8.0 Flue Options
8.1
Horizontal Flue Systems
1. The standard flue is suitable only for horizontal termination
applications.
(ii)
(i)
2. All fittings should be fully engaged. The approximate
engagement is 40mm. Apply soap solution to the seal on
each fitting to aid assembly.
3. Maximum permissible equivalent flue lengths are:(60/100)
(80/125)
Horizontal Concentric 10 metres
20 metres
4. Any additional “in line” bends in the flue system must be
taken into consideration.
Their equivalent lengths are:Concentric Pipes:
135° bend
0.5 metres
93° bend
1.0 metres
Twin Flue Pipe
135° bend
0.25 metres
91.5° bend
0.50 metres
Horizontal
Flues
4. The elbow connected to the boiler adaptor is not included
in any equivalent length calculations.
Plume Displacement Kit 60 /100 Ø
5. The illustrations opposite show examples of permissible
flue systems.
1M Extensions, 45° & 93° bends are
also available - see Section 9.0
NOTE: Flue length is measured from point (i) to (ii) as
shown.
IMPORTANT: All flue systems must be securely
supported at least once every metre. Suitable pipe
supports are available as accessories.
NOTE: Horizontal flue pipes should always be installed with a fall of at least 1.5°
from the terminal to allow condensate to run back to the boiler.
This bend is equivalent to
1 metre
C
A
(ii)
B
(i)
This bend is equivalent to
1 metre
Total equivalent length =
A+B+C+2x90°Bends
20