Download BA 24 B 24 B 28
Transcript
3.12 - ADJUSTING THE BURNER Attention, during these operations do not take any samples in domestic hot water mode. All boilers leave the factory already calibrated and tested, however in the event the gas valve recalibration is required: - Loosen the needle screw ‘’P’’ located inside the pressure socket at gas valve outlet and connect a pressure gauge with reference to the figure. - Check the supply pressure value (see NOZZLES - PRESSURES table). The following instructions are intended exclusively for authorised service personnel. 1) Maximum output adjustment 2) Minimum output adjustment - Operate the boiler in “calibration” mode at MAXIMUM OUTPUT (see 3.11.1). - Once the burner is on check that the “MAXIMUM” pressure value corresponds to that indicated in the table “NOZZLES - PRESSURE”. - Should it not correspond, correct it by removing the screw cap ‘’Q’’ and turning screw “S” below CLOCKWISE to increase it, ANTICLOCKWISE to decrease it. - Operate the boiler in “calibration” mode at MINIMUM OUTPUT (see 3.11.1) - Once the burner is on, check that the “MINIMUM” pressure value corresponds to that indicated in the table “NOZZLES - PRESSURE”. - Correct it if needed by turning (with a screwdriver) the screw “R”; CLOCKWISE to increase it, ANTICLOCKWISE to decrease it. Socket pressure OUTPUT INSTALLATION INSTRUCTIONS ENGLISH P 3) Conclusion of the basic calibrations - once the gas valve minimum and maximum pressure values are checked and top-up is required (points 1-2): - disable the timed “calibration” function by switching off the main switch. - Remove the flexible tube from the pressure gauge and close the pressure socket screw again. - Check that there are no gas leaks. 25