Converter MIN 0 - 250 x 10
0
F.16
Converter MAX 1 - 250 x 10
20
F.17
Master
Controller Modbus master/slave address 0:
1 - 247: Slave
0: 1200
1: 2400
2: 4800
9600
Modbus data transfer rate 3:
4: 19200
5: 38400
6: 57600
7: 115200
F.18
0: None
Modbus parity 1: Even
2: Odd
F.19
F.20
F.21
Controlled device
(Remote controller will automatically recognize the PRV and ECO plates)
0: None
1: Custom
2: ECO
3: PRV
Modbus address of controlled device 1 - 247
0
4
0
0
1
F.22
SET Temperature address 00:00 - FF:FF
00:00
F.23
SET Fan speed (%) address 00:00 - FF:FF
00:00
F.24
SET Fan speed fixed address 00:00 - FF:FF
00:00
F.25
SET Pressure address 00:00 - FF:FF
00:00
F.26
SET CO2 address 00:00 - FF:FF
00:00
F.27
Temperature address 00:00 - FF:FF
00:00
F.28
Alarm 1 address 00:00 - FF:FF
00:00
F.29
Alarm 2 address 00:00 - FF:FF
00:00
F.30
Alarm 3 address 00:00 - FF:FF
00:00
F.31
Alarm 4 address 00:00 - FF:FF
00:00
F.32
Alarm 5 address 00:00 - FF:FF
00:00
F.33
Alarm 6 address 00:00 - FF:FF
00:00
F.34
Alarm 7 address 00:00 - FF:FF
00:00
F.35
Alarm 8 address 00:00 - FF:FF
00:00
F.36
Alarm 9 address 00:00 - FF:FF
00:00
F.37
Alarm 10 address 00:00 - FF:FF
00:00
F.38
No
Restore controller factory settings 0:
1: Yes
0
F.39
Modbus (Holding register) type parameter
0 - 999
reading and changing tool
0
F.40
Modbus (Coil register) type parameter read0 - 999
ing and changing tool
0
Control panel version -
F.41
F.42
-
Fan’s controlled by 0..10 VDC signal start
0 - 120
delay time in seconds
0
0: OFF
1: ON
0
F.43
0..10 VDC ON/OFF
Stouch
EN
F.15
To restore factory settings, service password “022” should be reentered.