FOL7250* Troubleshooting Troubleshooting 8.1 LED displays The following section provides an overview of the possible LED displays of the repeater and their possible causes. LED display "System" State Possible cause Lights up green ■ Does not light up ■ ■ ■ Signaling contact Transfer rate detected, power supply in order no alarm Power supply failure (total failure; with redundant supply, failure of both supply voltages) Power supply incorrectly connected Module defective alarm Flashes red Transfer rate not yet detected ■ No transmitting node present ■ No connection with a partner module that transmits telegrams ■ Transmit and receive fiber optic cable connections reversed ■ Transfer rate does not conform to the PROFIBUS standard ■ There is only one active node connected that only transmits tokens to itself. The display must change after a second node is connected (token telegrams alone are not enough to set the transfer rate) ■ The connected RS 485 segment is only terminated at one end no alarm Flashes red/green Transfer time detected, but: ■ It is not yet possible to determine the slot time of the network (network parameter HSA set too low, no transmitting node present) ■ One optical channel is set to the mode "Redundant optical ring", but not the second (this operating mode must always be set on both optical channels, see chapter 5.1) ■ The slot time of the network is set to a value that is too low no alarm 201181 2012-09 EN 8 60 - EN