entering the room.
• Fix the piping onto the wall by saddle or equivalent.
Leakage
checking
3. Drain piping
• The drain hose should point downward for easy drain
flow.
Seal a small opening
around the pipings
with gum type sealer.
Downward slope
Trap
• Do not make drain piping.
Accumulated
drain water
Air
Do not raise
Water
leakage
Water
leakage
Waving
Tip of drain hose
dipped in water
Water
leakage
Less than
50mm gap
Trap
Ditch
-29-
5. Air Purging
1) Air purging
• Do a leak test of all joints of the tubing(both indoor
and outdoor) and both gas and liquid side service
valves.
Bubbles indicate a leak. Be sure to wipe off the soap
with a clean cloth.
• After the system is found to be free of leaks, relieve
the nitrogen pressure by loosening the charge hose
connector at the nitrogen cylinder. When the system
pressure is reduced to normal, disconnect the hose
from the cylinder.
Air and moisture remaining in the refrigerant system
have undesirable effects as indicated below.
• Pressure in the system rises.
• Operating current rises.
• Cooling(or heating) efficiency drops.
• Moisture in the refrigerant circuit may freeze and block
capillary tubing.
• Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor unit and tubing between the
indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture
from the system.
Indoor unit
2) Air purging with vacuum pump
1. Preparation
• Check that each tube(both liquid and gas side tubes)
between the indoor and outdoor units have been properly connected and all wiring for the test run has been
completed. Remove the service valve caps from both
the gas and the liquid side on the outdoor unit. Note
that both the liquid and the gas side service valves on
the outdoor unit are kept closed at this stage.
Outdoor unit
2. Leak test
• Connect the manifold valve(with pressure gauges)
and dry nitrogen gas cylinder to this service port with
charge hoses.
Manifold valve
Pressure
gauge
CAUTION
Lo
Hi
Be sure to use a manifold valve for air purging. If it is
not available, use a stop valve for this purpose. The
"Hi" knob of the manifold valve must always be kept
close.
Charge hose
• Pressurize the system to no more than 150 P.S.I.G.
with dry nitrogen gas and close the cylinder valve
when the gauge reading reached 150 P.S.I.G. Next,
test for leaks with liquid soap.
Nitrogen gas
cylinder(in vertical
standing position)
CAUTION
To avoid nitrogen entering the refrigerant system in a
liquid state, the top of the cylinder must be higher than
its bottom when you pressurize the system. Usually,
the cylinder is used in a vertical standing position.
-30-
Soap water method
Gas side
(1) Remove the caps from the 2-way and 3-way
valves.
(2) Remove the service-port cap from the 3-way valve.
(3) To open the 2-way valve turn the valve stem counterclockwise approximately 90°, wait for about 2~3
sec, and close it.
(4) Apply a soap water or a liquid neutral detergent on
the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the
connecting points of the piping.
(5) If bubbles come out, the pipes have leakage.
Liquid side
3-way valve
(Close)
2-way valve
(Open)
Cap
3. Evacuation
• Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing
and indoor unit.
Confirm the "Lo" knob of the manifold valve is open.
Then, run the vacuum pump.
The operation time for evacuation varies with tubing
length and capacity of the pump. The following table
shows the time required for evacuation.
Hexagonal wrench
Indoor unit
Required time for evacuation when 30 gal/h vacuum
pump is used
If tubing length is less than
if tubing length is longer
10m (33 ft)
than 10m (33 ft)
10 min. or more
Outdoor unit
15 min. or more
• When the desired vacuum is reached, close the "Lo"
knob of the manifold valve and stop the vacuum pump.
4. Finishing the job
• With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the
valve.
• Turn the valve stem of gas side valve counter-clockwise to fully open the valve.
• Loosen the charge hose connected to the gas side
service port slightly to release the pressure, then
remove the hose.
• Replace the flare nut and its bonnet on the gas side
service port and fasten the flare nut securely with an
adjustable wrench. This process is very important to
prevent leakage from the system.
• Replace the valve caps at both gas and liquid side
service valves and fasten them tight.
This completes air purging with a vacuum pump.
The air conditioner is now ready to test run.
Manifold valve
Pressure
gauge
Lo
Hi
Open
Vacuum pump
-31-
Close
6. Test Running
1. Check that all tubing and wiring have been properly
connected.
2. Check that the gas and liquid side service valves are
fully open.
Intake temperature
Discharge air
1. Prepare remote control
1. Remove the battery cover
by pulling it according to the
arrow direction.
2. Insert new batteries making
sure that the (+) and (–) of
battery are installed correctly.
3. Reattach the cover by
pushing it back into position.
Discharge
temperature
4. For reference; the gas side pressure of optimum condition is as below.(Cooling)
R-22
Outside ambient
TEMP.
35°C (95°F)
The pressure of the gas side
service valve.
4~5kg/cm2G(56.8~71.0 P.S.I.G.)
R-410A
35°C (95°F)
8.5~9.5kg/cm2G(120~135 P.S.I.G.)
Refrigerant
NOTE:
• Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries.
• Remove the batteries from the remote control if the
system is not going to be used for a long time.
NOTE: If the actual pressure is higher than shown, the
system is most likely over-charged, and charge
should be removed. If the actual pressure are
lower than shown, the system is most likely
undercharged, and charge should be added.
The air conditioner is now ready for use.
2. Settlement of outdoor unit
• Anchor the outdoor unit with a bolt and nut(ø10mm)
tightly and horizontally on a concrete or rigid mount.
• When installing on the wall, roof or rooftop, anchor the
mounting base securely with a nail or wire assuming
the influence of wind and earthquake.
• In the case when the vibration of the unit is conveyed
to the hose, secure the unit with an anti-vibration
bushing.
PUMP DOWN
This is performed when the unit is to be relocated
or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the
outdoor unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the
unit cooling mode.
Bolt
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to
the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge
the air from the manifold hose using the refrigerant
gas.
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the
cooling operation.
5. When the low-pressure gauge reading becomes 1
to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the
gas side valve stem and then quickly turn off the
unit. At that time, Pump Down has been completed
and all refrigerant gas will have been collected in
the outdoor unit.
Tubing connection
3. Evaluation of the performance
Operate unit for 15~20 minutes, then check the system
refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge
of air.
3. Ensure the difference between the intake temperature and the discharge is more than 8°C(46°F) (Cooling) or (Heating).
-32-
Operation
Name and Function-Remote Control
The remote control transmits the signals to the system.
Signal transmitter
1
2
3
4
5
5
1
6
3
6
10
7
4
2
7
11
8
13
14
9
8
17
18
9
12
10
16
15
11
Flip-up door
(opened)
12
13
Operation Mode
14
Cooling Operation
Auto Operation
15
Healthy Dehumidification Operation
16
Heating Operation
• Cooling Model(
), Heat Pump Model(
)
17
18
-33-
START/STOP BUTTON
Operation starts when this button is pressed and
stops when the button is pressed again.
OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.
INDOOR FAN SPEED SELECTOR
Used to select fan speed in four steps
low, medium, high and CHAOS.
