Download optional - Axor Industries
Transcript
2.6 Note about cable shielding Control signal cables The conductor of the analogic signal must be twisted and shielded, and the shield must be connected to ground as illustrated below: Remove the outside sheath and affix the shield to the dedicated retainer rings, by using plastic clamps. Note: • To reduce the capacitive and inductive coupling, these cables must be run keeping a distance of more than 30cm from the power cables (10 cm if they are shielded). • If it is absolutely necessary to cross the control cables with the I/O's, do so at 90°, in order to reduce the effect of the magnetic fields. Motor cables The shield of the motor cable (power and signal cables) are connected as follows: • drive side (20:50cm) remove the outside sheath and fix shield to the zinced pannel, by using a u-clamp: • motor side The shield is internally connected to the metal ring of the motor connector, thus to earth through the motor's carcass. AXOR Industries Service Manual MiniMagnumTM ver.1 rev. 01/'09 21