Download Installation Guide
Transcript
Dedicated Circuit 1. Provide Electrical Service CAUTION: Risk of electrical shock. Disconnect the power before proceeding. Refer to the ″Important Safety Instructions″ section. A Ground-Fault Circuit-Interrupter (GFCI) is recommended for this circuit. Local electrical codes may require that electrical work be performed by a licensed electrician. Follow all local electrical codes. Refer to the roughing-in information to determine the proper circuit location. The sink controls and system have been prewired at the factory. Only minor electrical connections are required during installation. The power wiring and terminal box must be provided by the customer. Provide a dedicated 120 V, 15 A, 60 Hz two-wire with ground circuit for the cook sink. Install a junction box in the cabinet in the vicinity of the cook sink’s location. Locate the junction box away from any water or drain piping. Pull wires from the circuit breaker panel board through the junction box to the cook sink area. Terminate the wires at the circuit breaker. Do not apply power until directed to do so. In the cabinet, route and support the cook sink power wiring to protect the wires from contact with any items that may be stored in the cabinet. Flexible watertight conduit is recommended. 1032056-2-B 4 Kohler Co.