JET COOL
Used to start or stop the speed
cooling. (Speed cooling operates
super high fan speed in cooling mode.)
CHAOS SWING BUTTON
Used to stop or start louver movement and set the
desired up/down airflow direction.
ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping
operation.
TIME SETTING BUTTONS
Used to adjust the time.
TIMER SET/CANCEL BUTTON
Used to set the timer when the desired time is
obtained and to cancel the Timer operation.
SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or
heating.
ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
PLASMA(OPTIONAL)
Used to start or stop the plasma-purification function.
HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON (NOT ON ALL MODELS)
Used to set the desired horizontal airflow direction.
RESET BUTTON
Used prior to resetting time or after replacing batteries.
2nd F Button
Used prior to using modes printed in blue at the
bottom of buttons.
AUTO CLEAN
Used to set Auto Clean mode.
LED LUMINOSITY
Used to adjust LED luminosity.
Disassembly of the parts (Indoor unit)
Warning :
Disconnect the unit from power supply before making
any checks.
Be sure the power switch is set to “OFF”.
To remove the Grille from the Chassis.
• Hold up Inlet Grille Horizentally.
• To remove the Grille, pull the lower left and right
side of the grille toward you (slightly tilted) and lift it
straight upward.
• To seperate connecter assembly and than to remove
Inlet Grille assembly.
1. Before removing the control box, be sure to
take out the wire screwed at the other end.
-34-
2. To remove the Control Box.
• Remove securing screws.
• Pull the control box out from the chassis carefully.
3. To remove the Discharge Grille.
• Unhook the discharge grille and pull the discharge grille out from the chassis carefully.
4. To remove the Evaporator.
• Remove 3 screws securing the evaporator(at the
left 2EA in the Eva Holder, at the right 1EA).
-35-
• Unhook the tab on the right inside of the chassis
at the same time, slightly pull the evaporator
toward you until the tab is clear of the slot.
5. To remove the Motor Cover
• Remove 2 securing screw.
• Pull the motor cover out from the chassis
carefully.
Motor cover
6. To remove the Cross-Flow Fan
• Loosen the screw securing the cross-flow fan to
the fan motor (do not remove).
• Lift up the right side of the cross-flow fan and the
fan motor, separate the fan motor from the
cross-flow fan.
• Remove the left end of the cross-flow fan from
the self-aligning bearing.
-36-
2-way, 3-way Valve
2-way Valve (Liquid Side)
Hexagonal wrench (4mm)
Flare nut
3-way Valve (Gas Side)
Valve cap
Open position
Flare nut
Closed position
Open position
Closed position
To
piping
connection
To
piping
connection
To outdoor unit
Works
Shipping
1.
Air purging
(Installation)
Operation
Pin
Service Service
port cap port
To outdoor unit
Shaft position
Shaft position
Service port
Closed
(with valve cap)
Closed
(with valve cap)
Closed
(with cap)
Open
(counter-clockwise)
Closed
(clockwise)
Open
(push-pin or with
vacumm pump)
Open
(with valve cap)
Open
(with valve cap)
Closed
(with cap)
Closed
(clockwise)
Open
(counter-clockwise)
Open
(connected manifold
gauge)
2.
Pumping down
(Transfering)
Evacuation
(Servicing)
Open
Open
3.
Open
(with charging
cylinder)
Gas charging
(Servicing)
Open
Open
4.
Open
(with charging
cylinder)
5.
Pressure check
(Servicing)
Open
Open
Open
(with charging cylinder)
6.
Gas releasing
(Servicing)
Open
Open
Open
(with charging cylinder)
-37-
1. Air purging (Only R-22 Model)
Required tools : hexagonal wrench, adjustable
wrench, torque wrenches, wrench to
hold the joints, and gas leak
detector.
The air in the indoor unit and in the piping must be
purged. If air remains in the refrigeration pipes, it will
affect the compressor, reduce to cooling capacity, and
could lead to a malfunction.
The additional gas for air purging has been charged
in the outdoor unit.
However, if the flare connections have not be done
correctly and there gas leaks, a gas cylinder and the
charge set will be needed.
Indoor unit
Liquid side
Open
Outdoor unit
2-way
valve
Gas side
Clsed
3-way
valve
Service port nut:
Be sure, using a torque wrench to tighten the service port nut (after using the service port), so that it prevents the
gas leakage from the refrigeration cycle.
*
CAUTION : Do not leak the gas in the air during Air purging.
• Procedure
(6) Set the 3-way valve to the back seat.
(1) Recheck the piping connections.
(7) Mount the valve stem nuts to the 2-way and 3way valves.
(2) Open the valve stem of the 2-way valve
counterclockwise approximately 90°, wait 10
seconds, and then set it to closed position.
– Be sure to use a hexagonal wrench to operate
the valve stem.
(8) Check for gas leakage.
– At this time, especially check for gas leakage
from the 2-way and 3-way valve’s stem nuts,
and from the service port nut.
(3) Check for gas leakage.
– Check the flare connections for gas leakage.
Caution
(4) Purge the air from the system.
– Set the 2-way valve to the open position and
remove the cap from the 3-way valve’s service
port.
– Using the hexagonal wrench to press the valve
core pin, discharge for three seconds and then
wait for one minute. Repeat this three times.
If gas leakage are discovered in step (3) above,
take the following mesures :
If the gas leaks stop when the piping connections
are tightened further, continue working from step (4).
If the gas leaks do not stop when the connections
are retightened, repair the location of the leak,
discharge all of the gas through the service port,
and then recharge with the specified amount of
gas from a gas cylinder.
(5) Use torque wrench to tighten the service port
nut to a torque of 1.8kg.cm.
-38-
2. Pumping down
Liquid side
Indoor unit
2-Way
valve
Open
Outdoor unit
Gas side
Closed
3-Way
valve
Lo
CLOSE
CLOSE
Purge the air
• Procedure
(6) Operate the air conditioner at the cooling
cycle and stop it when the gauge indicates
1kg/cm2g.
(1) Confirm that both the 2-way and 3-way valves
are set to the open position.
– Remove the valve stem caps and confirm that
the valve stems are in the raised position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(7) Immediately set the 3-way valve to the closed
position.
– Do this quickly so that the gauge ends up
indicating 3 to 5kg/cm2g.
(2) Operate the unit for 10 to 15 minutes.
(8) Disconnect the charge set, and mount the 2way and 3-way valve’s stem nuts and the
service port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
(3) Stop operation and wait for 3 minutes, then
connect the charge set to the service port of
the 3-way valve.
– Connect the charge hose with the push pin to
the service port.
(4) Air purging of the charge hose.
– Open the low-pressure valve on the charge set
slightly to air purge from the charge hose.
– Refrigerant must be recovered.
Don’t vent the Refrigerant in the atmosphere.
CAUTION
Do not use the existing charge set for R-22.
It is necessary to use new charge set for R-410A.
The pressure of R-410A is 1.6 times higher than
that of R-22. Thus, the high pressure side gauge
of charge set should be used higher pressure
gauge of 50kg/cm2 range.
(5) Set the 2-way valve to the closed position.
