Download AIR CONDITIONER

Transcript
FILE NO. SVM-06027
SERVICE MANUAL
AIR CONDITIONER
SPLIT WALL TYPE
RAS-13GKHP-ES2 / RAS-13GAH-ES2
RAS-13GKP-ES2 / RAS-13GA-ES2
RAS-13NKHP-AS2 / RAS-13N2AH-AS2
RAS-13NKP-AS2 / RAS-13N2A-AS2
June 2006
FILE NO. SVM-06027
CONTENTS
1.
SPECIFICATIONS
2.
CONSTRUCTION VIEWS
2-1 Indoor Unit
2-2 Outdoor Unit
3.
WIRING DIAGRAM
3-1
3-2
3-3
3-4
4.
SPECIFICATION OF ELECTRICAL PARTS
4-1
4-2
4-3
4-4
5.
RAS-13GKHP-ES2 / RAS-13GAH-ES2
RAS-13GKP-ES2 / RAS-13GA-ES2
RAS-13NKHP-AS2 / RAS-13N2AH-AS2
RAS-13NKP-AS2 / RAS-13N2A-AS2
Indoor Unit (RAS-13GKHP-ES2, RAS-13NKHP-AS2)
Outdoor Unit (RAS-13GAH-ES2,RAS-13N2AH-AS2)
Indoor Unit (RAS-13GKP-ES2,RAS-13NKP-AS2)
Outdoor Unit (RAS-13GA-ES2,RAS-13N2A-AS2)
REFRIGERATION CYCLE DIAGRAM
5-1 RAS-13GKHP-ES2 / RAS-13GAH-ES2
RAS-13NKHP-AS2 / RAS-13N2AH-AS2
5-2 RAS-13GKP-ES2 / RAS-13GA-ES2
RAS-13NKP-AS2 / RAS-13N2A-AS2
6.
CONTROL BLOCK DIAGRAM
6-1 RAS-13GKHP-ES2 / RAS-13GAH-ES2,
RAS-13NKHP-AS2 / RAS-13N2AH-AS2
6-2 RAS-13GKP-ES2 / RAS-13GA-ES2,
RAS-13NKP-AS2 / RAS-13N2A-AS2
7.
OPERATION DESCRIPTION
7-1 Outline of Air Conditioner Control
7-2 Description of Operation Circuit
7-3 Hi POWER Mode
7-4 High-Temperature Limit Control
7-5 Low-Temperature Limit Control
7-6 Defrost Operation
7-7 Current Limit Control
7-8 Auto Restart Function
7-9 Filter Check Lamp
7-10 Self-Cleaning function
7-11 QUIET Mode
7-12 COMFORT SLEEP mode
−1−
FILE NO. SVM-06027
8.
INSTALLATION PROCEDURE
8-1
8-2
8-3
8-4
8-5
8-6
8-7
9.
Safety Cautions
Installation Diagram of Indoor and Outdoor Units
Installation
Indoor Unit
Outdoor Unit
How to Set Remote Control Selector Switch
Others
TROUBLESHOOTING CHART
9-1
9-2
9-3
9-4
9-5
9-6
Troubleshooting Procedure
Basic Check Items
Primary Judgement
Self-Diagnosis by Remote Control (Check Code)
Troubleshooting Flowcharts
Troubleshooting for Remote Control (Including The Indoor P.C. Board)
10. PARTS REPLACEMENT
10-1 Indoor Unit
10-2 Outdoor Unit
11. EXPLODED VIEWS AND PARTS LIST
11-1
11-2
11-3
11-4
11-5
11-6
11-7
Indoor Unit (E-Parts Assy) (For RAS-13GKHP-ES2)
Indoor Unit (E-Parts Assy) (For RAS-13NKHP-AS2)
Indoor Unit (E-Parts Assy) (For RAS-13GKP-ES2)
Indoor Unit (E-Parts Assy) (For RAS-13NKP-AS2)
Indoor Unit
Outdoor Unit (RAS-13GAH-ES2,RAS-13N2AH-AS2)
Outdoor Unit (RAS-13GA-ES2,RAS-13N2A-AS2)
• This air conditioner is charged with
HFC (R410A) that doesn't deplete the
Ozone layer.
• This air conditioner requires special
installation for the refrigerant R410A.
−2−
FILE NO. SVM-06027
1. SPECIFICATIONS
ITEM
Cooling
Capacity
kW
Heating
220V
240V
220V
3.74
3.82
4.20
Phase
Power source
V
Power factor
1.19
1.14
%
98
96
96
A
current
Outdoor
A
Starting current
Moisture removal
Noise
Refrigerant
5.20
5.27
5.00
A
2.0
41/35/31
Outdoor (220-240V)
dB
51
50
95
98
97
5.18
5.10
51
50
0.98
1.08
mm
∅ 12.7
Flare connection
mm
∅ 6.35
Flare connection
m
15*1
m
6
RAS-13GKHP-ES2
RAS-13NKHP-AS2
RAS-13GKP-ES2
RAS-13NKP-AS2
Height
mm
275
Width
mm
790
Depth
mm
218
Net weight
4.90
Capillary tube
INDOOR UNIT
kg
10
Evaporator type
Finned tube
Indoor fan type
Cross flow fan
High fan
Airflow volume Medium fan
Low fan
Fan motor output
m3/h
630
650
630
3
m /h
520
550
520
m3/h
430
490
430
W
20
Air filter
Honeycomb woven filter with PP frame
OUTDOOR UNIT
Height
RAS-13GAH-ES2,RAS-13N2AH-AS2
mm
Width
mm
780
mm
kg
290
38
39
Condenser type
Finned tube
Outdoor fan type
Airflow volume
Propeller fan
m /h
3
Fan motor output
2120
2200
W
2200
2030
2150
30
PA150X2C-4FT
W
1100
Safety device
Fuse, Overload relay
Louver type
Usable outdoor temperature range
2120
42
Model
Output
RAS-13GA-ES2,RAS-13N2A-AS2
550
Depth
Net weight
Compressor
1.17
51
kg
Connection type
Dimensions
1.13
R410A
Refrigerant control
Dimensions
1.18
50
Name of refrigerant
Liquid side size
3.75
26
dB
Interconnection Connection type
Maximum length
pipe
(One way)
Maximum height
difference
3.75
30
lit/h
Gas side size
4.26
0.15
Indoor (H/M/L)
Rated amount
240V
50
1.15
Indoor
220V
220 − 240
kW
Running
Cooling
240V
1∅
Hz
Power consumption
RAS-13GKP-ES2 / RAS-13GA-ES2
RAS-13NKP-AS2 / RAS-13N2A-AS2
RAS-13GKHP-ES2 / RAS-13GAH-ES2
RAS-13NKHP-AS2 / RAS-13N2AH-AS2
MODEL
Automatic louver
°C
15 ~ 43
−10 ~ 24
−3−
15 ~ 43
FILE NO. SVM-06027
Note : 1
• Capacity is based on the following temperature conditions.
Temperature
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Condition
JIS B8615-1
Cooling
Heating
(DB)
27°C
20°C
(WB)
19°C
15°C
(DB)
35°C
7°C
(WB)
24°C
6°C
Note : 2
*1 No need to charge extra refrigerant.
−4−
FILE NO. SVM-06027
2. CONSTRUCTION VIEWS
2-1. Indoor Unit
Front panel
Air filter
Air inlet
Heat exchanger
218
6
60
60
275
790
6
Air outlet
48
Knock out system
48
Knock out system
64 53
590
120
80
Hanger
Drain hose (0.54m)
Connecting pipe (0.43m)
(Flare ∅6.35)
Connecting pipe (0.33m)
(Flare ∅12.7)
320
Hanger
For stud bolt (∅6)
Hanger
170 or more
160
170 or more
190
Minimum
distance
to ceiling
40
Minimum
distance
to ceiling
Hanger
Hanger
90
150
160
160
90
150
Installation plate outline
Center line
−5−
32
275
45
45
65 or more
Minimum
distance
to ceiling
For stud bolt
(∅ 8~∅10)
235
215
26
620
235
215
57
18
Wireless remote control
FILE NO. SVM-06027
2.2. Outdoor Unit
A
109
28
124
600
50
307
86
321
321
R15
36
321
307
Ø6 hole
R5.5
Ø6 hole
Ø11x14 hole
A detail Drawing (Back leg)
Ø 25 Drain outlet
FAN-GUARD
2- Ø11 x 14 Hole
(For Ø8 -Ø10 anchor bolt)
36
50
R15
B Detail Drawing (Front leg)
Ø 436
COVER-PV
275
550
Z
290
90
600
90
321
342
69
Electrical part cover
Liquid side
(Flare Ø 6.35)
129
54
Z View
84
Gas side
(Flare Ø12.7)
Service port
600
100 or more
Air intlel
321
600 or more
100 or more
Air outlel
600 or more
4x Ø11 Long holes(For Ø 8- Ø 10 anchor bolt)
−6−
FILE NO. SVM-06027
3. WIRING DIAGRAM
3-1. RAS-13GKHP-ES2 / RAS-13GAH-ES2
73°Cx2
THERMAL FUSE
BLU
BLU
BLU
BLU
BLU
BLU
BLU
1
1
2
3
4
5
6
7
8
9 10 11
2
1
1
2
3
4
5
6
7
8
9 10 11
CN07
CN14
DC5V
R21
VARISTOR
T6.3A 250VAC
FUSE F01
C01
1
3
3
CN27
1
2
CN01
BLK
BLK
THERMO
SENSOR (TA)
1
2
1
2
BLK
2
BLK
1
OUTDOOR
TERMINAL
BLOCK
HEAT EXCHANGER
SENSOR (TC)
3
GRN&YEL
4
INDOOR
OUTDOOR
1(L)
2(N)
4
3
BLU
BLK
BLU
CHASSIS
SOLENOID COIL
RED
RED
CAPACITOR
RED
WHI BLK
FAN
MOTOR
COMPRESSOR
PNK
R25
C15
CR02
2
C63
R27
BLU
BLK
1
DB01
IC03 R26
CN10
1
2
3
4
5
6
AC FAN MOTOR
INDOOR
TERMINAL
BLOCK
+
RY04
150°C
CN03
DC12V
R319
C02
MAIN P.C. BOARD
WP-003
RY03
Micro
Power
Module
Voltage
Regulator
L01
4
WHI
BLU
2
3
BLU
YEL
WHI
3
4
BLU
YEL
YEL
4
CR01
1
9 10 11
YEL
8
PNK
7
CR03
T02
C.T.
6
5
RY01
BLK
5
5
3
SINGLE PHASE
220-240V~, 50Hz
4
2
R22
VARISTOR
GRN & YEL
3
2
RED
BLU(N)
2
1
WHI
N
CN25 1
1
PNK
BRW(L)
SG01
DSA
INFRARED RAYS RECEIVE
AND INDICATION PARTS
2 3 4 5 6 7 8 9 10 11
1
CN04
BLK
P04
L
Louver
Motor
CAPACITOR
WHI
− 7−
1
2
3
4
5
6
BLK
GRY
YEL
BRW
RED
WHI
CN11
5
5
3
3
1
1
1 2 3
1 2 3
FILE NO. SVM-06027
3-2. RAS-13GKP-ES2 / RAS-13GA-ES2
Infrared rays receiver
and indication parts.
1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11
TRANS (TT-10)
CN14
GRY
RED
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
WHI
CN25
1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11
BLU
WHI
3
1
3 CN05
1
1
1
BLK
3
3 CN06
P04
Heat Exchanger
Sensor (TC)
Thermo Sensor (TA)
N
CN01
1 1
2 2
DB50
RY01
C50
+
F01
T6.3 A
250 VAC
CN03
1 1
2 2
R21
22
CR03
R48
1 1
4
3
CN04
WHI
WHI
150 C
1
2
3
4
5
6
1
2
3
4
5
6
BLK
RED
Indoor FAN motor
CN31
PNK
2
1
CN10
5 5
3 3
C01
BLK
C58
1
C15
INDOOR
OUTDOOR
OUTDOOR
TERMINAL
BLOCK
1(L)
1 1
2 2
3 3
D38
L01
2(N)
CHASSIS
RED
BLK
1
2
3
4
5
YEL
GRY
BRW
R46
R22
GRN&YEL
BLK
1
2
3
4
5
DC 5 V
R47
IC03
INDOOR
TERMINAL
BLOCK
WHI
YEL
YEL
YEL
YEL
Louver motor
BLU (N)
SINGLE PHASE
220-240V~, 50Hz
CN07
1 1
2 2
3 3
4 4
5 5
CN11
SG01
DSA
BRW (L)
DC 12 V
Regulator
circuit
GRN&YEL
L
MCC-920
4
3
RED
CAPACITOR
CAPACITOR
FAN MOTOR
RED
WHI
COMPRESSOR
PNK
WHI
−8−
1 2
1 2
TEMP FUSE
PNK
73 C
FILE NO. SVM-06027
3-3. RAS-13NKHP-AS2 / RAS-13N2AH-AS2
73°Cx2
THERMAL FUSE
Louver
Motor
1
BLU
BLU
BLU
BLU
BLU
BLU
BLU
1
1
2
3
4
5
6
7
8
9 10 11
2
1
1
2
3
4
5
6
7
8
9 10 11
CN07
CN14
DC5V
T6.3A 250VAC
FUSE F01
R21
VARISTOR
C01
1
3
3
CN27
1
2
CN01
BLK
BLK
THERMO
SENSOR (TA)
1
2
1
2
BLK
2
BLK
1
OUTDOOR
TERMINAL
BLOCK
GRN&YEL
BLU
RED
3
4
INDOOR
OUTDOOR
1(L)
2(N)
4
3
BLU
BLK
BLU
CHASSIS
SOLENOID COIL
RED
RED
CAPACITOR
RED
WHI BLK
FAN
MOTOR
COMPRESSOR
PNK
R25
C15
HEAT EXCHANGER
SENSOR (TC)
2
C63
R27
CR02
WHI
BLK
1
DB01
IC03 R26
CN10
1
2
3
4
5
6
AC FAN MOTOR
INDOOR
TERMINAL
BLOCK
+
RY04
150°C
CN03
DC12V
R319
C02
MAIN P.C. BOARD
WP-003
RY03
Micro
Power
Module
Voltage
Regulator
L01
4
WHI
BLU
2
3
BLU
YEL
WHI
3
4
BLU
YEL
YEL
4
CR01
1
9 10 11
YEL
8
PNK
7
5
RY01
T02
C.T.
