Download Installers Guide Guide d`installation
Transcript
Installing the Stove ! Installation (continued) WARNING: THE TERMINATION CAP MUST BE POSITIONED SO THAT THE ARROW IS POINTING UP. ! (suite) AVERTISSEMENT: POSER LA MITRE DE FAÇON À CE QUE LA FLÈCHE SOIT DIRIGÉE VERS LE HAUT. For roundcap termination kits: Kit de mitre ronde: • Use the exterior pipelock hole provided on the round flange of the wall firestop to secure the vent pipe in place. • Utiliser le trou de verrouillage extérieur situé sur la bride ronde du coupe-feu mural pour fixer la conduite. For trapezoidal cap termination kits: ROUND CAP TERMINATION (MITRE RONDE) • Using screws, secure the cap to the exterior wall through the flanges built into the cap. • Use a high-temperature sealant or fiberglass rope gasket to seal between the vent pipe and exterior firestop. Kit de mitre trapézoïdale: HOT (CHAUD) PERFORATION CANNOT BE INSIDE THE WALL (LA PERFORATION NE PEUT PAS SE TROUVER DANS LE MUR) 7 1/2” (191mm) MINIMUM • Visser la mitre sur le mur extérieur par les brides de la mitre. • Obturer l’espace entre la mitre et le coupe-feu extérieur avec un produit d’étanchéité pour hautes températures ou un cordonjoint de fibre de verre. TRAPEZOID CAP TERMINATION (MITRE TRAPEZOIDALE) 7 1/4” (184mm) Figure 19. Round & Trapezoid Termination Caps ! Figure 19. Mitres rondes et trapézoïdales ! WARNING: THE BOTTOM OF THE VENT TERMINATION CAP MUST BE A MINIMUM OF 12 INCHES (305MM) ABOVE GROUND LEVEL (GRADE). THE TOP OF THE CAP MUST BE A MINIMUM OF 18 INCHES (457MM) BELOW COMBUSTIBLE MATERIAL, SUCH AS A DECK, AND THE SIDE OF THE CAP MUST BE A MINIMUM OF 6 INCHES (152MM) AWAY FROM A PARALLEL OUTSIDE WALL. VENTING TERMINALS SHALL NOT BE RECESSED INTO A WALL OR SIDING. SEE THE FOLLOWING DIAGRAM FOR VENT TERMINATION CLEARANCES. 30 AVERTISSEMENT: LE BAS DE LA MITRE DOIT SE TROUVER À AU MOINS 305 MM (12 IN.) DU SOL. LE HAUT DE LA MITRE DOIT SE TROUVER À AU MOINS 457 MM (18 IN.) EN DESSOUS DE TOUT MATÉRIAU COMBUSTIBLE (BALCON DE BOIS, PAR EXEMPLE), ET LE CÔTÉ DE LA MITRE DOIT SE TROUVER À AU MOINS 152 MM (6 IN.) DE TOUT MUR EXTÉRIEUR PARALLÈLE. LES MITRES NE DOIVENT PAS ÊTRE ENCASTRÉES DANS LE MUR OU UN REVÊTEMENT DE MUR. VOIR LE SCHÉMA SUIVANT POUR LES DÉGAGEMENTS DE MITRE RECOMMANDÉS.