-39-
3. Re-air purging
(Re-installation)
Liquid side
Indoor unit
2-Way
valve
Closed
Outdoor unit
Gas side
Closed
3-Way
valve
Gas cylinder
Lo
R22
OPEN
CLOSE
• Procedure
(6) Disconnect the charge set and the gas
cylinder, and set the 2-way and 3-way valves
to the open position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(1) Confirm that both the 2-way valve and the 3way valve are set to the closed position.
(2) Connect the charge set and a gas cylinder to
the service port of the 3-way valve.
– Leave the valve on the gas cylinder closed.
(7) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
(3) Air purging.
– Open the valves on the gas cylinder and the
charge set. Purge the air by loosening the flare
nut on the 2-way valve approximately 45° for 3
seconds then closing it for 1 minute; repeat 3
times.
– After purging the air, use a torque wrench to
tighten the flare nut on the 2-way valve.
*
(4) Check for gas leakage.
– Check the flare connections for gas leakage.
(5) Discharge the refrigerant.
– Close the valve on the gas cylinder and
discharge the refrigerant until the gauge
indicates 3 to 5 kg/cm2g.
-40-
CAUTION:
Do not leak the gas in the air during Air
Purging.
4. Balance refrigerant of the 2-way, 3-way valves
(Gas leakage)
Liquid side
Indoor unit
Outdoor unit
2-Way
valve
Open
3-Way
valve
Open
Gas side
Lo
OPEN
CLOSE
• Procedure
(3) Open the valve (Lo side) on the charge set
and discharge the refrigerant until the gauge
indicates 0 kg/cm2G.
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not
running is higher than 1 kg/cm2G), discharge
the refrigerant until the gauge indicates 0.5 to 1
kg/cm2G. if this is the case, it will not be
necessary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is
discharged too suddenly, the refrigeration oil
will also be discharged.
(1) Confirm that both the 2-way and 3-way valves
are set to the back seat.
(2) Connect the charge set to the 3-way valve’s
port.
– Leave the valve on the charge set closed.
– Connect the charge hose with the push pin to
the service port.
-41-
5. Evacuation
Liquid side
Indoor unit
Outdoor unit
2-Way
valve
Open
Gas side
3-Way
valve
Open
Vacuum pump
Lo
OPEN
CLOSE
• Procedure
(1) Connect the vacuum pump to the charge set’s
center hose
CAUTION
Use vacuum pump equipped with check value
applied to be prevented from flowing backward.
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that
the gauge needle does not move (approximately 5 minutes after turning off the vacuum
pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dir ty or
depleted, replenish as needed.
-42-
6. Gas Charging
(After Evacuation)
Liquid side
Indoor unit
2-Way
valve
Open
Outdoor unit
Gas side
Open
3-Way
valve
Check valve
Charging
cylinder
R-410A
Lo
OPEN
CLOSE
• Procedure
(1) Connect the charge hose to the charging
cylinder.
– Connect the charge hose which you disconnected from the vacuum pump to the valve
at the bottom of the cylinder.
– If you are using a gas cylinder, also use a scale
and revers the cylinder so that the system can
be charged with liquid.
CAUTION
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner.
(4) Immediately disconnect the charge hose from
the 3-way valve’s service port.
– Stopping par tway will allow the gas to be
discharged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner turn off
the air conditioner before disconnecting the hose.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air. (Be careful of the liquid
refrigerant). The procedure is the same if
using a gas cylinder.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
– If the system can not be charged with the
specified amount of refrigerant, it can be
charged with a little at a time (approximately
150g each time) while operating the air
conditioner in the cooling cycle; however, one
time is not sufficient, wait approximately 1
minute and then repeat the procedure
(pumping down-pin).
(5) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
CAUTION
This unit is charged with R-410A.
Pay attention not to charge R-22.
-43-
7. Additional gas charging
(Gas leakage)
• When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal operating
suction pressure.
• Use the graph or the equation below to get operating suction pressure according to indoor and outdoor
temperature.
Suction pressure was measured at 3-way valve service port after operating the unit for 10 minutes.
The method of using graph
- Find outdoor temperature.
- Find indoor temperature onto the curve of outdoor temperature.
- Read suction pressure at the axis of ordinates.
The method of using equation
-. Calculate suction pressure after putting indoor and outdoor temperature into the equation.
Operating Suction Pressure
(According to Indoor & Outdoor Temperature)
(At operating the Unit for 10 minutes)
13
Suction Pressure
(Kg/cm2.g)
11
40˚C
10
30˚C
9
20˚C
8
10˚C
0˚C
Outdoor Temp.
(˚C)
50˚C
12
7
6
5
5
10
15
20
25
Indoor Temp. (˚C)
30
P = 3 + 0.0123 x Tout1.5 + 0.8 x Tin0.5
2
Where, P
: Suction Pressure(kg/cm .g)
Tout : Outdoor Temperature(˚C)
Tin : Indoor Temperature(˚C)
-44-
35
40
Cycle Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Operating Current
Temp. difference
Current
: approx. 0°C
: less than 80% of
rated current
• All amount of refrigerant leaked
out. Check refrigeration cycle.
Temp. difference
Current
: approx. 8°C
: less than 80% of
rated current
• Refrigerant leakege
Clog of refrigeration cycle
Defective compressor
Temp. difference
Current
: less than 8°C
: over the reated
current
• Excessive amount of refrigerant
Temp. difference
: over 8°C
• Normal
Notice :
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Suction pressure
(Compared with
the normal value)
Temperature
(Compared with
the normal valve)
Cause of Trouble
High
Defective compressor
Defective 4-way reverse valve
Current is low.
Excessive amount of
refrigerant
High pressure does not quickly
rise at the beginning of
operation.
Insufficient amount of
refrigerant (Leakage)
Clogging
Current is low.
Higher
Normal
Lower
Higher
Description
Current is low.
Notice :
1. The suction pressure is usually R-22: 4.5~6.0 kg/cm2G(Cooling) at normal condition.
R-410a: 7.2~9.6 kg/cm2G(Cooling) at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
-45-
Electronic Parts Troubleshooting Guide
1. Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power
(After 10 seconds)
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
YES
NO
Primarily, the operating condition of Micom is OK.
Check the voltage of power(About AC 220V, 60Hz)
(About AC 220/240V, 50Hz)
• Main power's voltage
• Voltage applied to the unit
• Connecting method of Indoor/Outdoor connecting
cable
• Check PWB Assembly
- Fuse
- Pattern damage
- Varistor(ZNR01J, ZNR02J)
Check each load(Indoor/Outdoor Fan Motor,
Compressor, Stepping Motor) and contacting
condition of related connector
Check the connection housing for contacting
• Connector related to CN-TAB1, RY-COMP NO.3
• Connector related to CN-MOTOR
• Connector contacting of Outdoor Fan/Compressor
• Display PWB Assembly Check
Main PCB Board Operation Check
Content
Items
• SMPS Transformer
(Indoor unit)
- Input Voltage
- Output Voltage(ZD02D)
Remedy
- About AC220V/240V±10% - Check the power voltage
- About DC12V
• Replace Trans
• IC04D(7805) Output
(Indoor/Outdoor unit)
• DC +5V
• Replace IC04D
• IC01A[S7136(KIA7036),
Reset IC] OSC01B
• Voltage of Micom No. 36,
(DC +4.5V over) and Soldering condition.
