Download Mechanical Specification
Transcript
Baycrest Centre for Geriatric Care Apotex Building 5th Floor HHA #2151048-01 Section 23 31 13 Ductwork Page 5 of 18 Table 2: Duct System Pressure and Seal Class No. 7 Ductwork System Supply air ductwork from discharge side of fan to inlet of terminal box or reheat coil; Static pressure construction class Pa (in.wg.) Seal class Sealing requirements (1)(2)(3)(4) +750 (3) Return air ductwork on discharge side of fan. 8 Return/Exhaust risers in mechanical rooms and vertical service spaces (duct shafts). -750 (3) 9 Supply air ductwork upstream of HEPA filters, including diffusers with integral HEPA filters.(5) +750 (3) 10 Return and/or exhaust air ductwork on suction side of fans other than in mechanical rooms and vertical service spaces. -500 (2) C Transverse joints and other connections 11 Supply air ductwork on downstream side of terminal units or reheat coil; 250 (1) C Transverse joints only 125 (½) D No sealing Exhaust air ductwork on discharge side of fan; Fan coil units, suction and discharge. 12 Supply air and return air ductwork from roof top air conditioning units, 5 tons or less Notes for table 2: (1) Transverse joints are connections of two duct or fitting elements oriented perpendicular to flow, (2) Longitudinal seams are joints oriented in direction of flow, (3) Duct wall penetrations are openings made by screws, non-self-sealing fasteners, pipe, tubing, rod and wire, (4) Other connections such as spin-ins taps and other branch fittings inserted into cut openings in duct, access door frames, insertion type control elements and duct joints at equipment are to be treated as transverse joints. (5) This pressure class also applies to supply ductwork downstream of a terminal box or reheat coil which serve diffusers with integral HEPA filters. 3.3 Fittings - Rectangular Ductwork .1 Refer to Annex A at the end of this Section for illustrations of referenced fitting types. .2 Elbows: .1 Elbows are to be installed as shown, or if not shown, in descending order as listed in table 3. (a) for clarity, elbows types are to be selected based on the highest order number (where 1 is the highest) which will fit the available space. Table 3: Rectangular Duct, Elbows Issued For Tender