LonWorks  System Integrator Guide for the Intelli-Fin  Boiler Interface Controller
Save Date: November 11, 2003
Version: IF-INT-02.doc
Edit: 2
Page 62
• Enter the neuron ids of the BICs from a copy of the REPLACEMNT CD ORDER FORM. Finish. During this
step, the BICs will be loaded with an updated network image (domain / subnet / node address and the bindings)
you have created for this project.
********* WARNING!!!! *********
Failure to match the Neuron Id with the correct BIC, will require that you delete the function blocks
and bindings from your project, rename the BICs according to the correct name for each neuron id,
and create function blocks and bindings again.
DO NOT DE-COMMISION BICs
DE-COMMISIONING RESETS CONFIGURATION PARAMETERS
and the factory set parameters will be lost.
In addition, De-Commissioning sets the node offline, and the BIC no longer will control a UNIT.
********* WARNING!!!! *********