6 Electrical Connection SMA Solar Technology AG 6. Damage to the inverter due to moisture ingress The inverter is only properly sealed when all unused DC inputs are closed with DC connectors and sealing plugs. • Do not insert the sealing plugs directly into the DC inputs on the inverter. • For unused DC connectors, push down the clamping bracket and push the swivel nut up to the thread. • Insert the sealing plug into the DC connector. • Tighten the DC connector (torque: 2 Nm). • Insert the DC connectors with sealing plugs into the corresponding DC inputs on the inverter. ☑ The DC connectors snap audibly into place. 7. Ensure that all DC connectors are securely in place. 30 STP20-25TL-BE-en-11 Operating Manual