Service Manual
308012En, Ed.1/Rev.D
August 2010
Rosemount Tank Radar Rex
Chapter 4 Service
Software configuration
Note!
For further information on how to configure/install the FCU see
TankMaster WinSetup Reference Manual.
1
Power down both FCUs.
2
Power up one of the FCUs.
3
Select the Devices folder in the TankMaster WinSetup workspace window, click the right mouse button and choose the Install New option.
4
Choose device type FCU, specify a name in the Tag input field and click
the Next button to continue.
5
Select a communication channel.
6
Set the FCU address:
1
In the FCU Communication window click the Change Address on
Device button.
2
Enter the Unit ID and the Modbus Address and click the OK button.
3
In the FCU Communication window click the Verify Communication button to make sure that communication is established.
4
Click the Next button to continue.
7
In the FCU Configuration window choose the Redundant, Primary
mode option to set the operation mode.
8
Click the Next button to open the FCU Slave Database window. Configure the FCU.
9
Click the Next button to open the Summary window and then the Finish
button to finish the FCU installation.
Comment:
The standard mode of operation is "normal".
There is no difference in operation between the
FCU designated "primary" and "backup",
respectively. The reason for having different
names is only to be able to distinguish between
the redundant FCUs.
10
Check that holding register 831=7 (only memory tests).
11
Power down the FCU.
4-51