6
5
3
SINGLE PHASE
220-240V~, 50Hz
5
2
BLU(N)
BLK
4
2
R22
VARISTOR
GRN & YEL
3
CR03
BRW(L)
2
1
PNK
SG01
DSA
CN25 1
1
CN04
BLK
P04
INFRARED RAYS RECEIVE
AND INDICATION PARTS
2 3 4 5 6 7 8 9 10 11
CAPACITOR
WHI
−9−
1
2
3
4
5
6
BLK
GRY
YEL
BRW
RED
WHI
CN11
5
5
3
3
1
1
1 2 3
1 2 3
FILE NO. SVM-06027
3-4. RAS-13NKP-AS2 / RAS-13N2A-AS2
Infrared rays receiver
and indication parts.
1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11
TRANS (TT-10)
CN14
GRY
RED
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
WHI
CN25
1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11
BLU
WHI
3
1
3 CN05
1
1
1
BLK
3
3 CN06
P04
Heat Exchanger
Sensor (TC)
Thermo Sensor (TA)
MCC-920
4
3
CN01
1 1
2 2
DB50
RY01
C50
+
F01
T6.3 A
250 VAC
CN03
1 1
2 2
DC 12 V
Regulator
circuit
CN07
1 1
2 2
3 3
4 4
5 5
R21
1 1
2 2
3 3
R47
R22
CR03
22
C58
D38
L01
C15
3 3
C01
R48
1 1
4
3
CN10
5 5
1
CN31
CN04
PNK
GRN&YEL
WHI
BLK
1 2
1 2
2
INDOOR
OUTDOOR
OUTDOOR
TERMINAL
BLOCK
1(L)
WHI
150 C
1
2
3
4
5
6
1
2
3
4
5
6
BLK
RED
Indoor FAN motor
SINGLE PHASE
220-240V~, 50Hz
1
YEL
GRY
BRW
R46
IC03
2(N)
CHASSIS
RED
BLK
1
2
3
4
5
Louver motor
BRW (L)
BLU (N)
GRN&YEL
BLK
1
2
3
4
5
DC 5 V
CN11
SG01
DSA
INDOOR
TERMINAL
BLOCK
WHI
YEL
YEL
YEL
YEL
RED
CAPACITOR
CAPACITOR
FAN MOTOR
RED
WHI
COMPRESSOR
PNK
WHI
− 10 −
TEMP FUSE
PNK
73 C
FILE NO. SVM-06027
4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit ( RAS-13GKHP-ES2, RAS-13NKHP-AS2)
No.
Parts name
Type
Specifications
AC Motor with 150 ° C thermo fuse
10k W at 25°C
1
Fan motor (for indoor)
SKF-220-20-4A-1
2
Thermo sensor (TA-sensor)
3
Micro Power Module (M01)
µRM1260V
4
Microcontroller unit (IC30)
TMP87CM40AN
5
Heat exchanger sensor
(TC-sensor)
6
Line filter (L01)
7
Bridge rectifier (DB01)
8
Capacitor (C63)
9
Fuse (F01)
10
Varistor (R21, R22)
11
Resistor (R319)
12
Louver motor
MP24Z
12VDC
13
Relay (Comp., RY01)
DI1U
Rating 25A/AC250 V, 3-48VDC
14
Relay (Fan, RY03)
G5NB-1A
Rating 3A/AC250 V, 12VDC
15
Relay (Solenoide, RY04)
G5NB-1A
Rating 3A/AC250 V, 12VDC
DC 390V, Secondary DC 12V
10k W at 25°C
LC*SS11V-06270
27mH, 600mA
D3SBA60
4A, 600 V
KMH400VSSN47M22S
BET 6.3A
47mF, 400 V
T6.3A, 250VAC
TND15G561K
RF-2TK5R6
560 V
5.6 W , 2 W
4-2. Outdoor Unit (RAS-13GAH-ES2, RAS-13N2AH-AS2)
No.
Parts name
Type
Specifications
Output (Rated) 1100W, 2poles, 1 phase, 220 − 240V, 50Hz
1
2
Compressor
Fan motor
(for outdoor)
PA150X2C-4FT
HF-240-42A or
WLF-240-42A
Winding resistance (Ω)
C-R
C-S
(at 20°C)
2.35
3.22
Output (Rated) 42W, 6poles, 1 phase, 220 − 240V, 50Hz
Winding resistance (Ω)
(at 20°C)
3
Running capacitor
(for fan motor)
DS451155NPQB
AC 450V, 1.5µF
4
Running capacitor
(for compressor)
RS44B306U0214S
AC 440V, 30µF
5
Solenoid coil
(for 4-way valve)
(for Heat pump
model)
STF-01AJ503H1
AC 220 − 240V, 50Hz
− 11 −
Red-Black
White-Black
176.2 or 188
290.5 or 289
FILE NO. SVM-06027
4-3. Indoor Unit (RAS-13GKP-ES2, RAS-13NKP-AS2)
No.
Parts name
Type
1
Fan motor (for indoor)
SKF- 220-20-4A-1
2
Thermo sensor (TA-sensor)
3
Transformer
4
Microcontroller unit (IC30)
5
Heat exchanger sensor
(TC-sensor)
6
Line filter (L01)
7
Bridge rectifier (DB50)
8
Capacitor (C50)
9
Fuse (F01)
10
Varistor (R21, R22)
11
Louver motor
12
Relay (Comp., RY01)
Specifications
AC Motor with 150 °C thermo fuse
10k W at 25°C
TT-10
TMP87CM40AN
10k W at 25°C
*SS11V-06270
KBP06M/51
27mH, 600mA
1.5A, 600 V
PF1E222MNN1625
2200mF, 25 V
BET6.3A
T6.3A, 250VAC
TND15G561K
560 V
MP24Z
12VDC
DI1U
Rating 25A/AC250 V, 3~48VDC
4-4. Outdoor Unit (RAS-13GA-ES2, RAS-13N2A-AS2)
No.
Parts name
Specifications
Type
Output (Rated) 1100W, 2poles, 1 phase, 220 − 240V, 50Hz
1
2
Compressor
Fan motor
(for outdoor)
PA150X2C-4FT
WLF-240-30A
Winding resistance (Ω)
C-R
C-S
(at 20°C)
2.35
3.22
Output (Rated) 30W, 6poles, 1 phase, 220 − 240V, 50Hz
Winding resistance (Ω)
(at 20°C)
3
Running capacitor
(for fan motor)
DS451155NPQB
AC 450V, 1.5µF
4
Running capacitor
(for compressor)
RS44B306U0214S
AC 440V, 30µF
− 12 −
Red-Black
White-Black
237
380
FILE NO. SVM-06027
5. REFRIGERATION CYCLE DIAGRAM
5-1. RAS-13GKHP-ES2 / RAS-13GAH-ES2
RAS-13NKHP-AS2 / RAS-13N2AH-AS2
Cooling
0.39m
(Connecting pipe)
∅12.7
T1
Indoor unit
Heat exchanger
0.49m
(Connecting pipe)
∅6.35
Heating
Cross flow fan
P
O.D.:12.7mm
O.D.:6.35mm
Packed valve
(∅12.7)
Packed valve
(∅6.35)
Heating
Cooling
4-way valve
Heating Cooling Compressor
PA150X2C-4FT
Capillary tube
∅1.5x1500l
Accumulator
Capillary tube
∅1.0x400l
Heat exchanger
Cooling
Heating
50Hz
Standard
Heating
Cooling
Overload*1
Refrigerant
R410A : 1.08 kg.
Propeller fan
Outdoor unit
Standar d
pressure P
(MPaG)
Mark(
Ambient temp.
conditions DB/WB
(°C)
Surface temp. of heat
exchang er inter changing
pipe T1 (°C)
Fan speed
(indoor)
44.5
High
20/15
7/6
Low
27/−
24/18
2.70
3.12 ~ 3.77
)means check points of Gas Leak.
52.0 ~ 56. 8
Indoor
Outdoor
Low temperature
2.20
35.0
High
20/−
−10/−10
Standard
0.90
10.0
High
27/19
35/24
Overload
0.99
14.0
High
32/23
43/26
Low temperature
0.65
2.0
Low
21/15
21/15
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
*1 • During heating overload operation, a value for the high temperature limit control operation is included.
− 13 −
FILE NO. SVM-06027
5-2. RAS-13GKP-ES2 / RAS-13GA-ES2
RAS-13NKP-AS2 / RAS-13N2A-AS2
T1
Indoor unit
Heat exchanger
Cooling
0.39m
(Connecting pipe)
∅12.7
0.49m
(Connecting pipe)
∅6.35
Cross flow fan
P
O.D.:12.7mm
O.D.:6.35mm
Packed valve
(∅12.7)
Packed valve
(∅6.35)
Cooling
Cooling Compressor
PA150X2C-4FT
Capillary tube
∅1.7x700 l
Accumulator
Heat exchanger
Cooling
50Hz
Cooling
Refrigerant
R410A : 0.98 kg.
Propeller fan
Outdoor unit
Standar d
pressure P
(MPaG)
Mark(
)means check points of Gas Leak.
Surface temp. of heat
exchang er inter changing
pipe T1 (°C)
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor
Standard
0.80
10.0
High
27/19
35/24
Overload
1.04
15.0
High
32/23
43/26
Low temperature
0.72
2.0
Low
21/15
21/15
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
− 14 −
6. CONTROL BLOCK DIAGRAM
FILE NO. SVM-06027
6-1. RAS-13GKHP-ES2 / RAS-13GAH-ES2, RAS-13NKHP-AS2 / RAS-13N2AH-AS2
M.C.U.
Main Unit Control Panel
Heat Exchange sensor
Operation
Display
Functions
Timer
Display
Thermo. Sensor
• Louver Control
Current Sensor
• 3-minutes Delay at Restart
for Compressor
(Compressor Current)
Filter Sign
Display
Hi Power
Sign Display
Infrared Rays Signal Reciver
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
• Motor Revolution Control
• Processing
(Temperature Processing)
• Timer
Compressor
ON/OFF
Signal
Noise Filter
Louver
ON/OFF
Signal
Louver
Motor
Relay Driver, Louver Driver
Relay
Compressor
Relay
RY03
RY01
REMOTE CONTROL
Indoor Fan
Motor
Outdoor Fan 4-Way Valve
ON/OFF
ON/OFF
Signal
Signal
Relay
220-240 V~, 50Hz
PRE DEF.
Sign Display
Outdoor Fan Motor
RY04
4-Way Valve
Infrared Rays
Remote Control
Operation (
)
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
− 15 −
FILE NO. SVM-06027
6-2. RAS-13GKP-ES2 / RAS-13GA-ES2, RAS-13NKP-AS2 / RAS-13N2A-AS2
Main Unit Control Panel
Heat Exchange sensor
M.C.U.
Operation
Display
Functions
Timer
Display
• Louver Control
Thermo. Sensor
Filter Sign
Display
• 3-minutes Delay at Restart
for Compressor
Infrared Rays Signal Reciver
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Hi Power
Sign Display
• Motor Revolution Control
Fan Only
Sign Display
• Processing
(Temperature Processing)
• Timer
Compressor
ON/OFF
Signal
Noise Filter
Indoor Fan
Motor
Louver
ON/OFF
Signal
Relay Driver, Louver Driver
Relay
RY01
220-240 V~, 50Hz
REMOTE CONTROL
Compressor, Outdoor Fan Motor
Infrared Rays
Remote Control
Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
− 16 −
Louver
Motor
FILE NO. SVM-06027
7. OPERATION DESCRIPTION
7-1. Outline of Air Conditioner Control
7-1-1. Louver control
This is a fixed capacity type air conditioner, which uses (1) Vertical air flow louver
Position of veritcal air flow louver is automatically
AC motor for an indoor fan. The AC motor drive
controlled according to the operation mode.
circuit is mounted in the indoor unit. And electrical
Besides, position of vertical air flow louver can be
parts which driving the compressor and the outdoor
arbitrarily set by pressing [FIX] button.
fan motor, are mounted in the outdoor unit.
The louver position which is set by [FIX] button is
The air conditioner is controlled by the controller
stored in the microcontroller, and the louver is
mounted in the indoor unit. The controller operates all
automatically set at the stored position for the next
components based on the commands transmitted from
operation.
the remote control and the feedback data of the sensor
is as follow:
(2) Swing
If [SWING] button is pressed when the indoor unit
• The temperature measurement at the air inlet of
is in operation, the vertical air flow louver starts
the indoor heat exchanger by the indoor
swinging. When [SWING] button is pressed again,
temperature sensor
it stops swinging.
• The temperature measurement at the indoor
heat exchanger by the indoor heat exchanger
7-1-2. Indoor fan control (AC Fan motor)
temperature sensor
• Indoor fan motor operation control
(1) The indoor fan is operated by the stepless speed
• Louver motor control
change AC motor.