• Replace faulty parts
-46-
2. The product is not operate with the remote control.
Turn on Main Power
While the compressor has been stopped, the compressor does not
operate owing to the delaying function for 3 minutes after stopped.
When the compressor stopped Indoor Fan is driven by a low speed.
At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the
low speed by force.)
Caused by other parts except the remote control
Cause by the remote control
When the mark(
battery.
) is displayed in LCD screen, replace
Check the contact of CN-VFD(WH) connector.
Check the connecting circuit between the remote controller
MICOM (No. ) - R17(2Ω) - IR LED - TR - R16(2.2KΩ).
Check Display PWB Assembly
- Voltage between CN-VFD(WH)
-
: DC +5V
Check point
• Check the connecting circuit between CN-VFD(WH)
- R01L(51kΩ) - C01L(680pF) - MICOM PIN 43
• Check Receiver Assembly
-47-
3. Compressor/Outdoor Fan are unable to drive.
Turn on Main Power
Operate "Cooling Mode( )" by setting the desired temperature of the
remote controller is less than one of the indoor temperature by 1°C at least.
When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.
Check the sensor for indoor temperature is attached as close as to be
effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad
connection or are not engaged, Compressor/Outdoor Fan is stopped.
• Check the related circuit of RY-FAN.
• Check the indoor temperature sensor is disconnected or not(About 10kΩ / at 25°C).
Check Relay(RY - COMP) for driving compressor.
• When the power(About AC220V/240V) is applied to the connecting wire
terminal support transferred to compressor, PWB Assembly is normal.
• Check the circuit related to the relay.
Check point
Between Micom(No.
59) and GND
Between IC01M(No. 11)
and GND
COMP ON
COMP OFF
DC5V
DC0V
Below DC 1V
(app)
About DC12V
Turn off Main Power
• Check the electrical wiring diagram of outdoor side.
• Check the abnormal condition for the component of
Compressor/Outdoor Fan Motor.
• Check the "open" or "short" of conmecting wires between indoor and
outdoor.
-48-
4. When indoor Fan does not operate.
Turn off Main power
Check the connection of CN-MOTOR
Check the Fan Motor
Check the Fuse(AC250V/T2A)
Check the related circuit of indoor Fan Motor.
• The pin NO 58 of Micom, and the part for driving TRIAC(the input and
output signal of IC01M, PIN NO 7, 10)
• Check the pattern
• Check the TRIAC
- TRIAC Open: Indoor Fan Motor never operate
- TRIAC short: Indoor Fan Motor always operates in case of ON or OFF.
Turn ON Main Power
Check the TRIAC high speed operation by remote control.
(The Indoor Fan Motor is connected)
The voltage of PIN NO 1(Black) and 3(Black) of CN-MOTOR.
About AC 180V over
About AC 50V below
TRIAC is not damaged
TRIAC change
-49-
5. When up/down Vertical Louver does not operate.
• Confirm that the up/down Vertical Louver is normally geared with the
shaft of Stepping Motor.
• If the regular torque is detected when rotating the up/down Vertical
Normal
Louver with hands
• Check the connecting condition of CN-U/D Connector
• Check the soldering condition(on PWB) of CN-U/D Connector
Check the up/down operating circuit of the Vertical Louver
• Confirm that there is DC +12V between pin (Gray) of CN-U/D and
GND.
• Confirm that there is a soldering short at following terminals.
- Between 60 , 61 , 62 and 63 of MICOM
- Between , ,
and
of IC01M
- Between , ,
and
of IC01M
If there are no problems after above checks
• Confirm the assembly conditions that are catching and interfering parts
in the rotation radial of the up/down Vertical Louver
-50-
6. When left/right Vertical Louver does not operate.
• Confirm that the left/right Vertical Louver is normally geared with the
shaft of Stepping Motor.
• If the regular torque is detected when rotating the left/right Vertical
Normal
Louver with hands
• Check the connecting condition of CN-L/R Connector
• Check the soldering condition(on PWB) of CN-L/R Connector
Check the left/right operating circuit of the Vertical Louver
• Confirm that there is DC +12V between pin (Gray) of CN-L/R and
GND.
• Confirm that there is a soldering short at following terminals.
- Between 54 , 55 , 56 and 57 of MICOM
- Between , ,
and
of IC02M
- Between , ,
and
of IC02M
If there are no problems after above checks
• Confirm the assembly conditions that are catching and interfering parts
in the rotation radial of the left/right Vertical Louver
-51-
7. When Inlet Grille does not operate.
• Confirm that the Inlet Grille is normally geared with the shaft of Stepping
Motor.
• If the regular torque is detected when moving the Inlet Grille with hands
Normal
• Check the connecting condition of CN-SUC Connector
• Check the soldering condition(on PWB) of CN-SUC Connector
Check the operating circuit of the Inlet Grille
• Confirm that there is DC +12V between pin (RED) of CN-U/D and
GND.
• Confirm that there is a soldering short at following terminals.
- Between , ,
and
of MICOM
- Between , ,
and
of IC01G
- Between , ,
and
of IC01G
If there are no problems after above checks
• Confirm the assembly conditions that are catching and interfering parts
in the rotation radial of the Inlet Grille
-52-
8. When Heating does not operate
Turn ON Main Power
Operate “Heating Mode( )” by setting the desired temperature of the
remote control is higher than one of the indoor temperature by 2°C at
least.
In heating Mode, the indoor fan operates in case the pipe temperature
is higher than 28°C.
Check the connector of intake and pipe sensor(thermistors)
• Check the related circuit of RY-4WAY
• Check the indoor room temperature is disconnected or not (about
10KΩ/at 25°C).
• Check the indoor pipe temperature is disconnected or not (about
5KΩ/at 25°C).
Check the DC voltage on the PWB ASSEMBLY
• The details of check are as followings
• Comp Relay.
• Outdoor fan Relay
Check point
Comp ON
Comp OFF
Check point
Fan ON
Fan OFF
Between Micom
(NO.59) and GND
DC 5V
DC 0V
Between Micom
(NO.53) and GND
DC 5V
DC 0V
Between IC01M
Below DC 1V
(NO.11) and GND
Between IC02M
Below DC 1V About DC 12V
(NO.12) and GND
About DC
12V
• 4 way Relay
Check point
4 way ON
4 way OFF
Between Micom
(NO.52) and GND
DC 5V
DC 0V
Between IC02M
Below DC 1V About DC 12V
(NO.11) and GND
-53-
Turn off Main Power
• Check the electrical wiring diagram of outdoor side.
• Check the abnormal condition for the component of
Compressor/Outdoor Fan Motor, 4 way.
• Check the "open" or "short" of connecting wires between indoor and
outdoor.
