Download EGDE 30

Transcript
ENGLISH
15.
OPERATION OF THE ELECTRONIC CONTROL UNIT A1
MAN
with the battery A or B button, under a breakable cover, for emergency starting,
MAN
MAN
A
B
with the buttons Man A or Man B,
A
0
15.1
Manual start
When the manual start is given, the electronic control unit immediately begins to start the motor pump set.
Manual start may be obtained in the following ways:
MAN
B
with the test button and the consent of the respective warning light
The test button is enabled on manual starting after the engine has been started and stopped again or after a
start failure.
When the control unit detects that the engine is in run status, the test button is automatically rendered
inoperative and the respective warning light goes out.
15.2
Automatic start
The pumps are started automatically, ONLYWITH THE SELECTOR IN AUTOMATIC POSITION, by
means of the pressure drop pressure switches of the float of the priming tank, when the respective warning
lights come on.
Fixed warning lights indicate the opening of the contacts of the pressure drop pressure switches and the
closing of the contacts of the priming float.
Blinking warning lights indicate the closing of the contacts of the pressure drop pressure switches and the
opening of the contacts of the priming float.
After the opening of the contact of the pressure switches (terminals 39 – 40) the start cycle begins with 6
alternate impulses automatically on the batteries A and B of about 15 seconds (if a battery is inefficient it is
automatically excluded and the start cycle continues on the other battery).
If the engine fails to start after the sixth impulse, the control unit blocks the automatic cycle.
15.3
Manual stop
The engine can be stopped only MANUALLY if the system is under pressure again.
However, this message will appear on the display:
DON’T SWITCH OFF IN EVENT OF FIRE.
If the system is not under pressure, with the selector turned to automatic, it is not possible to switch off the
motor pumps and this message will again appear on the display:
DON’T SWITCH OFF IN EVENT OF FIRE – STOP EXCLUDED.
15.4
Automatic Stop
Automatic stop occurs ONLYWITH THE SELECTOR IN AUTOMATIC POSITION and only if
STARTING HAS BEEN REQUESTED BYTHE PRESSURE DROP PRESSURE SWITCHES .
The motor pump stops 20 minutes after the permanent closing of the requesting pressure switches.
The display continuously indicates how much time is left before the motor pump will stop.
Automatic stop DOES NOT OCCUR if stopping has been requested by the priming float; in this case stopping
STOP
can only occur by pressing the STOP key
.
15.5
Regulating automatic stopping according to former standard UNI 10779 for the use of hydrants
It is possible to regulate automatic stopping only if:
THE JUMPER B HAS BEEN CUT, located above the Dip Switch device.
on the display of the control unit A1 is held down, this message appears:
When the test led button
“UNI 10779 ON” (active function).
38