DOOR CONNECTIONS
Magnetic Stripe Reader Connection
Magnetic Stripe Reader Cable Requirements
Magnetic Stripe Readers connect to terminal strips DR1
through DR8 (see Figure 11). Terminal strips DR1 through
DR8 follow the same connection procedures.
Magnetic Stripe Readers require a 5-conductor cable between
the Turbo Superterm and the particular unit (see Figure 11).
Table 8 lists the connections between the DR1 through DR8
terminal strips and the Magnetic Stripe Reader.
Table 8 - Connection Table for Magnetic Stripe Reader
DRx Terminal Strip Pin #
Function
1
4
5
6
7
NOTE: DO NOT use twisted pair cables.
If the Magnetic Stripe Reader does not feature an LED indicator, substitute with a 4-conductor cable.
Table 9 lists the cable gauge-vs-length requirements for proper
operation of the Turbo Superterm and Magnetic Stripe Readers.
+5VDC
Ground
LED
Data-1/DAT
Data-0/CLK
Table 9 - Cable Requirements for Magnetic Stripe Reader
Unit
Distance
Wire Gauge
Magnetic
(maximum)
22AWG
Stripe
500ft/153m
Shielded w/drain
Reader
CAUTION
Keep all drain and cable shield wires between the Turbo Superterm and Magnetic Stripe Readers short. Connect drain and cable shield wires to the ground posts located on both sides of Turbo Superterm cabinet. DO
NOT ground drain wires and cable shields at any other point.
Note: Please refer to reader manufacturer for specific instructions and specifications.
Turbo Superterm
Cabinet Ground Post
Turbo Superterm Circuit Board
Figure 11 - Magnetic Stripe Reader Connection to Turbo Superterm Board
Turbo Superterm P1800 v1.2
22