• LED display control
(2) For air flow level, speed of the indoor fan motor is
• Outdoor fan motor operation control
controlled in five steps (LOW, LOW+, MED, MED+
• 4-WAYS-VALVE operation control
and HIGH). If AUTO mode is selected, the fan
(Heat pump model only)
motor speed is automatically controlled by the
• Compressor operation control
difference between the preset temperature and
• Receiving the information of the operation
the room temperature.
status and judging the information or the
LOW+ = LOW+MED
2
indication of errors
MED+ = MED+HIGH
2
Table 7-1-1
FAN TAP
Cooling
OPERATION
MODE
Fan only
Model
RAS-13GKHP Series
RAS-13NKHP Series
H
M
L
L-
H
M
L
L-
M
L
L-
Dry
Heat
RAS-13GKP Series
RAS-13NKP Series
UH
UH
H
M
L
L-
UL
SL
UL
UL
SL
SL
rpm
1350
1300 1150 1100 1050 1000 950 900
850 800
750 700
Air flow volume (m3/h)
650
630
550 520 490 460 430 400
370 340
310 280
rpm
1350
1300 1150 1100 1050 1020 950 900
850 800
700 550
Air flow volume (m3/h)
650
630
370 340
280 190
− 17 −
550 520 490 470 430 400
FILE NO. SVM-06027
7-2. Description of Operation Circuit
7-2-2. Cooling operation
([MODE] button on the remote control is set
to the cooling operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are
controlled as shown in Fig. 7-2-2.
OFF OFF OFF ON
0
°C
Fig. 7-2-2
+3
M+
+2.5
*1
+2
*1
+1.5
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-3. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
*1
+1
(Room temp.) − (Preset temp.)
(Room temp.) - (Preset temp.)
Preset
temp.
ON
Outdoor fan
Preset
temp.
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
ON
0.5
OPERATION
display
7-2-1. Fan only operation
([MODE] button on the remote control is set
to the fan only operation.)
°C
4-way valve
(3) Once the operation mode is set, it is memorized in
the microcontroller so that the previous operation
can be effected thereafter simply by pressing
[ ] button.
Compressor
(2) When pressing [ ] button on the remote control,
receiving beep sounds from the indoor unit, and
the next operation is performed together with
opening the vertical air flow louver.
(Room temp.) - (Preset temp.)
(1) When turning on the breaker, the operation lamp
blinks. This means that the power supply is on.
L-
+0.5
0
(Preset temp.: 22 °C)
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L-.
(2) The Hi POWER, ECO and COMFORT SLEEP
operation cannot be set.
Fig. 7-2-1 Setting of air flow [FAN:AUTO]
Preset
temp.
°C
+3
M+
+2.5
*1
+2
+1.5
*1
*1
+1
+0.5
L-
0
-0.5
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L-.
Fig. 7-2-3 Setting of air flow [FAN:AUTO]
- 18-
FILE NO. SVM-06027
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are
controlled as shown in Fig. 7-2-4.
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are
controlled as shown in Fig. 7-2-6.
OFF
Outdoor fan
4-way valve
OPERATION
display
OFF
0
-0.5
ON
ON
Outdoor fan
+1
OFF ON OFF ON
OPERATION
display
ON
0
4-way valve
ON:6min.
OFF:4min.
OFF
Preset
temp.
Compressor
+2
°C
(Room temp.) - (Preset temp.)
ON:5min.
OFF:5min.
+3
ON:5min.
OFF:5min.
°C
Compressor
Preset
temp.
ON:6min.
OFF:4min.
7-2-4. Heating operation *Heat pump model only
([MODE] button on the remote control is set
to the heating operation.)
(Room temp.) - (Preset temp.)
7-2-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
Fig. 7-2-4
Fig. 7-2-6
(2) The microcontroller turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-2-5.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-7. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
Preset
(Room temp.) - (Preset temp.)
temp.
Room temp.
Preset temp.+1
Preset temp.
Compressor
ON
ON
ON
ON
Outdoor fan
OFF
Indoor fan
L
*SL
OFF
L
SL
OFF
L
SL
L
°C
0
-0.5
-1
-1.5
-2
L
*1
*2
M+
-5.0
-5.5
[FAN AUTO]
H
*1, *2 : The values marked with *1 and *2 are
calculated and controlled by the difference in
motor speed between M+ and L.
*Super Low
Fig. 7-2-7 Setting of air flow [FAN:AUTO]
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(4) The Hi POWER, ECO, COMFORT SLEEP and
QUIET operations cannot be set.
- 19 -
FILE NO. SVM-06027
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The
upper limit of the revolving speed is shown in
Fig. 7-2-8 and Table 7-2-1.
Indoor heat exchanger temperature
°C
45
34
34
33
32
31
21
20
Manual
AUTO (One of 5 steps)
*4
L- H (Up to
seting speed)
SL*1
Stop
*6
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-2-9. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the [RESET] button on the indoor unit
is pushed, the preset temperature is fixed at 24 °C
and the indoor unit is controlled as shown in
Fig. 7-2-9.
SL*3
*2 A+8 A+8
A− 4 A− 4
7-2-5. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
*5
Fig. 7-2-8 Cold draft preventing control
°C
*2: A is 24°C when the preset temperature is 24°C or
more and A is the preset temperature when it is
under 24 °C.
*3: SL means Super Low.
*4: Calculated from difference in motor speed
between SL and H.
*5 and *6:
Fan
speed
*5
AUTO
·
·
·
Manual
(L - H)
*6
Starting period
·
(Room temp.) - (Preset temp.)
NOTES :
*1: The fan stops for 2 minutes after thermostat-OFF
+4
Cooling operation
The louver moves to the position same
as Hi POWER operation.
Cooling operation
0
Fan only operation
-1
Heating operation
Heating model
Cooling model
.
Stabilized period
· From 12 to 25 minutes
Up until 12 minutes
passed after starting
passed after starting
the unit and room
the unit
temperature is
From 12 to 25 minutes
between preset
passed after starting
temperature and 3 °C
the unit and room
lower than preset
temperature is 3 °C
temperature
lower than preset
· 25 minutes or more
temperature
passed after starting
the unit
Room temperature
· Room temperature
Preset temperature
< Preset temperature
- 3.5 °C
- 4 °C
Table 7-2-1
- 20 -
Fig. 7-2-9
FILE NO. SVM-06027
7-3. Hi POWER Mode
([Hi POWER] button on the remote
control is pressed.)
7-4. High-Temperature Limit Control
*Heat pump model only
When [Hi POWER] button is pressed while the indoor
unit is in Auto, Cooling or Heating operation, Hi
POWER mark is indicated on the display of the remote
control and the unit operates as follows.
(1) Automatic operation
· The indoor unit operates in according to the
current operation.
The microcontroller detects the indoor heat exchanger
temperature to prevent pressure of a refrigerating cycle
from increasing excessively.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-4-1.
Heat exchanger
temp.
Compressor Outdoor fan
(2) Cooling operation
• The setting temperature drops 3°C.
(The value of the setting temperature on the
remote control does not change.)
• If the room temperature is higher than the
setting temperature by 3.5°C or more, the
horizontal louver moves to the Hi POWER
position automatically. Then when the room
temperature is 1°C less than the setting
temperature the horizontal louver returns
automatically.
• FAN speed : [AUTO]
If the room temperature is higher than the
setting temperature by 3.5°C or more, the air
conditioner operates at maximum airflow level.
If the room temperature is higher than the
setting temperature by less than 3.5°C, the air
conditioner operates at normal airflow level.
• FAN speed : One of 5 levels
If the room temperature is higher than the
setting temperature by 3.5°C or more, the air
conditioner operates at higher consecutive
airflow level. If the room temperature is higher
than the setting temperature by less than 3.5°C,
the air conditioner operates at normal airflow
level.
OFF
OFF
ON
OFF
ON
(°C)
60
53
52
ON
Fig. 7-4-1
7-5. Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger
temperature to prevent the indoor heat exchanger from
freezing.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-5-1
(3) Heating operation (Heat pump model)
· The preset temperature increases 2 °C,
(The value of the preset temperature on the
remote control does not change.)
· The indoor unit operates in normal heating
mode except the preset temperature is higher
(+2°C).
Heat exchanger
temperature
(°C)
6
2
Compressor Outdoor fan
ON
Less than 2°C continues
for 5 minutes
OFF
Fig. 7-5-1
(4) The Hi POWER mode can not be set in Dry or Fan
only operation.
- 21 -
FILE NO. SVM-06027
7-6. Defrost Operation *Heat pump model only
<In case of C>
(1) The heating operation is performed for at least 90
During the heating operation, the outdoor heat
minutes.
exchanger temperature goes down and sometimes it is
frozen.
(2) The defrost operating time is 10 minutes.
In this case, the air conditioner stops the heating
operation and starts the defrost operation to melt ice.
7-6-3. Ending condition at defrost operation
7-6-1. Condition to start the defrost operation
(1) When the compressor current becomes 7.5A or
more during defrost operation, the defrost
operation stops and the heating operation restarts.
(The current sensor detects the compressor
current.)
The defrost operation starts whichever below
conditions are satisfied.
Indoor heat exchanger temp
- Room temp
(1) When the cumulative compressor operating time is
(2) The defrost operation continues for at most
longer than 40 or 90 minutes and difference
6 minutes or 10 minutes.
between the indoor heat exchanger temperature
and the room temperature is less than the
specified value. (This value is decided by the
DEFROST LAMP :
microprocessor.) (Control example is shown in
· During defrost operation, the PRE-DEF. lamp is
Fig. 7-6-1. In case of B or C, the defrost operation
on and the indoor and outdoor fans are off.
starts.)
· The compressor start protection timer is inter(2) When the current limit control or the high
looked with the PRE-DEF. lamp. So the PRE-DEF.
temperature limit control is performed for total of
Lamp is off (the fans stop) for about 3 minutes
90 minutes.
after the [ ] button is turned on. When
the compressor is turned on, the PRE-DEF. lamp
comes on. After the heat ex-changer is preheated
to about 24°C or higher, the PRE-DEF. Lamp
goes off, and the indoor fan starts.
D
A
B
Cumulative
compressor
operating time
C
Fig. 7-6-1 (Indoor fan speed : M)
7-6-2. Defrost operation time control
<In case of B>
(1) The heating operation is performed for at least
40 minutes.
(2) The maximum defrost operating time is 6 minutes.
The defrost operating time for the 4th cycle is
10 minutes. (When the outdoor temperature is
very low, however, the defrost operating time is
10 minutes.)
Max 6 minutes
Defrost
Heating
minutes
40
Defrost
Heating
minutes
40
Defrost
Heating
minutes
40
Defrost
Heating
minutes
40
10 minutes
1 cycle
Fig. 7-6-2
- 22 -
FILE NO. SVM-06027
7-7. Current Limit Control *Heat pump model
only
The microcontroller detects the input current so as to
prevent it exceeds a specified value by means of
controlling the outdoor fan control as described in (1)
and (2).
(1) Current limit control (Cooling operation)
Control is performed as shown below by detecting
the compressor operating current with a current
sensor (C.T).
Input current
11A
I4
10A
I3
Compressor
Outdoor fan
More than I4 continues for 3 seconds
OFF
More than I3 continues for 5 minutes
OFF
ON
Fig. 7-7-1
(2)
Current limit control (Heating operation)
Control is performed as shown in Fig. 7-7-2
Input current
11A
I4
10A
I3
6A
I2
5A
I1
Compressor
Outdoor fan
More than I4 continues for 3 seconds
OFF
More than I3 continues for 5 minutes
OFF
ON
OFF
ON
Fig. 7-7-2
Remark : This function is available only for heat pump model (Cooling models have no a current sensor (C.T.)).
- 23 -
FILE NO. SVM-06027
7-8. Auto Restart Function
7-8-1. How to set auto restart function
The indoor unit is equipped with an automatic
restarting function which allows the unit to restart
operating with the set operating conditions in the event
of power supply being accidentally shut down. The
operation will resume without warning three minutes
after power is restored.
This function is not set to work when shipped from the
factory. Therefore it is necessary to set it to work.
To set the auto restart function, proceed as follows:
The power supply to the unit must be on; the function
will not set if the power is off.
Push the [RESET] button located in the center
of the front panel continuously for three seconds.
The unit receives the signal and beeps three times.
The unit then restarts operating automatically in the
event of power supply being accidentally shut down.
When the unit is on standby (Not operating)
Operation
Motions
Push [RESET] button for more
than three seconds.
The unit is on standby.
¯
The unit starts to operate.
¯
RESET
0
3S
The green lamp is on.
After approx. three seconds,
The unit beeps three times
and continues to operate.
The lamp changes from
green to orange.
If the unit is not required to operate at this time, push [RESET]
button once more or use the remote control to turn it off.
RESET button
When the unit is in operation
Operation
Motions
Push [RESET] button for more
than three seconds.
The unit is in operation.
The green lamp is on.
¯
The unit stops operating.
¯
The green lamp is turned off.
After approx. three seconds,
The unit beeps three times
RESET
0
3S
RESET button
·
·
·
If the unit is required to operate at this time, push [RESET]
button once more or use the remote control to turn it on.
While this function is being set, if the unit is in
operation, the orange lamp is on.
This function can not be set if the timer operation
has been selected.
When the unit is turned on by this function, the
louver will not swing even though it was swinging
automatically before shutting down.
·
- 24 -
While the filter check lamp is on, the
[RESET] button has the function of filter
reset button.
