Download D GB NL E
Transcript
Application B007 Article 682191 2.6 Humidity The humidity sensor senses the relative humidity of the air and the room temperature. Both measuring values are made available in the form of analog voltages. The measuring ranges of the sensor extend from 0 to 100 % of relative humidity and from –30 to +70 °C. For use with the analog input / analog sensor interface, the following parameters are recommended: Parameter Measuring value for 0% of the measuring signal: Measuring value for 100% of the measuring signal: Measuring range factor: Limit value 1: Hysteresis 1: Limit value 2: Hysteresis 2: Setting 0 10000 corresponds to 0 % r. h. 100 % r. h. 0,01 40 % 5% 70 % 5% 40 % r. h. 5 % r. h. 70 % r. h. 5 % r. h. Measuring value for 0% of the measuring signal: Measuring value for 100% of the measuring signal: Measuring range factor: Limit value 1: Hysteresis 1: Limit value 2: Hysteresis 2: –3000 +7000 –30°C +70°C 0,01 50 % 2% 55 % 2% 20 °C 2K 25 °C 2K 2.7 Air pressure For an air pressure sensor with an input range of 70.000 … 120.000 Pa which is converted to 0 … 10 volts, the following parameters are recommended for use with the analog input / analog sensor interface: Parameter Measuring value for 0% of the measuring signal: Measuring value for 100% of the measuring signal: Measuring range factor: Limit value 1: Hysteresis 1: Limit value 2: Hysteresis 2: © 2008 Merten GmbH 18 Setting 7000 12000 corresponds to 700 hPa 1200 hPa 10 60 % 2% 64 % 4% 1000 hPa 10 hPa 1020 hPa 20 hPa