Installation
Water connections
Please refer to the Safety information manual.
- Finally wrap connections with anti-condensate insulation
and tighten with tape, without exerting great pressure the
insulation.
- When all the installation connections are complete, start
water filling.
- When making the hydronic connections to the module,
always use a counter spanner when tightening.
- To avoid bacteria and dirty proliferation in the circuit it is
recommended to use water treatment mixed water.
- Place valves (not included) at the inlet and outlet of the
hydronic module.
- Use pipe 1" or bigger for the connection between the
hydronic module and the floor / fan coil / radiator.
Pump speed selection
The pump provided with the module has 3 speeds.
The installer selects the speed of the module pump in order
to guarantee the target flow rate, knowing the available
pressure of the system at different pump speed (see fig. 23a)
and the pressure drop of the installation.
Hydronid
module
CDU
80AW1
For 80AW2 modules, the installer should also decide the
target flow rate for the zone, depending on the terminal
connected; after that, the installer selects the speed of the
pump knowing the available pressure of the system at
different speeds (see fig. 23b) and the pressure drop of the
installation.
80AWT
80AW2
38AW050
38AW065
38AW090
38AW115
38AW090
38AW115
5,0
6,5
9,0
11,5
9,0
11,5
5
5
5
5
5
5
Nominal
Flow Rate
[lt/h]
860
1118
1548
1978
1548
1978
Min Flow
Rate [lt/h]
688
894
1238
1582
1238
1582
Max Flow
Rate [lt/h]
1032
1342
1858
2374
1858
2374
Nominal
Capacity
[kW]
Nominal DT
[°C]
Refrigerant connections
Please refer to the Safety information manual and the
R-410A- Installation manual.
WARNING:
The installer can rout the copper pipes from CDU to the
hydronic module. However the refrigerant connections
must be done by a skilled fridge installer during the
commissioning.
Before the commissioning the installer must rout the copper
insulated pipe from CDU to the hydronic module, cut it at
the correct length and close it at each side by pinching and
adhesive tape.
Make sure that during the routing, external materials do not
enter in the pipes.
20
38AW050 38AW065 38AW090 38AW115
Max line length
w/o additional
refrigerant [m]
20
20
20
20
Min line lenght
[m]
1
1
1
1
Max height
differential
between ODU/
ID [m]
6
6
6
6
Refrigerant
R410A
(standard<20m)
[g]
1170
1360
2100
2100
80AW1- 80AWT - 80AW2
128H88__0-27_GB.indd Sez2:20
12-10-2009 9:16:48