FILE NO. SVM-06027
7-8-2. How to cancel auto restart function
To cancel auto restart function, proceed as follows:
Repeat the setting prodedure: the unit receives the
signal and beeps three times.
The unit will be required to be turned on with the
remote control after the main power supply is turned
off.
When the unit is on standby (Not operating)
Operation
Motions
Push [RESET button for more
than three seconds.
The unit is on standby.
¯
The unit starts to operate.
¯
RESET
0
3S
The orange lamp is on.
After approx. three seconds,
The unit beeps three times
and continues
¯ to operate.
The lamp changes from
orange to green.
If the unit is not required to operate at this time, push [RESET]
button once more or use the remote control to turn it off.
RESET button
When the unit is in operation
Operation
Motions
Push [RESET] button for more
than three seconds.
The unit is in operation.
The orange lamp is on.
¯
The unit stops operating.
¯
The orange lamp is turned off.
After approx. three seconds,
The unit beeps three times
RESET
0
3S
RESET button
·
If the unit is required to operate at this time, push [RESET]
button once more or use the remote control to turn it on.
While this function is being set, if the unit is in
operation, the orange lamp is on.
7-9. Filter Check Lamp
7-8-3. Power failure during timer operation
When the elapsed time reaches 1000 hours, the filter
check lamp indicates. After cleaning the filters, turn off
the filter check lamp.
When the unit is in Timer operation, if it is turned off
because of power failure, the timer operation is
cancelled. Therefore, set the timer operation again.
7-9-1. How to turn off filter check lamp
Push [RESET] button on the indoor unit.
Note:
If [RESET] button is pushed while the filter
check lamp is not indicating, the indoor unit will start
the Automatic Operation.
- 25-
FILE NO. SVM-06027
7-10. Self-Cleaning function
Self-Cleaning function is designed to reduce humidity that causes mold to form inside the air conditioning unit.
This advanced, efficient system reduces moisture in the coil. When air conditioner is turned off, the internal fan
activates and dries the moisture in the coil for 20 minutes, then it turns off automatically.
Operation display
ON
OFF
OFF
FCU fan
ON
rpm is depend on presetting.
ON
rpm is SL speed.
OFF
FCU louver
OPEN
CLOSE
CLOSE
Timer display
ON or OFF
depend on presetting of timer function.
ON
ON or OFF
depend on presetting of timer function.
Compressor
ON or OFF
depend on presetting per room temperature.
OFF
OFF
ON or OFF
depend on presetting per room temperature.
OFF
OFF
CDU fan
8
Cool mode or dry mode
operation more than 10 mins.
8
Self-Cleaning mode
operate 20 mins.
Operation time
Automatically turn-off.
Turn off by remote controller or
timer-off function.
• The Self-Cleaning function is set as default at ex-factory.
• Self-Cleaning operation can stop manually by press [ ] button of the remote control two more time.
7-10-1. How to cancel Self-Cleaning function
7-10-2. How to set Self-Cleaning function.
To cancel the Self-Cleaning function, proceed as
follows:
•
•
•
•
To set the Self-Cleaning function, proceed as follows.
• Press [RESET] button one time or use remote
control to turn on air conditioner. The OPERATION
Press [RESET] button one time or use remote
display will show in orange color (When AUTOcontrol to turn on air conditioner. The OPERATION
RESET is ON) or green color (When AUTOdisplay will show in orange color (When AUTORESTART is OFF).
RESTART is ON) or green color (When AUTO• Hold down the [RESET] button for more than
RESTART is OFF).
20 seconds. (The air conditioner will stop suddenly
Hold down the [RESET] button for more than
when the [RESET] button is pressed but keep
20 seconds. (The air conditioner will stop suddenly
holding it continue. Then will beep 3 times is the first
when the [RESET] button is pressed but keep
3 seconds but it is not related to Self-Cleaning
holding it continue. Then will beep 3 times in the first
function)
3 seconds but it is not related to Self-Cleaning
• After holding about 20 seconds, the air conditioner
function)
will beep 5 times and OPERATION display blinks
After holding about 20 seconds, the air conditioner
5 times.
will beep 5 times without any blinking of display.
• The Self-Cleaning function had been set.
The Self-Cleaning Operation had been cancelled.
Remarks
• Per setting of Self-Cleaning function above, AUTORESTART function had been cancelled. To set
AUTO-RESTART again, please follow item 7-8-1.
Remarks
• Per setting of Self-Cleaning function above, AUTORESTART function had been cancelled. To set
AUTO-RESTART again, please follow item 7-8-1.
RESET
– 26 –
FILE NO. SVM-06027
7-11. QUIET Mode
Quiet mode is the system which, control the
revolving speed of indoor fan to work constantly
at lower than speed L. In addition, noise level of
indoor unit is less than usual.
When the [QUIET] button is pressed, the fan of the
indoor unit will be restricted the revolving speed at
speed L - until the [QUIET] button is pressed once
again (cancel Quiet mode).
Remarks :
1. Quiet mode is unable to work in dry mode.
2. Quiet mode is appropriate to work with less
cooling load and less heating load condition.
Because of the fan speed L- may cause not
enough the cooling capacity or heating capacity.
7-12. COMFORT SLEEP mode
The principles of comfort sleep mode are:
• Quietness for more comfortable.
• Save energy by changing room temperature
automatically.
• The air condition can shut down by itself
automatically.
7-12-1. Cooling mode
• The fan speed of indoor unit operates automatically,
it relates with the compressor's operation.
Compressor’s Operation
ON
OFF
Fan Speed
LSL
• The preset temperature will increase 1°C after the
Comfort sleep mode has operated for 1 hour and
the temperature will increase another 1°C after the
comfort sleep mode has operated for 2 hour. (The
value of the preset temperature on the remote control
does not change.)
• Press the [COMFORT SLEEP] button to choose the
operating hours. Repeat pressing to select the hours.
(1hr, 3hr, 5hr or 9hr)
• If the [COMFORT SLEEP] button is pressed again
means cancel comfort sleep mode.
7-12-2. Heating mode
• The fan speed of indoor unit operates automatically,
it relates with the compressor's operation.
Compressor’s Operation
ON
OFF
Fan Speed
LSL
• The preset temperature will drop down 1°C after the
Remarks:
comfort sleep mode has operated for 1 hour and the
1. Comfort sleep mode will not operate in dry mode
temperature will decrease another 1°C after the
and fan only mode.
comfort sleep mode has operated for 2 hour. (The
2. Comfort sleep mode is appropriate to work with less
value of the preset temperature on the remote control.
cooling load and less heating load condition.
dose not change.)
Because of the fan speed L- may cause not enough
•
Press
the [COMFORT SLEEP] button to choose the
the cooling capacity or heating capacity.
operating hours. Repeat pressing to select the hours.
(1hr, 3hr, 5hr or 9 hr)
• If the [COMFORT SLEEP] button is pressed again
means cancel comfort sleep mode.
- 27 -
FILE NO. SVM-06027
8. INSTALLATION PROCEDURE
8-1. Safety Cautions
For general public use
Power supply cord of parts of appliance for Outdoor use shall be at least polychloroprene sheathed flexible
cord (design H07 RN-F), or cord designation 245 IEC66.
CAUTION
New Refrigerant Air conditioner Installation
• THIS AIR CONDITIONER USES THE NEW HFC REFRGERANT (R410A), WHICH DOES NOT DESTROY
THE OZONE LAYER.
R410A refrigerant is apt to be affected by impurity such as water, oxidizing membranes, and oils because the
pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. As well as the adoption of this new
refrigerant, refrigerating machine oil has also been changed. Therefore, during installation work, be sure that
water, dust, former refrigerant, or refrigerating machine oil does not enter into the refrigerating cycle of a
new-refrigerant air conditioner.
To avoid mixing refrigerant and refrigerating machine oil, the sizes of charging port connecting sections on
the main unit are different from those for the conventional refrigerant, and different size tools are also
required. Accordingly, special tools are required for the new refrigerant (R410A) as shown below. For
connecting pipes, use new and clean piping materials with high-pressure withstand capabilities, designed for
R410A only, and ensure that water or dust does not enter. Moreover, do not use any existing piping as its
pressure withstand may be insufficient, and may contain impurities.
CAUTION
To Disconnect the Appliance from the Main Power Supply
This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a
contact separation of at least 3 mm.
If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after
installation. The plug must be disconnected from the power supply socket in order to disconnect the
appliance completely from the mains.
− 28 −
FILE NO. SVM-06027
DANGER
• FOR USE BY QUALIFIED PERSONS ONLY.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
• CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED
WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT
WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATORS,
FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY
CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R410A) WITH ANY OTHER GASEOUS
BODY INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE
REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY
HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE
INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS
IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
• Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock
switches.
• Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
• Before doing the electrical work, attach an approved plug to the power supply cord.
Also, make sure the equipment is properly earthed.
• Appliance shall be installed in accordance with national wiring regulations.
If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately.
CAUTION
• Exposure of unit to water or other moisture before installation could result in electric shock.
Do not store it in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Please read this installation manual carefully before installing the unit. It contains further important instructions for proper installation.
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to the local power supplier
before installation. If you experience any problems, or if the installation is not accepted by the supplier, the
service agency will take adequate countermeasures.
Remark per EMC Directive 89/336/EEC
To prevent flicker impressions during the start of the compressor (technical process) following installation
conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution. This distribution
has to be of an impedance.
Normally the required impedance is reached at a 32A fusing point. Air conditioner fuse has to be 16A max.!
2. No other equipment should be connected to this power line.
3. For detailed installation acceptance, please contact your power supplier whether its restriction does apply
for products like washing machines, air conditioners or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
− 29 −
FILE NO. SVM-06027
170
mm
65 mm or more
8-2. Installation Diagram of Indoor and Outdoor Units
or m
ore
Hook
1 Installation
For the rear left and left
piping
plate
Wall
Hoo
Air
filte
170
k
mm
or m
ore
Insert the cushion between
the indoor unit and wall,
and tilt the indoor unit for
better operation.
r
(At
tac
h to
the
fron
t pa
nel
.)
Shield
pipe
4 Sasa-Zeolite
Do not allow the drain hose
to get slack.
Vitamin C filter
6 Bio-enzyme &
Cut the piping hole
sloped slightly
Gingko filter
Before installing the
wireless remote control
8 Pan head wood screw
• With the remote control cover
open, load the batteries supplied
correctly, observing their polarity.
2 Wireless remote control
Make sure to run the drain
hose sloped downward.
2 Wireless remote
Cover
control
4 Remote control holder
3 Batteries
The auxiliary piping can be
connected the left, rear left,
rear right, right, bottom right
or bottom left.
Right
Vinyl tape
Apply after carrying
out a drainage test.
600 mm or more
Rear right
600
mm
Left
Bottom left
100
mm
or m
ore
Saddle
100
mm
or m
ore
m
or
Rear left
Bottom right
Insulate the refrigerant
pipes separately with
insulation, not together.
Extension
drain hose
(Not available,
provided by installer)
o re
600
mm
or m
ore
6 mm thick heat resisting
polyethylene foam
– 30 –
FILE NO. SVM-06027
8-3. Installation
8-3-1. Optional installation parts
Part
Code
Parts name
A
Refrigerant piping
Liquid side : ∅6.35 mm
Gas side : ∅12.7 mm
B
Pipe insulating material
(polyethylene foam, 6 mm thick)
C
Putty, PVC tapes
Q'ty
One
each
1
One
each
<Fixing bolt arrangement of outdoor unit>
108 mm
125 mm
86 mm
102 mm
Air inlet
7 mm
320 mm
30
32.5 mm
Air outlet
600 mm
90 mm
Drain outlet
Fig. 8-3-1
• Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong wind.
• Use ∅8 mm or ∅10 mm anchor bolts and nuts.
• If it is necessary to drain the defrost water, attach 9 drain nipple and 10 cap water proof to the
bottom plate of the outdoor unit before installing it.
− 31 −
FILE NO. SVM-06027
8-3-2. Accessory and installation parts
Part
No.
Part name (Q'ty)
1
Part
No.
Part name (Q'ty)
4
Installation plate x 1
2
8
Pan head wood screw
∅3.1 x 16 s x 2
Sasa-Zeolite Vitamin C filter x 1
6
9
Drain nipple* x 1 (For Heat pump model only)
Bio-enzyme & Gingko filter x 1
Battery x 2
Others
Mounting screw ∅4 x 25 s x 6
Remote control holder x 1
Wireless remote control x 1
Part name (Q'ty)
7
5
3
Part
No.
Name
Owner’s manual
!
Installation manual
Cap water proof* x 2
(For Heat pump model only)
The part marked with asterisk (*) is packaged with the
outdoor unit.
− 32 −
FILE NO. SVM-06027
8-3-3. Installation/Servicing tools
<Changes in the product and components>
In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged
accidentally, the service port diameter of the outdoor unit control valve (3 way valve) has been changed. (1/2
UNF 20 threads per inch)
• In order to increase the pressure withstand strength of the refrigerant piping, flare processing diameter and
size of opposite side of flare nuts have been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)
New tools for R410A
Applicable to R22 model
Changes
Gauge manifold
As pressure is high, it is impossible to measure by
means of conventional gauge. In order to prevent
any other refrigerant from being charged, each
port diameter has been changed.
Charge hose
In order to increase pressure withstand strength,
hose materials and port size have been changed
(to 1/2 UNF 20 threads per inch).
When purchasing a charge hose, be sure to
confirm the port size.
Electronic balance
for refrigerant charging
As pressure is high and gasification speed is fast,
it is difficult to read the indicated value by means
of a charging cylinder, as air bubbles occur.