-54-
Electronic Control Device
(1) MAIN P.W.B ASSEMBLY (AC PART)
LS-135GB/GM/GR, LS-1351GB/GM/GR
• TOP VIEW
(1) MAIN P.W.B ASM (AC)
• BOTTOM VIEW
-55-
LS-1352GB/GC/GD/GM/GR/GW, LS-1202GB/GC/GD/GM/GR/GW
LS-1262GB/GC/GD/GR/GW, C142CM/CR
-H
RY-FAN
CN-RY02
RY-O2
D07D
OSC01B
CN-TH2
JS08
CO1B
JS07
JS06
A10C
JS09
JS10
JS07
A10C
JS09
JS06
C01A
IC01A
IC04D
IC02D
JS10
IC01A
JS05
JS02
ZD02D JS01
Q01C
C01A
JS05
C09D
IC04D
IC02D
D02D
11PJ
C10D
C09D
JS02
C06D
C02D
C02D
D02D
C06D
R03D
IC01J
21PJ
Q01C
JS04
ZD02D
C05D
IC01D
JS08
CO1B
JS04
L1
C05D
IC01D
11PJ
C10D
D07D
1
SMPS
SD01D
SMPS
IC03D
OSC01B
C01E
21PJ
R03D
BD1D
BD1D
BD2D
BZ01E
L1
NC
BU
SNC
CN
-S
F20RUB
PWB: 6870A90177D
PWB ASM: 6871A10056
C01E
PWB: 6870A90177D
PWB ASM: 6871A10056
SD01D
IC03D
S-
-S
F20RUB
BZ01E
D05D
C01D
3
BD4D
NTC C04D
1
BD3D
CN-4WAY/FAN/O2
3
BD2D
7
4
BD3D
NTC C04D
D05D
C01D
C02J
BU
CN
CN-COM
IC01J
7
TR01J
4
TR01J
CN-4WAY/FAN/O2
L)
CN-COM
R02J
BD4D
NF01J
C02J
CN-RY02
ZNR02J
JS03
(B
CN-TH1(WH)
CN-TH1(WH)
R02J
NF01J
VB
JS11
50SJ
JS03
R03J
CN
CN
-H
VB
(B
L)
RY-4WAY
RY-O2
RY-4WAY RY-FAN
ZNR02J
C03J
R03J
C1NP
-SDID
IS-PN
1C
L10C
C01L
JS11
50SJ
C01J
ZNR01J
C1NP
-SDID
IS-PN
1C
L10C
C01L
CN-MOTOR
CN-MOTOR
C03J
CN-U/D(WH)
CN-L/R(BL)
ZNR01J
CN-TH2
C01J
R01J
F10R
CN-TAB3
CN-U/D(WH)
CN-L/R(BL)
F10R
CN-TAB1
RY-COMP
CN-TAB2
CN-TAB3
R01J
FUSE
FUSE
AC 250V/T2A
AC 250V/T2A
CN-TAB1
RY-COMP
CN-TAB2
• TOP VIEW
JS01
• BOTTOM VIEW
EY1
EY2
CN-U/D
CN-L/R
JP19
JP23
EY3
ZNR01J
C01J
CN-MOTOR
ZNR01J
NF01J
FUSE
RY-FAN
RY-4WAY
48
RY-02
RY-4WAY
R03J
TR01J
BD03D
BD02D
IC01J
R05D
IC01J
R04J
R05D
R04J
JP21
IC03D
JP21
IC03D
IC02D
R03J
TR01J
BD03D
BD02D
IC02D
IC01D
BD01D
-56-
R02D
JS01
ZD02D
IC04D
IC01S
R02D
C07V
C01A
JS02
JS01
C05D
D02D
D02D
C02D
C02D
R06D
IC01D
BD04D
C01D
R06D
C05D
ZD02D
C06D
C08D
BD01D
C01D
D05D
SD01D
R03D
C06D
JS05
C07V
R07D
R04D
R08D
IC04D
JS02
C07D
C08D
C09D
BD04D
C02J
SMPS
L1
ZNR02J
JS03
C02J
JS04
R01L R02L
R01L R02L
SD01D
R09D
C07D
C09D
L4
JS05
C01A
JP13
R07D
R04D
R08D
C01B
SMPS
L1
C10D
L4
Q01C
C04D
R03D
D07D
C01B
C03J
ZNR02J
JS03
D05D
NTC
R09D
C11D
C01E
Q01C
R01B
OSC01B
JS04
R02A
NF01J
RY-02
D07D
C10D
JP14
32
17
R01B
OSC01B
C11D
Q02E
JP14
32
C01E
JP16 33
JP15
JP15
33
NTC
C04D
C03J
R02J
Q02E
JP16
M
OI
R01E
Q03E Q01E
R01J
R02J
JP17
BZ01E
W
01
E0
49
R01E
Q03E Q01E
CN-4WAY/FAN/O2
CN-4WAY/FAN/O2
48
JP18
JP17
RY-FAN
R02A
JP13
CN-MOTOR
JP18
49
CR
M
17
OR1H
R22H
IC01S
OR1H
R23H
JP12
JP11
JP10
JP08
OI
64
1
JP11
JP10
C02Z
OR4H
BZ01E
JP12
JP09
C01L
R02H OR6H
R05H
R23H R22H
R25H
OR4H OR3H OR2H R21H
OR5H
R24H
R25H
R02E R03E
R02E R03E
W
01
E0
CR
64
R26H JP06
R12H
R11H OJ2H
E2 R26H JP06
R02H OR6H
R05H E3
OR3H OR2H R21H
OR5H
R24H
JP08
JP24
16
R12H
C02Z
OJ1H
JP09
C01L
JS05
R04H
R01X JP07
R04H
R01X JP07
JS05
JP05
R11H OJ2H
E2
E3
IC01G
16
R04C
JP02
EEPROM
R01P
R02P
JP03
OJ1H
JP04
JP05
R02C
R03C EEPROM
R05C
JP01
R01P
R02P
JP03
R01F
C01F
CN-TH1
JP22
R05C
JP01
R04C
JP02
JP04
CN-TH1
R01F
C01F
Q05T
R02F Q05G
C01J
FUSE
IC01G
C01Z
CN
JP22
EY4
IC02M
IC01M
1
R02C
R03C
Q03T
Q04T Q03G
Q04G
C01Z
Q05T
R02F Q05G
B
U
-S
Q02T Q01T
Q02G Q01G
EY3EY1
RY-COMP
JP24
JP20
Q03T
Q04T Q03G
Q04G
DIS
CN
Q02T Q01T
Q02G Q01G
R01J
CN-U/D
P1
JP20
UB
-S
CN
EY4
EY2
CN-TAB1
CN-TAB3
CN-TAB2
RY-COMP
IC02M
IC01M
1
ISP
-D
CN
JP23
CN-TAB1
CN-TAB3
CN-TAB2
CN-L/R
JP19
(2) DISPLAY ASSEMBLY
– 6302A90003A
• TOP VIEW
REV1
R8
R7
R17
R5
1
TP1
C18
C19
R10
D1
C13
C8
C9 R13
Q1
C20
TP2
P/N 3210018043
R9
SVM-GP1119AI
Q2
SEJIN ELECTRON INC.
