Download (AMS) Switch - Schneider Electric
Transcript
NHA40218 01/2015 ENGLISH ENGLISH Instruction Bulletin Alternate Maintenance Setting (AMS) Switch Retain for future use. Components Required Table 1: Components Parts Part Number Description Quantity S48890 Restraint Interface Module (RIM) 120 Vac/12 Vdc (Order Separately) 1 9001K11J38LLL Switch with blue indicator light (order separately) 1 9001KA3 Switch contact block (order separately) 1 9001K7 Padlock attachment (order separately) 1 80298-173-01 AMS nameplate 1 NHA41456 AMS danger label 1 KM3301RR05Q C & K AMS push button 1 Wiring per the schematic on Page 9 Table 2: Instruction Bulletins Required Bulletin Located At Circuit breaker installation guide Shipped with the circuit breaker Micrologic™ P or H trip unit user guide M2CTEST Instruction bulletin Available on the Schneider Electric internet site FFTK (Full-Function Test Kit) instruction bulletin Introduction Square D™ brand PowerPact L/P/R and Masterpact™ NT/NW circuit breakers, manufactured by Schneider Electric™, have superior arc-flash protection characteristics. These circuit breakers feature additional arc flash protection when a Short-Time Zone Selective Interlocking (ST-ZSI) scheme is used. When properly applied, the circuit breakers provide reduced arc flash incident energy (AFIE) without changing settings or temporarily compromising the system selective coordination. See the circuit breaker catalogs and the Schnieder Electric internet site for more information on zone-selective interlocking (ZSI). For applications where the above solutions are not sufficient, Schneider Electric has developed a method to temporarily reduce the short-time delay setting of the circuit breaker using an alternate maintenance setting (AMS) switch. When AMS is installed, ZSI cannot be applied for short-time on the same circuit breaker. Either of these solutions (ZSI or AMS) meet the NEC 240.87 requirements for arc flash reduction. In order to quantify the AFIE reduction, an arc-flash analysis must first be performed. Values must be calculated for the possible maintenance setting to © 2015 Schneider Electric All Rights Reserved ™