Torque wrench
(nominal dia. 1/2, 5/8)
The size of opposing flare nuts has been increased.
Incidentally, a common wrench is used for nominal
diameters 1/4 and 3/8.
Flare tool
(clutch type)
By increasing the clamp bar's receiving hole,
strength of spring in the tool has been improved.
Gauge for projection
adjustment
Used when flare is made with a conventional flare
tool.
Vacuum pump adapter
Connected to conventional vacuum pump. It is
necessary to use an adapter to prevent vacuum
pump oil from flowing back to the charge hose.
The charge hose connecting part has two ports:
one for conventional refrigerant (7/16 UNF 20
threads per inch) and one for R410A. If the
vacuum pump mineral oil mixes with R410A,
a sludge may occur and damage the equipment.
Gas leakage detector
Exclusive for HFC refrigerant.
• Incidentally, the "refrigerant cylinder" comes with the refrigerant designation (R410A) and protector coating in
the U. S ARI specified rose color (ARI color code: PMS 507).
• Also, the "charge port and packing for refrigerant cylinder" require 1/2 UNF 20 threads per inch
corresponding to the port size of the charge hose.
– 33–
FILE NO. SVM-06027
8-4-2. Cutting a hole and mounting installation
plate
8-4. Indoor Unit
8-4-1. Installation place
• A place which provides the spaces around the
indoor unit as shown in the above diagram.
• A place where there is no obstacle near the air inlet
and outlet.
• A place that allows easy installation of the piping to
the outdoor unit.
• A place which allows the front panel to be opened.
<Cutting a hole>
When installing the refrigerant pipes from the rear.
Pipe
hole
CAUTION
∅65 mm
• Direct sunlight to the indoor unit's wireless
receiver should be avoided.
• The microprocessor in the indoor unit should not
be too close to RF noise sources.
(For details, see the owner's manual.)
The center of the pipe
hole is above the arrow.
100 mm
Fig. 8-4-2
<Remote control>
• A place where there are no obstacles such as a
curtain that may block the signal from the indoor
unit.
• Do not install the remote control in a place exposed
to direct sunlight or close to a heating source, such
as a stove.
• Keep the remote control at least 1 m apart from the
nearest TV set or stereo equipment. (This is
necessary to prevent image disturbances or noise
interference.)
• The location of the remote control should be
determined as shown below.
1. After determining the pipe hole position on the
mounting plate (A), drill the pipe hole (∅65 mm) at
a slight downward slant to the outdoor side.
NOTE
• When drilling a wall that contains a metal lath, wire
lath or metal plate, be sure to use a pipe hole brim
ring sold separately.
<Mounting the installation plate>
62
82.5
m
Indoor unit 5
45°
45 °
*7m
m
7m
5
Indoor unit
Hook
(Top view)
(Side view)
°
75
170
85
Remote
Reception control
range
Reception
range
1
Remote control
* : Axial distance
Pipe hole
Fig. 8-4-1
Hook
Hook
Thread
Indoor unit
Pipe hole
Weight
7 Mounting screw
Fig. 8-4-3
− 34 −
Installation
plate
FILE NO. SVM-06027
<When the installation plate is directly mounted on
the wall>
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook up
the indoor unit.
2. To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as
illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
8-4-3. Electrical work
1. The supply voltage must be the same as the rated
voltage of the air conditioner.
2. Prepare the power source for exclusive use with the
air conditioner.
CAUTION
• This appliance can be connected to the mains in
either of the following two ways.
(1) Connection to fixed wiring:
A switch or circuit breaker which disconnects
all poles and has a contact separation of at
least 3 mm must be incorporate in the fixed
wiring. An approved circuit breaker or
switches must used.
(2) Connection with power supply plug:
Attach power supply plug with power cord
and plug it into wall outlet. An approved
power supply cord and plug must be used.
CAUTION
When installing the installation plate with a
mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Installation plate
<Keep horizontal direction>
Anchor
bolt
NOTE
• Ensure all wiring is used within its electrical rating.
Projection
15 mm or less
5 mm dia. hole
Model
7 Mounting
screw
s
∅4 x 25s
Power source
Clip anchor
(local parts)
Fig. 8-4-4
CAUTION
RAS-13GKHP-ES2
RAS-13GKP-ES2
RAS-13NKHP-AS2
RAS-13NKP-AS2
50 Hz, 220 − 240 V Single phase
Maximum
running current
12A
Plug socket &
fuse rating
16A
Power cord
Failure to firmly install the unit may result in
personal injury and property damage if the unit falls.
• In case of block, brick, concrete or similar type
walls, make 5 mm dia. holes in the wall.
• Insert clip anchors for appropriate 7 mounting
screws.
NOTE
• Secure four corners and lower parts of the
installation plate with 4 to 6 mounting screws to
install it.
− 35 −
1.3 mm2 or more
FILE NO. SVM-06027
<How to connect the connecting cable>
For Cooling
Wiring of the connecting cable can be carried out
without removing the front panel.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward
you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to the local
cords) into the pipe hole on the wall.
4. Take out the connecting cable through the cable
slot on the rear panel so that it protrudes about
15 cm from the front.
5. Insert the connecting cable fully into the terminal
block and secure it tightly with screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m)
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air
inlet grille on the indoor unit.
Cord clamp
Terminal
cover
Terminal block
Screw
Connecting
cable
abo
ut 1
1 2
1 2
Earth line
5 cm
Screw
Screw
Connecting cable
Fig. 8-4-7
Earth line
60 mm
10 mm
CAUTION
• Be sure to refer to the wiring system diagram
labeled inside the front panel.
• Check local electrical cords and also any specific
wiring instructions or limitations.
10 mm
50 mm
Stripping length of the connecting cable
Fig. 8-4-8
For Heat pump
Cord clamp
Terminal
cover
Terminal block
Screw
Connecting
cable
abo
ut 1
4
1 2
3
4
1 2
3
Earth line
5 cm
Screw
Screw
NOTE
• Use stranded wire only.
• Wire type : H07 RN-F or more
<How to install the air inlet grille on the indoor unit>
• When attaching the air inlet grille, the contrary of
the removed operation is performed.
Connecting cable
Fig. 8-4-5
Earth line
80 mm
10 mm
Fig. 8-4-9
70 mm
10 mm
10 mm
50 mm
Stripping length of the connecting cable
Fig. 8-4-6
− 36 −
FILE NO. SVM-06027
8-4-4. Piping and drain hose installation
How to fix the drains cap
1) Insert hexagonal wrench (4 mm) in a center
head.
<Piping and drain hose forming>
*
Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes. (Use
polyethylene foam as insulating material.)
4 mm
Left
Bottom right
Right
Piping preparation
Bottom left
Die-cutting
Front panel slit
Rear left
Changing
drain hose
Rear right
Fig. 8-4-12
2) Firmly insert drains cap.
No gap
Do not apply lubricating oil
(refrigerant machine oil) when
inserting the drain cap.
Application causes deterioration
and drain leakage of the plug.
1. Die-cutting Front panel slit
For leftward connection, cut out slit on the left side of
the front panel. (A knife will produce splinters, so use
nippers.)
Insert a hexagon
wrench (4 mm)
Fig. 8-4-13
2. Changing drain hose
For leftward connection, bottom leftward connection
and rear leftward connection’s piping, it is necessary to
change the drain hose and drain cap.
How to remove the drains cap
Clip drain cap by needle-nose plier, and pull out.
CAUTION
Firmly insert the drain hose and drain cap; otherwise,
water may leak.
<In case of right or left piping>
• After scribing slits of the front panel with a knife or a
making-off pin, cut them with a pair of nippers or an
equivalent tool.
Fig. 8-4-10
How to install the drain hose
Firmly insert drain hose connecting part until hitting on
a heat insulator.
Slit
Fig. 8-4-14
<In case of bottom right or bottom left piping>
• After scribing slits of the front panel with a knife or a
making-off pin, cut them with a pair of nippers or an
equivalent tool.
Heat insulator
Drain hose
Fig. 8-4-11
Slit
Fig. 8-4-15
− 37 −
FILE NO. SVM-06027
<Left-hand connection with piping>
8-4-5. Indoor unit fixing
Bend the connecting pipe so that it is laid within 43 mm 1. Pass the pipe through the hole in the wall, and hook
above the wall surface. If the connecting pipe is laid
the indoor unit on the installation plate at the upper
exceeding 43 mm above the wall surface, the indoor
hooks.
unit may unstably be set on the wall. When bending the 2. Swing the indoor unit to right and left to confirm that
connecting pipe, make sure to use a spring bender so
it is firmly hooked up on the installation plate.
as not to crush the pipe.
3. While pressing the indoor unit onto the wall, hook it
at the lower part on the installation plate. Pull the
Bend the connection pipe within a radius of 30 mm.
indoor unit toward you to confirm that it is firmly
To connect the pipe after installation of the unit (figure)
hooked up on the installation plate.
(To the forefront of flare)
Hook here
1
270 mm
170 mm
1 Installation
plate
Liquid side
Gas side
2
Hook
43 mm
Outward form of indoor unit
Press
(unhook)
R 30 mm (Use polisin (polyethylene)
core or the like for bending pipe.)
80
Fig. 8-4-17
• For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while pushing
its bottom up at the specified parts.
Use the handle of screwdriver, etc.
Fig. 8-4-16
NOTE
If the pipe is bent incorrectly, the indoor unit may
unstably be set on the wall.
After passing the connecting pipe through the pipe
hole, connect the connecting pipe to the auxiliary pipes
and wrap the facing tape around them.
Push
Push
Fig. 8-4-18
CAUTION
• Bind the auxiliary pipes (two) and connecting
cable with facing tape tightly. In case of leftward
piping and rear-leftward piping, bind the auxiliary
pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Connecting cable
Installation plate
• Carefully arrange pipes so that any pipe does not
stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and
connecting pipes to each other and cut off the
insulating tape wound on the connecting pipe to
avoid double-taping at the joint, moreover, seal
the joint with the vinyl tape, etc.
• Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes. (Use
polyethylene foam as insulating material.)
• When bending a pipe, carefully do it, not to crush it.
− 38 −
FILE NO. SVM-06027
8-4-6. Drainage
8-5. Outdoor Unit
1. Run the drain hose sloped downwards.
8-5-1. Installation place
NOTE
• Hole should be made at a slight downward slant on
the outdoor side.
Do not form the
drain hose into
a wavy shape.
Do not rise the
drain hose.
50 mm
or more
Do not put
the drain
hose end
into water.
Do not put
the drain
hose end in
the drainage
ditch.
Fig. 8-4-19
2. Put water in the drain pan and make sure that the
water is drained out of doors.
3. When connecting extension drain hose, insulate the
connecting part of extension drain hose with shield
pipe.
Shield pipe
Drain hose
Inside the room
Extension drain hose
Fig. 8-4-20
CAUTION
Arrange the drain pipe for proper drainage from the
unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to drain
water collected from dew, which forms on the back of
the indoor unit, to the drain pan.
Therefore, do not store the power cord and other parts
at a height above the drain guide.
• A place which provides the spaces around the
outdoor unit as shown in the left diagram.
• A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level
and vibration.
• A place where the operation noise and discharged
air do not disturb your neighbors.
• A place which is not exposed to a strong wind.
• A place free of a leakage of combustible gases.
• A place which does not block a passage.
• When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
• An allowable length of the connecting pipe is up to 15m
• An allowable height level is up to 6m.
• A place where the drain water does not raise any
problem.
CAUTION
1. Install the outdoor unit without anything blocking
the air discharging.
2. When the outdoor unit is installed in a place
exposed always exposed to strong wind like a
coast or on a high storey of a building, secure
the normal fan operation using a duct or a wind
shield.
3. In particularly windy areas, install the unit such
as to avoid admission of wind.
4. Installation in the following places may result in
trouble.
Do not install the unit in such places.
• A place full of machine oil.
• A saline-place such as the coast.
• A place full of sulfide gas.
• A place where high-frequency waves are likely
to be generated as from audio equipment,
welders, and medical equipment.
Wall
Strong
wind
Drain guide
Fig. 8-5-1
Space for pipes
Fig. 8-4-21
− 39 −
FILE NO. SVM-06027
(Unit : N·m)
8-5-2. Refrigerant piping connection
1. Cut the pipe with a pipe cutter.
Outer dia.
Roughness
Obliquity
90°
Warp
Fig. 8-5-2
∅6.35
16 to 18 (1.6 to 1.8 kgf·m)
∅ 12.70
50 to 62 (5.0 to 6.2 kgf·m)
• Tightening torque of flare pipe connections
The operating pressure of R410A is higher than that of
R22. (Approx. 1.6 times). It is therefore necessary to
firmly tighten the flare pipe connecting sections (which
connect the indoor and outdoor units) up to the
specified tightening torque. Incorrect connections may
cause not only a gas leakage, but also damage to the
refrigerant cycle.
2. Insert a flare nut into the pipe, and flare the pipe.
• Projection margin in flaring : A (Unit : mm)
A
Die
Tightening torque
Pipe
Flare at indoor unit side
Fig. 8-5-3
Rigid (Clutch type)
Outer dia.
of copper pipe
R410A
tool used
Conventional
tool used
6.35
0 to 0.5
1.0 to 1.5
12.70
0 to 0.5
1.0 to 1.5
Flare at outdoor unit side
Fig. 8-5-4
Imperial (wing nut type, conventional tool)
Outer dia.
of copper pipe
R410A
Mark line
6.35
1.5 to 2.0
12.70
2.0 to 2.5
Fig. 8-5-5
<Tightening connection>
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers. Then
tighten the nut with a spanner and torque wrench as
shown in the figure.