M43
TP3
TP4
C7
R18
R3 R4
C21
TP5
R19
TP6
R6
M42
M45
M44
R2
C14
C15
• BOTTOM VIEW
TP1
TP2
TP4
TP3
TP7
TP8
– 6871A20463
-57-
(3) SUB P.W.B ASSEMBLY
– 6871A20259
– 6871A20258
• TOP VIEW
K
• BOTTOM VIEW
K
K
-58-
1
-59-
2
RD
OR
4
3
3
4
2
2
1
1
1
2
1
3
1
2
3
4
5
1
2
3
4
5
2
3
1
2
AC PART
CN-12V
1
1
2
CN-CONT
SW PWB ASM
2
STEPPING MOTOR
SUCTION 2
3
4
5
1
2
3
4
5
5V
12V
+ C10D
220
10V SD
4
3
2
1
SMD 2012
L4 100nH
4
3
2
1
5
6
6
5
7
8
9
7
8
9
10 10
11 11
+ C09D
220
10V SD
HVB
1
C08D
103
50V
4
3
2
1
4
3
2
1
;;;
;;;;;
;;;;;
;;;;;
;;;;;
;;;;; ;;
;;;;
Q01T
C104S
12V
HVB OUT
Q06T
A104S
12V
C02T
102
D01T
1N4148
IC04D
78L05BP
O
I
7805
1
1
3
2
2
3
5V
C01T
104
12V
CN-HVB(BL)
1
2
2
1
3
4
5
6
7
CN-SUC(WH)
1
2
3
4
5
CN-U/D(WH)
3
4
5
6
7
1
2
3
4
5
1
2
2
CN-TEL
3
3
RD
OR
YL
PK
BL
RD
OR
YL
PK
BL
5V
Q03T
C104S
C07D
104
50V
12V
20K 2012
R11H~R14H
5V
C03T
102
R03T
1K
A2
SCL
WP
6
7
Vcc 8
5
A0 SDA
A1
OJ4H
BZ
2
3 4 5 6
7
8
A
V
d
d
1
A
V
s
s
AVref
AVdd
RESET
X2
X1
Vss1
INT0
INT1
D07D
UG2D
SMPS
5V
C02Z
0.01
17 18 1920 21 22 23 24 25 26 27 28 29 30 31. 32
Vss0
11
+
1
NEC
UPD780023AGC-C
Vdd0
12
13
14
15
16
CN-L/R(BL)
12V
33
36
35
34
38
37
42
41
40
39
44
43
47
46
45
48
5V
5V
ZD02D
BZX55C11
R02D
20K
L1
ZBF503D
DC LOW
VOLTAGE GND
C06D
330
25V SD
5V
4
3
IC02D
TLP421(BL)
DC HIGH
VOLTAGE GND
C05D
472M 3KV
6
1
R03D
39
1/8W 2012
C04D
470/35V/SD
R22H
R24H
R23H
C02D
104
R21H
IC01D
TNY266P
DC HIGH
VOLTAGE GND
S 2
BP 1
EN 4
D 5
+
C01D
15uF
450V/SD
Q01C
KTC3198-Y
2SC5343
5V
Q02V
KRA107S
3
1
2
3.6V
DC LOW
VOLTAGE GND
IC03D
TLP421 BL
INT
5V
E3 1K
E2 1K
C01A
0.01
50V
R02A,20K
3
4
D02D
1N4148
R05D
300K
1/4W
2
2
R06D
300K
1/4W 3216
1
3
1
4
3
8
4
8
7
6
5
7
6
4
3
5
2
4
BD01D~04D
1N4007
CN-TH1(WH)
Vout
JP11,330
3
1
2
1
CN-VFD(WH)
Vout
D05D
1N4007
DC HIGH
VOLTAGE GND
2
1
R04D
27k
1/8W 2012
5V
C01E
100/25V
R03E
220
R01L
5.1K
5V
R02H
12.1K
1%
C01L
681
50V
5V
5V
12V
C03~04V
0.01
50V
R04H
6.2K
1%
IC01A
KIA7036P
+
BZ01E
PKM17EPP-2002
R02E
910
Q01V
KTB 1151-Y
INT
R08D
56K
5V
R05H
10K
R07D
12K
R02L,1K
R04V,1K
R03V,1K
R05V
10K
Q02E
KRA107S
12V
R01E
100
R06V
220
Q01E
KRC107S
Q03E
KRC107S
OSC01B
CSTS0800MG03-T2
CRTL8.00MSOT
NTC SCK-102
OR6H OR5H OR4H OR3H OR2H OR1H
Low O/L
Hi
Med
F2
F1
SD01D
STO2D-200
Bz
R21H~R26H
12.1K, 1%
R01B
1M
C07V
104
R26H
OJ3H
20K
R02P
2012
Bz
5V
C01Z
0.01
5V
1
1
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
4
5
6
7
8
9
10
2
3
1
5
5
IC02M
KID65004AF
16 15 14 13 12 11 10 9
4
4
R11H
OJ2H
20K
R01P
2012
C01F
0.01
50V
R01F
1K
8
1
2
3
7
6
5
4
8
1
2
3
4
5
6
3
R25H
OJ1H
EEPROM
4
3
2
1 G
R02F
20K
9
9
5V
12V
IC01G
KID65004AF
12V
HVB OUT
COMP
3
2
4WAY
2
FAN
BL PK YL OR RD
o2
R12H
R13H
R14H
Q04T
A104S
INDOOR FAN
KID65004AF
7
BZ FREQ
YL
PK
BL
RD
OR
YL
PK
BL
Sub Part
STEPPING MOTOR
SUCTION 1
STEPPING MOTOR
(UP/DOWN)
IC01M
PIPE-TH
ROOM-TH
VFD DISPLAY
C03J
METAL FILM
100nF/275V/436D
C02J
METAL FILM
47nM/275V/435D
NF01J
15mH/1A
C01J
METAL FILM
100nM/275V/436D
R02J
100,1/2W
R04J
560
1/4W
R01J
120, 1/2W
INDOOR FAN
12V
3
2
1
T2
RY-FAN
RY-4WAY
RY-O2
OPTION
ZNR01J
TVR10561
FUSE
250V/T2A
T1
TR01J
3
CN-TAB2
1
1
1
1
1
3
2
1
1
1
3
2
5
4
2
5
4
3
3
2
CN-MOTOR
CN-TAB1
RY-COMP
G4A-1A-E-LG
4
TRAICS
SM1L43
R03J
680
1/2W
ZNR02J
TVR10561
4
5
IC01J
TLP762JF
N
L
INDOOR
FAN
MOTOR
T-BLOCK
1
2
4
5
6
1(L)
2(N)
AC220~240V
50/60Hz
1
2
4
5
6
SH-CAPACITOR
COMPRESSOR
OUTDOOR
FAN MOTOR
Schematic Diagram
Exploded View and Replacement Parts List
1. Indoor Unit
135312
146811
159830
152302
668713
146811
145200
668713
135314
263020
237900
135080
733010
267110
359011
342800
354210
131410
352150
346810
249951
35211B
146811
159901
135311
135516
-60-
Parts List(Indoor)
LOCATION
No.
