Download SITRANS Probe LR - Electrocomponents

Transcript
Seite 106
SITRANS Probe LR – BETRIEBSANLEITUNG
ENTITY CONCEPT DEFINITION: THE ENTITY CONCEPT ALLOWS THE INTERCONNECTIONS OF INTRINSICALLY
SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATIONS.
THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE AND CURRENT WITH INTRINSICALLY SAFE
APPARATUS CAN RECEIVE AND REMAIN INTRINSICALLY SAFE, CONSIDERING FAULTS, MUST BE EQUAL OR
GREATER THAN THE VOLTAGE (Uo) AND CURRENT (Io) LEVELS WHICH CAN BE DELIVERED BY
THE ASSOCIATED APPARATUS, CONSIDERING FAULTS AND APPLICABLE FACTORS. IN ADDITION, THE MAX.
UNPROTECTED CAPACITANCE (Ci) AND INDUCTANCE (Li) OF THE INTRINSICALLY SAFE APPARATUS, INCL.
INTERCONNECTING WIRING, MUST BE EQUAL OR LESS THAN THE CAPACITANCE AND INDUCTANCE WHICH
CAN BE SAFELY CONNECTED TO THE ASSOCIATED APPARATUS.
THE ENTITY EVALUATION CONCEPT IS A METHOD USED TO DETERMINE
ACCEPTABLE COMBINATIONS OF INTRINSICALLY SAFE APPARATUS AND
CONNECTED ASSOCIATED APPARATUS THAT HAVE NOT BEEN
INVESTIGATED IN SUCH COMBINATION.
8. EXTERNAL BONDING HUBS ARE REQUIRED WHEN BOTH CONDUIT ENTRIES ARE USED.
7. USE SUPPLY WIRES RATED FOR 10 ° ABOVE.
6. INSTALL PER NEC / CEC
5. SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY.
4. UNDER THE ENTITY EVALUATION CONCEPT, THE LR 200 HAS THE
FOLLOWING:
Ui = 30 VOLTS D.C.
Ii = 120 mA
Pi = 0.8W
Ci = 3.6 nF
Li = 0.1 mH
3. THE MAXIMUM VOLTAGE OF THE NON-INTRINSICALLY SAFE APPARATUS
MUST NOT EXCEED 250 V rms.
2. APPROVED DUST-TIGHT AND WATER-TIGHT CONDUIT SEALS ARE REQUIRED
FOR CLASS II, DIV.1, Gr. E, F, G AND OUTDOOR NEMA 4X/TYPE 4X LOCATIONS
1. ANY CSA / FM INTRINSICALLY SAFE BARRIER / POWER SUPPLY, WITH ITS OUTPUT
VOLTAGE (Uo) NOT EXCEEDING 30 V AND ITS OUTPUT CURRENT (Io) LIMITED BY
LOAD RESISTANCE (Ro); SUCH THAT Io = Uo / Ro, DOES NOT EXCEED 120 mA
NOTES:
Load
4 – 20 mA
HAZARDOUS AREA
2365161102
T. ADAM
IVZ
PETERBOROUGH
BPS
1:1
23651611
1
SITRANS LR 200,
INTRINSICALLY SAFE
CONNECTION DIAGRAM
NTS
IVZ
BPS
26 / FEB. / 03
RADAR
Product Group
SN
SN
RPC
RPC
FOR APPROVAL
ADD NOTE 8 PER ECN 2003-0348
ADD CSA/FM NOTE1, ADD NOTES 5, 6 AND 7, ADD
VALUES IN NOTE 4 PER ECN 2003-0167
1
0
2
INTRINSICALLY SAFE
(SEE NOTE 1)
SAFE AREA APPARATUS
NON-HAZARDOUS AREA
G: Einbau in Ex-Bereichen
mmmmm
1
2
B
NOV
07/2003
APRIL
29/03
FEB
26/03
Anschlusszeichnung Eigensicherheit (FM)
Zeichnungsnummer 23651611
7ML19985HR32