Half union
Externally
threaded side
Use a wrench to secure.
CAUTION
Flare nut
Internally
threaded side
Use a torque wrench to tighten.
Fig. 8-5-6
• Do not apply excess torque.
• Otherwise, the nut may crack depending on the
conditions.
CAUTION
• KEEP IMPORTANT 4 POINTS FOR PIPING WORK
(1) Take away dust and moisture (Inside of the
connecting pipes.)
(2) Tight connection (between pipes and unit)
(3) Evacuate the air in the connecting pipes using
VACUUM PUMP.
(4) Check gas leak (connected points)
− 40 −
FILE NO. SVM-06027
8-5-3. Evacuating
<Packed valve handling precautions>
After the piping has been connected to the indoor unit,
you can perform the air purge together at once.
• Open the valve stem all the way out; but do not try
to open it beyond the stopper.
• Securely tighten the valve stem cap with torque in
the following table:
AIR PURGE
Evacuate the air in the connecting pipes and in the
indoor unit using
a vacuum pump. Do not use the refrigerant in the
outdoor unit.
For details, see the manual of the vacuum pump.
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow
prevention function so that inside oil of the pump does
not flow backward into pipes of the air conditioner
when the pump stops. (If oil inside of the vacuum pump
enters into the air conditioner, which use R410A,
refrigeration cycle trouble may result.)
1. Connect the charge hose from the manifold valve to
the service port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum
pump.
3. Open fully the low pressure side handle of the
gauge manifold valve.
4. Operate the vacuum pump to start evacuating.
Perform evacuating for about 15 minutes if the piping
length is 20 meters. (15 minutes for 20 meters)
(assuming a pump capacity of 27 liters per minute.)
Then confirm that the compound pressure gauge
reading is −101 kPa (−76 cmHg).
5. Close the low pressure side valve handle of gauge
manifold.
6. Open fully the valve stem of the packed valves
(both sides of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
Compound pressure gauge
Pressure gauge
-101kPa (-76cmHg)
Manifold valve
Handle Hi
(Keep full closed)
Handle Lo
Charge hose
(For R410A only)
Charge hose
(For R410A only)
Connecting pipe
Vacuum pump
adapter for
counter-flow
prevention
(For R410A only)
Vacuum
pump
Packed valve at gas side
Service port
(Valve core (Setting pin))
Packed valve at liquid side
Fig. 8-5-7
− 41 −
Gas side
(∅12.70 mm)
50 to 62 N·m
(5.0 to 6.2 kgf·m)
Liquid side
(∅6.35 mm)
16 to 18 N·m
(1.6 to 1.8 kgf·m)
Service port
9 to 10 N·m
(0.9 to 1.0 kgf·m)
Hexagonal wrench
is required.
4m
Fig. 8-5-8
m
FILE NO. SVM-06027
8-5-4. Wiring connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminal as
identified with their respective matched numbers on
the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the
outdoor unit terminal, make a loop as shown in the
installation diagram of indoor and outdoor unit, to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any
water coming in the outdoor unit. Proceed them so
that they do not touch any electrical or metal parts.
<Stripping length of connecting cable>
For RAS-13GAH-ES2, RAS-13N2AH-AS2
Terminal block
Earth line
Terminal
screw
1(L) 2(N) 3
Screw
50 mm
<Remote control selector switch>
• When two indoor units are installed in the same
room or the adjacent two rooms, they may be
controlled simultaneously with a single remote
control. To prevent this, set either unit and its
remote control to B setting. (Both units are set to A
setting before shipment.)
• The remote control signal is not recived when the
indoor unit setting is different from the remote
control one.
1) Turn the circuit breaker of the main power switch off
before setting the selector switch.
4
Earth
line
10 mm
When two indoor units ae installed in seperated rooms,
there is no need to change the selector switch.
1. Set the remote control selector switch with the
indoor unit.
100 mm
10 mm
8-6. How to Set Remote Control Selector
Switch
2) Remove the Air inlet grille and Front panel. (Refer to
page 59, 10-1)
Connecting
cable
3) Select the terminal of selector switch from
[A position] to [B position].
Cord clamp
Fig. 8-5-9
For RAS-13GA-ES2, RA-S13N2A-AS2
Terminal block
100 mm
10 mm Earth line
1(L) 2(N)
Terminal
screw
Screw
Earth
line
10 mm
40 mm
Connecting
cable
Selector Switch
Cord clamp
Fig. 8-5-10
CAUTION
LED Assembly
• Wrong wiring connection may cause some
electrical parts burn out.
• Be sure to comply with local codes on running
the wire from indoor unit to outdoor unit (size of
wire and wiring method etc.)
• Every wire must be connected firmly.
Fig. 8-6-1
NOTE
• Wire type: H07 RN-F or 245 IEC66 (2.0 mm2 or
more)
− 42 −
FILE NO. SVM-06027
2. Set the remote control selector switch with the
remote control
8-7. Others
8-7-1. Gas leak test
[B] is indicated on the liquid crystal display when
setting remote control selector switch to B. [A] is
not indicated on the display even if the selector
switch is set to A.
Valve cover
1) Load the remote control with the batteries.
Valve stem cap
connection
2) Press the [CHECK] button using something with
sharp point. (The preset temperature on the remote
control changes to [00].)
Service cap
connection
3) Press the [MODE] button while pressing the
[CHECK] button, [B] is indicted at the right of the
present temperature display.
• To reset the switch to the [A] setting, press the
[MODE] button again while pressing the [CHECK]
button.
Fig. 8-7-1
• Check the flare nut connections, valve stem cap
connections and service port cap connections for
gas leak with a leak detector or soap water.
8-7-2. Test operation
To switch the TEST RUN (COOL) mode, press
RESET button for 10 sec.
(The beeper will make a short beep.)
RESET
[MODE] button
RESET button
Fig. 8-7-2
[CHK] button
8-7-3. Auto restart setting
This product is designed so that, after a power failure,
it can restart automatically in the same operating mode
as before the power failure.
Fig. 8-6-2
3. Confirm that the indoor unit can operate with
the new setting.
Information
The product was shipped with Auto Restart function
in the off position. Turn it on as required.
<How to set the auto restart>
• Press and hold the RESET button for about
3 seconds. After 3 seconds, the electronic beeper
makes three short beeps to tell you the Auto
Restart has been selected.
• To cancel the Auto Restart, follow the steps
described in the section Auto Restart Function of
the Owner’s Manual.
− 43 −
FILE NO. SVM-06027
9. TROUBLESHOOTING CHART
9-1. Troubleshooting Procedure
9-2-2. Incorrect cable connection between Indoor
and outdoor units
Follow the details of 9-2. Basic Check Items.
If there is no troub le corresponding to 9-2, check
whether or not there are faulty parts following
9-4. Self-Diagnosis by Remote Control.
The indoor unit is connected to the outdoor unit with
5 cables (Heat pump model) or 3 cables (Cooling Only
model). Check that the indoor and outdoor units have
been properly connected with terminals assigned the
same numbers. If the connectors are not properly
connected, the outdoor unit will not operate normally,
or OPERATION lamp and TIMER lamp will blink (5Hz).
9-2. Basic Check Items
9-2-1. Power supply voltage
The line voltage must be AC 220 − 240V. If it is not
within this range, the air conditioner may not operate
normally.
9-2-3. Program control
The microcontroller operates as shown in Table 9-2-1
to control the air conditioner. If there are any operational problems, check whether or not the problems
correspond to Table 9-2-1. If they correspond to the
Table, they are not problems with the air conditioner,
but they are indispensable operations to control and
maintain the air conditioner properly.
Table 9-2-1
No.
Operation of air conditioner
Descriptions
1
When the main power supply is turned on,
the OPERATION lamp on the indoor unit
blinks.
The OPERATION lamp blinks to indicate that power is turned on.
If the [ ] button is pressed, the lamp stops blinking.
2
The indoor fan motor speed does not change
in the Dry operation.
The indoor fan motor speed is automatically controlled in the Dry
operation.
3
The compressor is not turned off even though The compressor has a function that it is not turned off for
the room temperature is in the range that the 3 minutes after it is turned on even though the room temperature
compressor is turned off.
is in the range that the compressor is turned off.
4
The compressor is not turned on and off even In the Dry operation, the compressor is turned on and off
though the thermo control is operated in the
automatically at the regular intervals, independent of the thermo
Dry operation.
control.
5
The PRE-DEF. lamp is indicated when the
Heating operation starts.
The PRE-DEF. lamp is indicated during the Defrosting
operation or if the indoor heat exchanger temperature is low when
the Heating operation starts. At this time, the indoor fan motor
stops to prevent cold air from blowing in the room.
6
The outdoor fan motor stops in the Heating
operation.
When the indoor heat exchanger temperature is high, the outdoor
fan motor is stopped by the high-temperature limit control
operation.
7
The compressor is not turned on even though The compressor is not turned on in the restart delay timer
the room temperature is in the range that the (3-minutes timer) operation. It is also not turned on after the power
compressor is turned on.
supply is turned on because of this timer operation.
8
The operation mode changes in the
Automatic operation.
In Automatic operation, the room temperature is detected all time
for control fan speed and the operation mode is changed every
15 minutes according to difference between the room temperature
and the preset temperature.
9
The Fan only operation continues in the
Automatic operation.
When the room temperature is in the range (Preset temperature
± 1°C), the Fan only operation is selected.
10
The Hi-POWER operation does not work.
This operation does not work when the unit is in the Dry operation
or Fan only operation.
− 44 −
FILE NO. SVM-06027
9-3. Primary Judgement
9-3-2. Failure diagnosis
9-3-1. Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
• Temperature measurement at the air outlet of the
indoor heat exchanger by the indoor temperature
sensor
• Temperature setting of the indoor heat exchanger by
the heat exchanger sensor
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation commands to the outdoor
unit
The indoor unit diagnoses the operation condition and
indicates the information of the self-diagnosis with the
lamps on the display panel of the indoor unit.
Table 9-3-1
Lamps
Self-diagnosis
A
OPERATION lamp is blinking. (1Hz)
Power failure (when the power supply is turning on)
B
OPERATION lamp is blinking. (5Hz)
Thermo sensor (TA) short or break
C
OPERATION lamp is blinking. (5Hz)
Heat exchanger sensor (TC) short or break
D
OPERATION lamp is blinking. (5Hz)
Indoor fan motor lock or failure
E
OPERATION lamp is blinking. (5Hz)
Indoor P.C. board failure
F
OPERATION and TIMER lamps are blinking.
(5Hz)
Wrong wiring of connecting cable
G
OPERATION, TIMER and PRE-DEF.
(or FAN ONLY for cooling only model) lamps
are blinking.
Cycle failure
• Gas shortage or other refrigerant cycle trouble
• Heat exchanger sensor open, break or short
• Overload relay or thermostat trouble of compressor
Table 9-3-2 Diagnosis by detective operation
Symptom
The remote control
does not work.
The outdoor fan
does not rotate.
Check
Primary judgement
Turn off the power supply once, The remote control
then turn it on. Try to operate
still does not work.
the remote control.
The remote control
works.
The indoor unit (and/or remote
control) is/are defective.
The compressor operates.
The outdoor unit (Outdoor fan
motor) is defective.
The compressor does not operate.
An internal part of the
compressor or PCB is defective.
− 45 −
OK.
FILE NO. SVM-06027
9-4. Self-Diagnosis by Remote Control
(Check Code)
(1) If the lamps are indicated as shown B to G in Table
9-3-1, exchanger the self-diagnosis by the remote
control.
(2) When the remote control is set to the service
mode, the indoor controller diagnoses the
operation condition and indicate the information of
the self-diagnosis on the display of the remote
control with the check codes. If a fault is detected,
all lamps on the indoor unit will blink at 5Hz and it
will beep for 10 seconds (Pi, Pi, Pi....). The timer
lamp usually blinks (5Hz) during the self-diagnosis.
9-4-1. How to use remote control in service mode
(1) Press [CHK] button with a tip of pencil to set the
remote control to the service mode.
• “00” is indicated on the display of the remote
control.
• The timer lamp on the indoor unit blinks
continuously. (5 times per 1 sec.)
(2) Press [TIMER 8] button.
If there is no fault with a code, the indoor unit will
beep once (Pi) and the display of the remote
control will change as follows:
00
01
02 1d
1E
22
• Check the unit with all 35 check codes (00 to 22).
as shown in Table 9-4-1.
• Press [TIMER 9] button to change the check
code backwards.
If there is a fault, the indoor unit will beep for 10
seconds (Pi, Pi, Pi...).
Note the check code on the display of the remote
control.
• 2-digits alphanumeric will be indicated on the
display.
• All lamps on the indoor unit will blink. (5 times
per 1 sec.)
(3) Press [CLR] button. After service finish for clear
service code in memory.
• “7F” is indicated on the display of the remote
control.
• Alphanumeric characters are used for the check code.
is 5.
is A.
is C.
(4) Press [ ] button to release the service
mode.
• The display of the remote control returns to as it
was before service mode was engaged.
is 6.
is B.
is D.
* This illustration in only for Heat pump model.
For Cooling only model, there is not the ( ) symbol.
− 46 −
FILE NO. SVM-06027
Table 9-4-1
Block level
Check
code
Block
Indoor
P.C. board
Diagnosis function
Check
code
Air
Conditioner
status
Symptom
Condition
Judgement and action
Thermo. sensor
short/break.
Continued
operation.
Indicated
when detected
abnormal
1.Check thermo sensor.
2.If it is OK, check
P.C. board.
Heat exchanger
sensor
short/break.