PART No.
DESCRIPTION
131410
135080
135080
135311
135314
CHASSIS ASSEMBLY
DECORATION (TOP)
DECORATION (BOTTOM)
GRILLE ASSEMBLY, DISCHARGE
GRILLE ASSEMBLY, INLET
135312
GRILLE ASSEMBLY, FRONT
145200
146811
146811
152302
159830
159901
237900
249951
263230
263230
264110
266090
267110
268714
342800
346810
35211B
352150
354210
359011
668713
668713
73310
W0CZZ
LINK
MOTOR ASSEMBLY, STEP
MOTOR ASSEMBLY, STEP
FILTER (MECH), A/C
AIR CLEANER ASSEMBLY
VANE HORIZONTAL
WINDOW, DISPLAY
CONTROL BOX ASSEMBLY
DIGITRON
THERMISTOR ASSEMBLY
POWER CORD ASSEMBLY
H.V ASSEMBLY
REMOTE CONTROLLER ASSEMBLY
PWB(PCB) ASSEMBLY, MAIN
BEARING
MOTOR ASSEMBLY, INDOOR
TUBE ASSEMBLY, TUBING
HOSE ASSEMBLY, DRAIN
EVAPORATOR ASSEMBLY, FINAL
FAN ASSEMBLY, CROSS FLOW
PWB ASSEMBLY, SUB
PWB ASSEMBLY, SUB
PLATE
CAPACITOR,DRAWING
REMARKS
MIRROR
BLUE
METAL
MIRROR
BLUE
METAL
LSN135G*
LSN1351G*
3141A20007B
3508A20034A
3508A20034B
3531A10137B
3531A20118E
3531A20138X
3531A20138Y
3531A10147J
3531A10158T
3531A10158U
4520A20008A
4681A20055A
4681A20055B
5230A20022A
5983A10006A
5990A20015B
3790A20037F
4995A20287F
6302A90003A
6323A20004H
3H03671M
6609A10005A
6711A20073H
6871A10099C
4280A20004A
4681A20048E
5211AR7066N
5251AR1222R
5421A20086D
5901A20016A
6871A20258B
6871A20259A
1H00843A
3H01487A
3141A20007B
3508A20034E
3508A20034F
3531A10137E
3531A20118E
3531A21010B
3531A21010A
3531A10147X
3531A21004X
3531A21029A
4520A20008A
4681A20055A
4681A20055B
5230A20022A
5983A10010A
5990A20015B
3790A20083A
4995A20287R
6302A90003A
6323A20004H
3H03671M
6609A10005A
6711A20073H
6871A10099C
4280A20004A
4681A20048E
5211AR7066N
5251AR1222R
5421A20086D
5901A20016A
6871A20258B
6871A20259A
1H00843A
3H01487A
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
-61-
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
LOCATION
No.
131410
135311
135312
135314
145200
146811
146811
152302
159830
159901
249951
263230
264110
266090
267110
268712
268714
342800
346810
35211B
352150
354210
359011
668713
668713
733010
W0CZZ
PART No.
DESCRIPTION
REMARKS
CHASSIS ASSEMBLY
GRILLE ASSEMBLY,DISCHARGE(INDOOR)
GRILLE ASSEMBLY,FRONT(INDOOR) MIRRIOR
BLUE
WHITE
WOOD
METAL
CHERRY
GRILLE ASSEMBLY,INLET
MIRRIOR
BLUE
WHITE
WOOD
METAL
CHERRY
LINK
MOTOR ASSEMBLY,STEP
MOTOR ASSEMBLY,STEP
FILTER(MECH),A/C
AIR CLEANER ASSEMBLY
VANE,HORIZONTAL
CONTROL BOX ASSEMBLY,INDOOR
THERMISTOR ASSEMBLY
POWER CORD ASSEMBLY
H.V ASSEMBLY
REMOTE CONTROLLER ASSEMBLY
PWB(PCB) ASSEMBLY,DISPLAY
PWB(PCB) ASSEMBLY,MAIN
BEARING
MOTOR ASSEMBLY,INDOOR
TUBE ASSEMBLY,TUBING
HOSE ASSEMBLY,DRAIN
EVAPORATOR ASSEMBLY,FIRST
FAN ASSEMBLY,CROSS FLOW
PWB(PCB) ASSEMBLY,SUB
PWB(PCB) ASSEMBLY,SUB
PLATE
CAPACITOR,DRAWING
LSN1352G*
LSN1202G*
LSN1262G*
3141A20007B
3531A10137E
3531A20284V
3531A20284T
3531A20284X
3531A20284U
3531A20284W
3531A20284Y
3531A20285E
3531A20285B
3531A20285D
3531A20285C
3531A20285A
3531A20285F
4520A20008A
4681A20055A
4681A20055B
5230A20022A
5983A20010K
5990A20015B
4995A20486J
6323A20004H
3H03671M
6609A10005D
6711A20091J
6871A20463D
6871A10056G
4280A20004A
4681A20048E
5211AR7066N
5251AR1222R
5421A20086D
5901A20016J
6871A20259A
6871A20258E
1H00843A
3H01487K
3141A20009B
3531A20184B
3531A20287V
3531A20287T
3531A20287X
3531A20287U
3531A20287W
3531A20287Y
3531A20286A
3531A20286B
3531A20286E
3531A20286D
3531A20286C
3531A20286F
4520A20008A
4681A20055A
4681A20055B
5230A20033A
5983A10014F
5990A20022B
4995A20375R
6323A20004A
3H03671F
6609A10005E
6711A20091K
6871A20463B
6871A10056N
4280A20004A
4681A20103A
5211A30596A
5251AR1222R
5421A20086H
5901A20016H
6871A20259A
6871A20258E
3301A10005A
3H01487A
3141A20007B
3531A10137E
3531A20284V
3531A20284T
3531A20284X
3531A20284U
3531A20284Y
3531A20285E
3531A20285B
3531A20285D
3531A20285C
3531A20285F
4520A20008A
4681A20055A
4681A20055B
5230A20022A
5983A20010K
5990A20015B
4995A20486J
6323A20004H
3H03671M
6609A10005D
6711A20091J
6871A20463D
6871A10056G
4280A20004A
4681A20048E
5211AR7066N
5251AR1222R
5421A20086D
5901A20016J
6871A20259A
6871A20258E
1H00843A
3H01487K
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
-62-
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
LOCATION
No.
131410
135311
135312
135314
145200
146811
146811
152302
159830
159901
249951
263230
264110
266090
267110
268712
268714
342800
346810
35211B
352150
354210
359011
668713
668713
733010
W0CZZ
PART No.
