Seite 106 SITRANS Probe LR – BETRIEBSANLEITUNG ENTITY CONCEPT DEFINITION: THE ENTITY CONCEPT ALLOWS THE INTERCONNECTIONS OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATIONS. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE AND CURRENT WITH INTRINSICALLY SAFE APPARATUS CAN RECEIVE AND REMAIN INTRINSICALLY SAFE, CONSIDERING FAULTS, MUST BE EQUAL OR GREATER THAN THE VOLTAGE (Uo) AND CURRENT (Io) LEVELS WHICH CAN BE DELIVERED BY THE ASSOCIATED APPARATUS, CONSIDERING FAULTS AND APPLICABLE FACTORS. IN ADDITION, THE MAX. UNPROTECTED CAPACITANCE (Ci) AND INDUCTANCE (Li) OF THE INTRINSICALLY SAFE APPARATUS, INCL. INTERCONNECTING WIRING, MUST BE EQUAL OR LESS THAN THE CAPACITANCE AND INDUCTANCE WHICH CAN BE SAFELY CONNECTED TO THE ASSOCIATED APPARATUS. THE ENTITY EVALUATION CONCEPT IS A METHOD USED TO DETERMINE ACCEPTABLE COMBINATIONS OF INTRINSICALLY SAFE APPARATUS AND CONNECTED ASSOCIATED APPARATUS THAT HAVE NOT BEEN INVESTIGATED IN SUCH COMBINATION. 8. EXTERNAL BONDING HUBS ARE REQUIRED WHEN BOTH CONDUIT ENTRIES ARE USED. 7. USE SUPPLY WIRES RATED FOR 10 ° ABOVE. 6. INSTALL PER NEC / CEC 5. SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY. 4. UNDER THE ENTITY EVALUATION CONCEPT, THE LR 200 HAS THE FOLLOWING: Ui = 30 VOLTS D.C. Ii = 120 mA Pi = 0.8W Ci = 3.6 nF Li = 0.1 mH 3. THE MAXIMUM VOLTAGE OF THE NON-INTRINSICALLY SAFE APPARATUS MUST NOT EXCEED 250 V rms. 2. APPROVED DUST-TIGHT AND WATER-TIGHT CONDUIT SEALS ARE REQUIRED FOR CLASS II, DIV.1, Gr. E, F, G AND OUTDOOR NEMA 4X/TYPE 4X LOCATIONS 1. ANY CSA / FM INTRINSICALLY SAFE BARRIER / POWER SUPPLY, WITH ITS OUTPUT VOLTAGE (Uo) NOT EXCEEDING 30 V AND ITS OUTPUT CURRENT (Io) LIMITED BY LOAD RESISTANCE (Ro); SUCH THAT Io = Uo / Ro, DOES NOT EXCEED 120 mA NOTES: Load 4 – 20 mA HAZARDOUS AREA 2365161102 T. ADAM IVZ PETERBOROUGH BPS 1:1 23651611 1 SITRANS LR 200, INTRINSICALLY SAFE CONNECTION DIAGRAM NTS IVZ BPS 26 / FEB. / 03 RADAR Product Group SN SN RPC RPC FOR APPROVAL ADD NOTE 8 PER ECN 2003-0348 ADD CSA/FM NOTE1, ADD NOTES 5, 6 AND 7, ADD VALUES IN NOTE 4 PER ECN 2003-0167 1 0 2 INTRINSICALLY SAFE (SEE NOTE 1) SAFE AREA APPARATUS NON-HAZARDOUS AREA G: Einbau in Ex-Bereichen mmmmm 1 2 B NOV 07/2003 APRIL 29/03 FEB 26/03 Anschlusszeichnung Eigensicherheit (FM) Zeichnungsnummer 23651611 7ML19985HR32