fig. 3c
D
L (m)
Italiano
H
(m)
C
Øi 8 mm. Øi 10 mm.
0.0
25
60
0.5
21
50
1.0
18
44
1.5
15
38
2.0
12
32
2.5
10
26
3.0
8
20
3.5
6
16
L
Total length of the inlet pipe, including the vertical
sections
H Difference in height
Øi Internal diameter of pipes
P Auxiliary pump
English
Nota: for each curve or gate valve, add 0.25 metres
to the length of the pipe (pressure drop).
fig. 3d
11
Connection to the pump
6
4
3
Key
Suction
Return with internal by-pass screw
Delivery to nozzle
1st stage pump pressure adjustment
Pressure gauge connections
Vacuum gauge connection
2nd stage pump pressure adjustment
2nd stage coil
1st stage coil
By-pass screw
Nozzle
7
10
2
1
fig 4
Cod. 35445523 - 02/2007 (Rev. 00)
23
Español
1
2
3
4
5
6
7
8
9
10
11
Deutsch
If the pump is operated with the return closed
5
and the bypass screw inserted, it will be damaged immediately.
Français
The burner leaves the factory with the internal pump bypass
closed, that is, the burner is fitted for two-pipe connection.
Remove the caps and connect the two flexible pipes to the
pump inlet (1) and return (2), as shown in Figure 4, making
sure the flexible pipes are not twisted and that they are
positioned so that they will not be stepped on or come into
contact with the hot parts of the boiler.
8
If the internal pump bypass needs to be used for single-pipe
connections, remove the bypass screw (10) and cap the
return fitting (2) on the pump, connecting only the flexible 9
pipe to the inlet fitting (1).