Electrical connection NOTE In some cases it is better to mount accessories before placing the fan on the roof base. CAUTION At DVVI • The corners of sound attenuator are provided with securing bolts during transport and lifting. Remove them directly before mounting and change with the supplied ones. At DVV/DVVI 1000, 1000‐M, 1000‐P • Suction side is equipped with a short nozzle, which contribute to better ex‐ traction. If the suction side should be provided with a flap VKV/F rsp. con‐ nected to a duct, remove the nozzle before mounting. After removing the nozzle, all screws should be well tightened to prevent ingress of moisture. NOTE It is recommended to install a certified flexible connection (needed for smoke extract fans only) between fan and duct to avoid eventual tensions or distortions of the base plate. Flexible connection has to comply temperature/time class of the fan (400°C/2h rsp. 600°C/2h). NOTE Mounting examples with accessories see Appendix 2. Mounting faults see Appendix 3. 7 Electrical connection The wiring diagram is placed on the cover of connection box/service switch (inside). WARNING Hazard from hot surface at smoke extract fans! • The quality and routing of power supply cable must ensure uninterrupted energy supply, also in case of fire. Inside fire zone use only certified cable. Electric cable must not touch or be fastened on the casing of the fan. NOTE • IE2 motors have serial built‐in PTC (at other motors on request). More than two PTC chains may not be switched in series, as this can lead to undefined cut‐outs. • Maximum check voltage of PTC is 2,5 V. • The wiring diagrams see Appendix 4. 24 DVV 17.12.2012