DESCRIPTION
REMARKS
CHASSIS ASSEMBLY
GRILLE ASSEMBLY,DISCHARGE(INDOOR)
GRILLE ASSEMBLY,FRONT(INDOOR) MIRRIOR
METAL
GRILLE ASSEMBLY,INLET
MIRRIOR
METAL
LINK
MOTOR ASSEMBLY,STEP
MOTOR ASSEMBLY,STEP
FILTER(MECH),A/C
AIR CLEANER ASSEMBLY
VANE,HORIZONTAL
CONTROL BOX ASSEMBLY,INDOOR
THERMISTOR ASSEMBLY
POWER CORD ASSEMBLY
H.V ASSEMBLY
REMOTE CONTROLLER ASSEMBLY
PWB(PCB) ASSEMBLY,DISPLAY
PWB(PCB) ASSEMBLY,MAIN
BEARING
MOTOR ASSEMBLY,INDOOR
TUBE ASSEMBLY,TUBING
HOSE ASSEMBLY,DRAIN
EVAPORATOR ASSEMBLY,FIRST
FAN ASSEMBLY,CROSS FLOW
PWB(PCB) ASSEMBLY,SUB
PWB(PCB) ASSEMBLY,SUB
PLATE
CAPACITOR,DRAWING
C142CR. NU1
C142CM.NU1
3141A20007B
3531A10137B
3531A20284Q
3531A20285E
4520A20008A
4681A20055A
4681A20055B
5230A20022A
5983A20010G
5990A20015B
4995A20486G
6323A20004H
6411A20015J
6609A10005D
6711A20077U
6871A20463D
6871A10056G
4280A20004A
4681A20048E
5211AR7066N
5251AR1222R
5421A20086D
5901A20016J
6871A20259A
6871A20258E
1H00843A
3H01487K
3141A20007B
3531A10137B
3531A20284R
3531A20285A
4520A20008A
4681A20055A
4681A20055B
5230A20022A
5983A20010G
5990A20015B
4995A20486G
6323A20004H
6411A20015J
6609A10005D
6711A20077U
6871A20463D
6871A10056G
4280A20004A
4681A20048E
5211AR7066N
5251AR1222R
5421A20086D
5901A20016J
6871A20259A
6871A20258E
1H00843A
3H01487K
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
-63-
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
2. Outdoor unit
437210
435301
437212
554031
435511
546810
552102-2
559010
649950
552201
552111
552102-1
552116
W0CZZ
552202
567502
561410
554160
447910
550140
552203-1
430410
552203-2
-64-
Parts List(Outdoor)
LOCATION
No.
430410
435511
437210
437212
447910
546810
550140
552102-1
552102-2
552111
552116
552201
552202
552203-1
552203-2
554031
554160
559010
W0CZZ
561410
649950
PART No.
DESCRIPTION
REMARKS
BASE ASSEMBLY, OUTDOOR
COVER ASSEMBLY, CONTROL
PANEL ASSEMBLY, FRONT
PANEL ASSEMBLY REAR
BARRIER ASSEMBLY, OUTDOOR
MOTOR ASSEMBLY, OUTDOOR
ISOLATOR, COMP.
TUBE, CAPILLARY BENT
TUBE, CAPILLARY BENT
TUBE ASSEMBLY, CAPILLARY
TUBE ASSEMBLY, REVERSING
VALVE, CHECK
VALVE, REVERSING
VALVE, SERVICE
VALVE, SERVICE
CONDENSER ASSEMBLY, BENT
COMPRESSOR
FAN ASSEMBLY, PROPELLER
CAPACITOR, DRAWING
O.L.P
CONTROL BOX ASSEMBLY, OUTDOOR
LSU135G*
LSU1351G*
3041AR2205C
3550AR2620P
3721AR2658E
3721AR2734B
4681AR1392H
4H00982E
5210A20595X
-
3041AR2205C
3550AR2620P
3721AR2658E
3721AR2734B
4681AR1392H
4H00982E
5210A20595X
-
2H01890P
2H02479J
5403A20061D
2520UKRK1BA
5900AR1119B
2H01451P
6750U-L033A
4995A20445A
2H01890P
2H02479J
5403A20061D
2520UKRK1BA
5900AR1119B
2H01451P
6750U-L033A
4995A20445B
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
-65-
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
LOCATION
No.
430410
435511
437210
437212
546810
550140
552102
554031
554160
559010
561410
649950
552203-1
552203-2
W0CZZ
PART No.
DESCRIPTION
REMARKS
BASE ASSY,OUTDOOR
COVER ASSEMBLY,CONTROL(OUTDOOR)
PANEL ASSEMBLY,FRONT SUB
PANEL ASSEMBLY,REAR(OUTDOOR)
MOTOR ASSEMBLY,OUTDOOR
ISOLATOR,COMP
TUBE,CAPILLARY BEND
CONDENSER ASSEMBLY,BENT
COMPRESSOR SET
FAN ASSEMBLY,PROPELLER
O.L.P
CONTROL BOX ASSEMBLY,OUTDOOR
VALVE,SERVICE
VALVE,SERVICE
CAPACITOR,DRAWING
LSU1352G*
LSU1202G*
LSU1262G*
3041AR2205C
3550AR2620P
3721AR2658E
3721AR2734B
4681AR1392H
4H00982E
5210A20595X
5403A20061D
2520UKRK1BA
5900AR1119B
6750U-L033A
4995A20445B
2H01890P
2H02479J
2H01451P
3041AR2205C
3550AR2620P
3721AR2658E
3721AR2734B
4681AR1392H
4H00982E
5210A20204G
5403A20061D
2520UKBK1AA
5900AR1119B
6750U-L008A
4995A20445D
2A00393K
2H02479J
6120AR2194G
3041AR2205C
3550AR2620P
3721AR2658E
3721AR2734B
4681AR1392H
4H00982E
5210A20595X
5403A20061D
2520UKRK1BA
5900AR1119B
6750U-L033A
4995A20445B
2H01890P
2H02479J
2H01451P
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
-66-
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
LOCATION
No.
430410
435511
437210
437212
546810
550140
552102
554031
554160
559010
561410
649950
552203-1
552203-2
W0CZZ
PART No.
DESCRIPTION
REMARKS
BASE ASSY,OUTDOOR
COVER ASSEMBLY,CONTROL(OUTDOOR)
PANEL ASSEMBLY,FRONT SUB
PANEL ASSEMBLY,REAR(OUTDOOR)
MOTOR ASSEMBLY,OUTDOOR
ISOLATOR,COMP
TUBE,CAPILLARY BEND
CONDENSER ASSEMBLY,BENT
COMPRESSOR SET
FAN ASSEMBLY,PROPELLER
O.L.P
CONTROL BOX ASSEMBLY,OUTDOOR
VALVE,SERVICE
VALVE,SERVICE
CAPACITOR,DRAWING
C142CR. UU1
C142CM. UU1
3041AR2205C
3550AR2620P
3721AR2658E
3721AR2734B
4681AR1392H
4H00982E
5210A20595X
5403A20061D
2520UKRK1BA
5900AR1119B
6750U-L033A
4995A20445A
2H01890P
2H02479J
2H01451P
3041AR2205C
3550AR2620P
3721AR2658E
3721AR2734B
4681AR1392H
4H00982E
5210A20595X
5403A20061D
2520UKRK1BA
5900AR1119B
6750U-L033A
4995A20445A
2H01890P
2H02479J
2H01451P
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
-67-
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
P/No.: 3828A30114B
Printed in Korea