Instruction Bulletin
Alternate Maintenance Setting (AMS) Switch
Retain for future use.
Components Required
Table 1:
Components Parts
Part Number
Description
Quantity
S48890
Restraint Interface Module (RIM) 120 Vac/12 Vdc
(Order Separately)
1
9001K11J38LLL
Switch with blue indicator light (order separately)
1
9001KA3
Switch contact block (order separately)
1
9001K7
Padlock attachment (order separately)
1
80298-173-01
AMS nameplate
1
NHA41456
AMS danger label
1
KM3301RR05Q
C & K AMS push button
1
Wiring per the schematic on Page 9
Table 2:
Instruction Bulletins Required
Bulletin
Located At
Circuit breaker installation guide
Shipped with the circuit breaker
Micrologic™ P or H trip unit user guide
M2CTEST Instruction bulletin
Available on the Schneider Electric
internet site
FFTK (Full-Function Test Kit) instruction bulletin
Introduction
Square D™ brand PowerPact L/P/R and Masterpact™ NT/NW circuit breakers,
manufactured by Schneider Electric™, have superior arc-flash protection
characteristics. These circuit breakers feature additional arc flash protection
when a Short-Time Zone Selective Interlocking (ST-ZSI) scheme is used.
When properly applied, the circuit breakers provide reduced arc flash incident
energy (AFIE) without changing settings or temporarily compromising the
system selective coordination. See the circuit breaker catalogs and the
Schnieder Electric internet site for more information on zone-selective
interlocking (ZSI).
For applications where the above solutions are not sufficient, Schneider
Electric has developed a method to temporarily reduce the short-time delay
setting of the circuit breaker using an alternate maintenance setting (AMS)
switch. When AMS is installed, ZSI cannot be applied for short-time on the
same circuit breaker. Either of these solutions (ZSI or AMS) meet the NEC
240.87 requirements for arc flash reduction.
In order to quantify the AFIE reduction, an arc-flash analysis must first be
performed. Values must be calculated for the possible maintenance setting to