Continued
operation.
Indicated
when detected
abnormal
1.Check heat exchanger
sensor.
2.If it is OK, check
P.C. board.
Indoor fan lock,
abnormality of
indoor fan or
thermal fuse break.
All off
Indicated
when detected
abnormal
1.Check heat thermal
fuse is blow or not?
(Terminal block part.)
2.If the thermal fuse is
not blow, check indoor
fan motor.
(Refer to trouble
shooting flow charts.)
Abnormality of other All off
indoor unit P.C.
board.
Indicated
when detected
abnormal
Replace P.C. borad.
Cable
connection/
Thermal
fuse
Refrigerant
system
1) Wrong wiring or All off
disconnection of
connective cable.
2) Terminal fuse cut
off.
Indicated
when detected
abnormal
1.Check connective
cable correct if wiring is
wrong.
2.Check thermal fuse
and Terminal blocks.
3.If it is OK, check
P.C. board.
Other parts
(including
compressor)
1) Overload relay or All off
thermostat for
compressor
break.
Indicated
when detected
abnormal
1.If overload relay and
themostat for compressor are OK, check
refrigerant cycle.
2.If refrigerant cycle is
OK, check P.C. board.
3. If heat exchanger
sensor is OK, check
overload relay and
themostat for
compressor.
Content detected by the check codes "
" t o " " are stored in memory of the microcomputer even if the
power supply is turned off. Therefore, contents of operations in the past are all displayed.
– 47 −
FILE NO. SVM-06027
9-5. Troubleshooting Flowcharts
9-5-1. Power can not be turned on (No operation at all)
<Preliminary checks>
Operation
(1) Is the supply voltage normal?
(2) Is the connection to the AC output OK.?
Check Items
Heat pump Model
Main cause
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
Countermeasure
Symptom
NO
Does the OPERATION
lamp blink?
YES
Does the power turn on
by pushing the [ ]
button of the remote
control?
Does the transmission
indicator of remote
control flash normally
and transmit certainly?
NO
YES
NO
YES
(No problem)
Does the fuse
(F01) blow?
Remote control is
defective.
YES
Parts (R21, R22, SG01,
C01, DB01, C02, C63,
M01) are defective.
YES
Wrong wiring of
AC cord or connecting
cable is defective.
Replace the remote
control.
NO
Does the thermal
fuse blow?
(Under PF. Terminal)
Replace the
thermal fuse set.
Check connection.
NO
NO
Is the indication voltage
(DC12V or 5V) of main
P.C. board correct?
YES
Does the CN14
connector the wrong
connecting?
Is the voltage
Refer to the paragraph
NO
across C63 measured
"Pre-check", or defective circuit
DC310V ~ 340V?
before power P.C. board block.
NO
P.C. board is
defective.
Replace the main
P.C. board.
YES
Re-wiring the cable.
YES
Is the voltage
across C66
measured DC12V?
YES
NO
Shut off the power
supply once, and
disconnecting the motor
connector CN11*.
Check Resistance
of Pin 1 and 3
of Fan-motor
= 162Ω .
NO
Replace Fan-motor
and P.C. board.
YES
Replace P.C. board
* Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of damage of the motor.
− 48−
FILE NO. SVM-06027
Cooling Model
Operation
Check Items
Main cause
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
Countermeasure
Symptom
NO
Does the OPERATION
lamp blink?
YES
Does the power turn on
by pushing the [ ]
button of the remote
control?
Does the transmission
indicator of remote
control flash normally
and transmit certainly?
NO
YES
NO
YES
(No problem)
Does the fuse
(F01) blow?
Remote control is
defective.
YES
Parts (R21, R22, SG01,
C15, C01, DB01, C50,
TT-10) are defective.
YES
Wrong wiring of
AC cord or connecting
cable is defective.
Replace the remote
control.
NO
Does the thermal
fuse blow?
(Under PF. Terminal)
Replace the
thermal fuse set.
Check connection.
NO
NO
Is the indication voltage
(DC12V or 5V) of main
P.C. board correct?
YES
Does the CN14
connector the wrong
connecting?
Is the voltage
Refer to the paragraph
NO
across C50 measured
"Pre-check", or defective circuit
DC12V ~ 15V?
before power P.C. board block.
NO
P.C. board is
defective.
Replace the main
P.C. board.
YES
Re-wiring the cable.
YES
Is the secondary
voltage of
transformer (TT-10)
measured DC10~16V?
YES
NO
Shut off the power
supply once, and turn
it on again after
disconnecting the motor
connector CN10*.
Is the secondary
voltage of
transformer
measured DC10~16V,?
NO
transformer (TT-10)
for power supply is
defective.
Replace the main
P.C. board.
YES
Motor is defective.
* Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of damage of the motor.
– 49 −
FILE NO. SVM-06027
9-5-2. Power can not be turned on after replacing indoor P.C. board
<Checking Procedure>
Connect the AC
Power supply
NO
Does the OPERATION
lamp blink?
YES
Is it wired as shown
in Figure below?
Return the wiring of the
power relay is returned to
the normal procedure.
NO
YES
To the paragraph of
"No Power turns on".
Heat pump Model
Brown
L
Blue
N
Green & Yellow
Indoor Terminal Block
RY01
1
2
3
Green & yellow
Blue
White
Red
Black
CN31
T02
4
PC Board
– 50 −
FILE NO. SVM-06027
Cooling Model
Black
White
Green / Yellow
1 2
Indooe Terminal Block
RY01
CN31
Brown
Blue
Green / Yellow
L
N
PC Board
9-5-3. Outdoor unit does not operate
Shut off the power supply
from AC outlet once and turn
it on after 5 seconds.
Does the OPERATION lamp blink?
NO
See "Power can not be turned on".
YES
Does the power turn on by pushing
the [ ] button of the remote control?
NO
See "Power can not be turned on".
YES
Is AC 220-240V supplied between
terminal block 1 - 2 ?
NO
Relays (RY01) or (IC31 : Cooling only model,
Q16 : Heat pump only model)or IC30 is failure.
NO
Correct cabling between indoor
and outdoor units.
YES
Is cable connection between indoor
and outdoor units correct?
YES
Check items as following procedure
in 9-5-4, 9-5-5, 9-5-6
– 51−
Replace the
P.C. board.
FILE NO. SVM-06027
9-5-4. Only compressor does not operate
Shut off the power supply
from AC outlet once and turn
it on after 5 seconds.
Does the OPERATION lamp blink?
NO
See "Power can not be turned on".
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
NO
See "Power can not be turned on".
YES
Is the voltage across the indoor terminal
( 1 - 2 ) AC 220-240V?
NO
Relays (RY01) or IC31
or IC30 is failure.
NO
Correct cabling between indoor
and outdoor units.
NO
Cables between indoor and
outdoor units are defective.
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the outdoor terminal
( 1 - 2 ) AC 220-240V?
YES
Are all the cords for compressor normal?
NO
Re-wire or replace the defective cords.
YES
Is the compressor motor winding normal?
(Check the winding resistor.)
NO
Compressor is defective.
YES
Is the capacitor for compressor normal.
NO
Capacitor is defective.
YES
Is the overload relay normal?
NO
Overload relay is defective.
YES
Does the compressor start?
NO
Compressor is defective.
YES
Compressor starts but
it stops after a while?
YES
Is the gas quantity normal?
(Check the pressure)
NO
Gas shortage (Gas leakage)
YES
Compressor is defective
− 52 −
Replace the
P.C. board.
FILE NO. SVM-06027
9-5-5. Only outdoor fan does not operate
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
Does the OPERATION lamp blink?
NO
See "Power can not be turned on".
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
NO
See "Power can not be turned on".
YES
Is the voltage across the indoor terminal
( 2 - 4 : Heat pump model, 1 - 2 :
Cooling only model) AC 220-240V?
NO
Relays (RY03) or IC31
or IC30 is failure.
NO
Correct cabling between indoor
and outdoor units.
NO
Cables between indoor
and outdoor units are defective.
NO
Correct the wire or
replace the defective cords.
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the terminal
( 2 - 4 : Heat pump model, 1 - 2 :
Cooling only model) AC 220-240V?
YES
Are all the cords for outdoor
fan motor normal?
YES
Is the outdoor fan motor winding normal?
(Check the winding resistance)
NO
Outdoor fan motor is defective.
YES
Is the capacitor for compressor normal?
YES
NO
Capacitor for outdoor
fan motor is defective.
Outdoor fan motor is defective.
− 53 −
Replace the
P.C. board.
FILE NO. SVM-06027
9-5-6. Only 4-Way valve does not operate (During heating operation)
Heat Pump Model
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
Does the OPERATION lamp blink?
NO
See "Power can not be turned on".
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
NO
See "Power can not be turned on".
YES
Is the voltage across the indoor terminal
( 2 - 3 ) 220-240V?
NO
Relays (RY04) or IC31
or IC30 is failure.
NO
Correct cabling between indoor
and outdoor units.
NO
Cables between indoor
and outddor units are defective.
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the outdoor terminal
( 2 - 3 ) 220-240V?
YES
Is the wiring of solenoid coil for
4-way valve normal?
NO
Solenoid coil is defective.
YES
4-way valve is defective.
− 54 −
Replace the P.C.
board.
FILE NO. SVM-06027
9-5-7. Only the indoor fan does not operate
<Check procedure>
Heat Pump Model
Shut off the
power supply once.
Turn the power supply.
Does the fan stop in
no operating status?
NO
Replace the P.C. board.
Control P.C. board is defective.
YES
Start the operation
with low fan setting
in cool operation.
Does the fan rotate?
NO
YES
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
Does connecting
terminal, connecting
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
NO
YES
YES
Shut off the power supply.
Change the setting of
cooling to high fan.
Does the cross flow
fan rotate normally?
NO
NO
YES
Repair the
bearing of
the fan.
Thermal fuse operated
due to prevent
temperature rising cause
of incompleted connecting.
Turn on the power supply.
Does the fan speed
become higher?
NO
Motor control circuit failure
(IC30, IC03, D38, R25, R26, Q17)
or 12V power circuit failure.
Operation
stops
YES
Replace the P.C. board.
Is the rotation signal (DC+5V-0V)
output between 2 (gray lead wire)
and 3 (brown lead wire) of the motor
connector (CN11) when rotating
the cross flow fan by hand in no
operating status?
(1 pulse/one turn)
NO
Replace the fan motor
YES
Normal
Replace connecting
the cable (or power cord),
thermal fuse and
terminal block.
Replace the control
P.C. board.
− 55 −
FILE NO. SVM-06027
Cooling Model
Shut off the
power supply once.
Turn the power supply.
Does the fan stop in
no operating status?
NO
Replace the P.C. board.
Control P.C. board is defective.
YES
Start the operation
with low fan setting
in cool operation.
Does the fan rotate?
NO
YES
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
Does connecting
terminal, connecting
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
NO
YES
YES
Shut off the power supply.
Change the setting of
cooling to hight fan.
Does the cross flow
fan rotate normally?
NO
NO
YES
Repair the
bearing of
the fan.
Thermal fuse operated
due to prevent
temperature rising cause
of incompleted connecting.
Turn on the power supply.
Does the fan speed
become higher?
NO
Motor control circuit failure
(IC30, IC03, IC31, TT-10) or 12V
power circuit failire.
Operation
stops
YES
Replace the P.C. board.
Is the rotation signal (DC+5V-0V)
output between 2 (gray lead wire)
and 3 (brown lead wire) of the motor
connector (CN11) when rotating
the cross flow fan by hand in no
operating status?
(1 pulse/one turn)
NO
Replace the fan motor
YES
Normal
Replace connecting
the cable (or power cord),
thermal fuse and
terminal block.
Replace the control
P.C. board.
− 56 −
FILE NO. SVM-06027
9-6. Troubleshooting for Remote Control (Including the Indoor P.C. Board)
Push the [
There is no been from
the indoor unit.
The operation lamp of
the air conditioner main
unit does not light.
] button.
Does the transmission
indicator blink?
NO
YES
Is there direct
sunlight on the
receptor of the air
conditioner?
Reset the remote control
by use the tip pencil push
in the RESET hole
NO
YES
Is there any
thyristor
fluorescent light
near by?
NO
Is operation
possible when the
transmitter is moved
nearer to the infrared
signal receiver of the
air conditioner?
NO
YES
Push the [
button
YES
]
Battery life
NO
Dose the
transmission
indicator light?
Is operation possible
when setting the
temporary switch of the
air conditioner main unit
to "TEST RUN" or
"TEMPORARY AUTO"?
NO
YES
NO
YES
Is there any
beep and
operation?
YES
Can any signal tone
be heard in a trasistor
radio when transmitting
within 5 cm distance
from the radio?
NO
YES
Remote control
is failure.
P.C. board is failure.
Avoid direct
sunlight.
Keep the air
conditioner away
from thyristor
fluorescent light.
Replace
P.C. board
Replace the
batteries
− 57 −
Normal
Replace remote
control.
FILE NO. SVM-06027
(2) Inspection procedres
1) When a P.C. board is judged to be defective,
(1) Operating precautions
check for disconnection, burning, or discolora1) When removing the front panel or the P.C. board,
tion of the copper foil pattern or this P.C. board.
be sure to shut off the power supply.
2)
The
P.C. board consists of the following 2 parts
2) When removing the P.C. board, hold the edge of
a.
Main
P.C. board part:
the P.C. board and do not apply force to the
power
relay, indoor fan motor drive circuit and
parts.
control
circuit, C.P.U. and peripheral circuits,
3) When connecting or disconnecting the connecbuzzer
drive
circuit and buzzer.
tors on the P.C. board, hold the Whole housing.
b.
