Download Megaflo System installation instructions
Transcript
17.0 Fault Finding Refer to Section 16.0 “Illustrated Wiring Diagram” for position of terminals and components Central Heating - Follow operational sequence Turn selector switch to The display illuminates NO Go to section ‘A’ YES Error 110 flashing Error 130 flashing Error 133 flashing YES Turn the selector switch to reset position for 5 seconds YES If the error 110 is still flashing. Go to section ‘J’ NO Error 20, 28 or 50 flashing YES Go to section ‘E’ NO YES Error 119 flashing Go to section ‘C’ Ensure controls are set to demand and verify the contacts are closed NO NO Turn Central Heating thermostat to Maximum. Pump runs NO Ensure all controls and integral clock are calling for heat YES Go to section ‘B’ YES Error E125 or E193 flashing NO Ensure that primary circulation is OK & that there is no blockage YES 3-way valve is open to Central Heating circuit YES Go to section ‘K’ NO Fan runs NO Error 160 flashing Go to section ‘D’ NO Error 160 flashing Go to section ‘L’ YES Fan runs at correct speed YES Spark at ignition electrodes for up to 5 seconds and for 3 attempts YES NO Error 133 flashing YES Go to section ‘H’ Turn the selector switch to reset Go to section ‘F’ NO YES Burner lights Burner does not stay alights after 5 seconds YES Error 133 flashing Go to section ‘I’ YES Pump continues to run for 3 minutes (room thermostat open) Check the Central Heating NTC sensor Go to section ‘E’ YES NO Burner output modulates to maintain the temperature set Error 130 flashing Go to section ‘M’ YES Burner goes out 44 © Baxi Heating UK Ltd 2015 YES Fan stops after 10 seconds YES Operation sequence successful