Infrared
rays
receive and indication parts:
Do not pull at the lead wire.
Infrared rays receiver unit and LED.
9-6-1 How to check the P.C. board
− 58 −
FILE NO. SVM-06027
10. PART REPLACEMENT
10-1. Indoor Unit
No.
1
Part name
Front panel
Procedures
How to remove the front panel
1) Stop the operation of the air conditioner and
turn off its main power supply.
2) Pull the air inlet grille toward you to open it
and remove the air inlet grille.
Then remove the 4 screws fixing the front
panel.
3) First open the horizontal louver, and then
remove the front panel from the back body
by pulling it toward you.
Remarks
2
2
2
2 4-Screws
3
How to mount the front panel
Push the front panel back in and make sure
all hooks are locked.
2
Electrical part
How to remove the electrical part.
1) Remove the front panel with procedure 1 .
2) Remove the screw holding the electrical part
cover.
3) Disconnect the 2 connectors (3P) for the fan
motor and the connector (5P) for the louver
motor from the P.C. board assembly.
4) Pull out the TC sensor from the sensor
holder.
5) Remove the screw for the ground connection,
remove the 2 screws for the electrical part
box and remove the screw from the LED unit.
Then remove the LED unit and the electrical
part box from the main unit.
How to mount the electrical part.
1) To put back the electrical part box, lock it to
the upper hook of the back body.
2) Tighten the screws on the electrical part box.
3) Connect the 3 connectors and arrange the
wiring same as original condition and then
tighten the screw from the LED unit to the
back body.
4) Attach the TC sensor to the holder.
5) Tighten the screw for the ground connection.
6) Assemble the drain guide (the TC sensor wire
should be covered by the drain guide).
7) Tighten the screw on the electrical part cover.
3
Horizontal
louver
1) Remove the front panel and the electrical
part following procedure 2.
2) Remove the center shaft of the horizontal
louver from the back body.
3) Remove the left shaft from the back body.
4) Remove the horizontal louver from the back
body.
− 59 −
2 Scr e w s
4 TC Sensor
5 Scr e w
3
3-Connectors
6 Screw
3 Left shaft
2 Center shaft
FILE NO. SVM-06027
No.
Part name
Procedures
4
Heat exchanger
1) Remove the front panel, electrical part and
the horizontal louver following procedure 3.
2) Remove the pipe holder at the rear side of
main unit.
3) Remove the 2 screws on the heat exchanger
at the base bearing.
4) Remove the 2 screws on the heat exchanger
at the 2 fixed plates (upper and lower) from
the back body, and then pull out the upper
side of the heat exchanger slowly.
Remarks
2 Pipe holder
3
2-Screws
4
2-Screws
5
Cross flow fan
1) Remove the front panel, electrical part,
horizontal louver and the heat exchanger
following procedure 4.
2) Remove the 2 screws on the band motor (L)
and remove the 2 screws on the band motor
(R) and then remove the cross flow fan.
3) Loosen the set screw of the cross flow fan
then separate the fan and the fan motor.
2
2-Screws
(R)
2 2-Screws (L)
6 mm
Notice
To assemble cross flow fan and fan motor to the
unit, please turn the fan motor unit the center of
its terminal meets the lowest point of band motor
(R) (point A).
Fix the cross flow fan with the set screw at the
position where the gap between the back body
and the right surface of the cross flow fan is
6 mm.
6
Base bearing
1) Remove the front panel, electrical part,
horizontal louver, heat exchanger and the
cross flow fan following procedure 5.
2) Remove the 2 screws fixing the base bearing.
3) Remove the bearing from the base bearing. If
the housing protrudes from the base bearing,
put the housing in position and attach the
bearing to the base bearing.
− 60 −
6 Set screw
Middle of the fan motor terminal
2
2-Screws
FILE NO. SVM-06027
10-2. Outdoor Unit
No.
1
Part name
Common
procedure
Procedures
1) Stop the operation of air-conditioner, and
disconnect the power cord from the AC
supply.
2) Remove packed valve cover and Electric
parts cover.
(2-Screws ∅4 x 10L)
3) Remove the cord clamp (2-Screws ∅4 x 16L)
and disconnect the connecting cable.
4) Remove the upper cabinet (5-Screws ∅4 x 10L)
Pulling out upword.
5) Remove the front cabinet.
(3-Screws ∅4 x 10L)
Pull the front right portion toward you, and
remove it pulling out upward.
Remarks
Cord clamp
2-Screws Ø4 x 16L
2-Screws Ø4 x10L
Packed valve cover
Upper
cabinet
Front
cabinet
2
3
Capacitor for
compressor
Capacitor for
fan motor
1) Perform the common procedure 1.
2) Remove the fixing screw and the capacitor
band.
(1-Screw ∅4 x 10L)
3) Disconnect the lead wires.
Screws
∅4 x 10L
Capacitor band
Capacitor
for
compressor
1) Perform the common procedure 1.
2) Remove the fixing screw and the capacitor
band.
(1-Screw ∅4 x 10L)
3) Disconnect the lead wires.
Screws
Ø4 x10L
Capacitor for fan motor
– 61 –
FILE NO. SVM-06027
11. EXPLODED VIEWS AND PARTS LIST
11-1. Indoor Unit (E-Parts Assy)
(RAS-13GKHP-ES2)
Location
No.
Part
No.
401
402
403
404
43T60001
43T60002
43T69004
43T69005
Description
TERMINAL
TERMINAL BLOCK; 3P
SENSOR;HEAT EXCHANGER
SENSOR;THERMOSTAT
− 62 −
Location
No.
Part
No.
405
406
410
411
43T69079
43T60077
43T62003
43T69568
Description
PC BOARD ASSY;WRS-LED
FUSE, TEMPERATURE, 73C
CORD CLAMP
PC BORD
FILE NO. SVM-06027
11-2.
Indoor Unit (E-Parts Assy)
(RAS-13NKHP-AS2)
Location
No.
Part
No.
401
402
403
404
43T60001
43T60002
43T69004
43T69005
Description
TERMINAL
TERMINAL BLOCK; 3P
SENSOR;HEAT EXCHANGER
SENSOR;THERMOSTAT
− 63 −
Location
No.
Part
No.
405
406
407
410
411
43T69079
43T69364
43T60371
43T62003
43T69432
Description
PC BOARD ASSY;WRS-LED
FUSE,TEMPERATURE
POWER CORD (AS)
CORD CLAMP
PC BOARD
FILE NO. SVM-06027
11-3.
Indoor Unit (E-Parts Assy)
(RAS-13GKP-ES2)
Location
No.
Part
No.
402
403
404
405
43T60002
43T69004
43T69005
43T69079
Description
TERMINAL BLOCK; 3P
SENSOR;HEAT EXCHANGER
SENSOR;THERMOSTAT
PC BOARD ASSY;WRS-LED
− 64 −
Location
No.
Part
No.
406
410
411
412
43T60077
43T62003
43T69567
43T69361
Description
FUSE, TEMPERATURE, 73C
CORD CLAMP
PC BORD
TRANSFORMER(TT-10)
FILE NO. SVM-06027
11-4.
Indoor Unit (E-Parts Assy)
(RAS-13NKP-AS2)
Location
No.
Part
No.
402
403
404
405
406
43T60002
43T69004
43T69005
43T69079
43T69364
Description
TERMINAL BLOCK; 3P
SENSOR;HEAT EXCHANGER
SENSOR;THERMOSTAT
PC BOARD ASSY;WRS-LED
FUSE,TEMPERATURE
− 65 −
Location
No.
Part
No.
407
407
410
411
412
43T60374
43T60374
43T62003
43T69367
43T69361
Description
POWER CORD (AS)
POWER CORD (AS)
CORD CLAMP
PC BOARD
TRANSFORMER(TT-10)
FILE NO. SVM-06027
11-5. Indoor Unit
Location
No.
Part
No.
201
43T00435
201
43T00430
202
203
204
205
206
207
208
209
210
43T09387
43T03341
43T80311
43T80310
43T09328
43T70310
43T79301
43T21372
43T44384
210
43T44385
211
212
213
214
215
43T47352
43T47353
43T49330
43T11302
43T19302
Description
Location
No.
Part
No.
216
217
218
219
220
221
222
223
224
43T49331
43T49006
43T22308
43T39301
43T20321
43T39302
43T21322
43T39303
43T69421
224
43T69422 WIRELESS-REMOCO
225
226
227
228
229
230
43T83003
43T62302
43T60317
43T07303
43T82310
43T60359
FRONT PANEL ASSY
(RAS-13GKHP-ES2,RAS-13NKHP-AS2)
FRONT PANEL ASSY
(RAS-13GKP-ES2,RAS-13NKP-AS2)
INLET GRILLE ASSY
BACK BODY ASSY
AIR-FILTER(R)
AIR FILTER (L)
HORIZONTAL LOUVER
DRAIN-HOSE
CAP-DRAIN
MOTOR; STEPPING
REFRIGERATION CYCLE ASSY
(RAS-13GKHP-ES2,RAS-13NKHP-AS2)
REFRIGERATION CYCLE ASSY
(RAS-13GKP-ES2,RAS-13NKP-AS2)
PIPE; DELIVERY
PIPE; SUCTION
SPRING
PIPE-SHIELD
HOLDER SENSOR
− 66 −
Description
PLATE OF EVA SEAL
HOLDER FOR PLATE
ASM-M-BEARING
BASE; BEARING
ASSY-CROSS FLOW FAN
BAND MOTOR-L
MOTOR; FAN
BAND MOTOR-R
WIRELESS-REMOCO
(RAS-13GKHP-ES2,RAS-13NKHP-AS2)
(RAS-13GKP-ES2,RAS-13NKP-AS2)
HOLDER; REMOTE CONTROLLER
TERMINAL COVER
CORD MOTOR LOUVER
HOLDER PIPE
PLATE; INSTALLATION(For 43T82301)
CORD-FM
FILE NO. SVM-06027
11-6. Outdoor Unit (RAS-13GAH-ES2, RAS-13N2AH-AS2)
Location
No.
Part
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
43T42328
43T41380
43T49008
43T97307
43T43383
43T00448
43T46332
43T46335
43T47331
43T47333
43T47008
43T00468
43T00459
43T00451
43T21362
43T20319
43T47001
43T19329
Description
BASE PLATE ASSEMBLY
COMPRESSOR(Made in China)
CUSHION,RUBBER
COMPRESSOR BOLT (M6)
CONDENSER ASSEMBLY
FIXING PLATE VALVE
VALVE;PACKED 6.35 DIA
VALVE;PACKED 12.7 DIA (H4)
BONNET, 6.35 DIA
BONNET, 12.70 DIA
CAPILLARY TUBE; 1.5 DIA
FRONT CABINET
LEFT CABINET
RIGHT CABINET ASSEMBLY
FAN MOTOR(Made in China)
PROPELLER FAN
NUT FLANGE
FAN GUARD
− 67 −
Location
No.
Part
No.
Description
19
20
21
22
23
24
25
26
28
29
30
31
32
33
34
35
43T04301
43T39322
43T39318
43T19330
43T00460
43T96305
43T62325
43T19331
43T61308
43T55339
43T55325
43T60373
43T46337
43T46339
43T79305
43T47308
PARTITION
MOTOR BASE CONNECTION PLATE
MOTOR BASE
PACKED VALVE COVER
UPPER CABINER ASSEMBLY
BUSHING
ELECTRIC PART COVER
FIN GUARD
ELECTRIC PARTS BASE
CAPACITOR,PLASTIC FILM
CAPACITOR; PLASTIC-FILM
TERMINAL-4P
4 WAY VALVE
COIL;V-4WAY;AC220-240V 50Hz
DRAIN NIPPLE
CAPILLARY TUBE; 1.0 DIA
FILE NO. SVM-06027
11-7. Outdoor Unit (RAS-13GA-ES2, RAS-13N2A-AS2)
Location
No.
Part
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
43T42328
43T41380
43T49008
43T97307
43T43382
43T00448
43T46332
43T46335
43T47331
43T47333
43T47014
43T00468
43T00459
43T00451
43T21361
Description
BASE PLATE ASSEMBLY
COMPRESSOR(Made in China)
CUSHION,RUBBER
COMPRESSOR BOLT (M6)
CONDENSER ASSEMBLY
FIXING PLATE VALVE
VALVE;PACKED 6.35 DIA
VALVE;PACKED 12.7 DIA (H4)
BONNET, 6.35 DIA
BONNET, 12.70 DIA
CAPILLARY TUBE; 1.7DIA
FRONT CABINET
LEFT CABINET
RIGHT CABINET ASSEMBLY
FAN-MOTOR
− 68 −
Location
No.
Part
No.
16
17
18
19
20
43T20319
43T47001
43T19329
43T04301
43T39322
PROPELLER FAN
NUT FLANGE
FAN GUARD
PARTITION
MOTOR BASE
21
22
23
24
25
26
28
29
30
31
43T39318
43T19330
43T00460
43T96305
43T62325
43T19331
43T61308
43T55339
43T55325
43T60367
MOTOR BASE
PACKED VALVE COVER
UPPER CABINER ASSEMBLY
BUSHING
ELECTRIC PART COVER
FIN GUARD
ELECTRIC PARTS BASE
CAPACITOR,PLASTIC FILM
CAPACITOR; PLASTIC-FILM
TERMINAL-2P
Description
CONNECTION PLATE
FILE NO. SVM-03001(1)
TOSHIBA CARRIER (THAILAND) CO.,LTD.
144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI,
AMPHUR MUANG, PATHUMTHANI 12000,THAILAND.
– 72 –