05/27/2005,08:07:24,
MAIL:
subject
"CS121
Event
29"
successfully
sent.
These are 4 Emails indicating the status of the AUX Ports (Auxiliary connection for
external alarms), which are set to give notification of the status signal LOW. Since
the AUX Status can only be set to High or Low and given that the CS121 in itself
cannot distinguish the device, an alarm email will be sent by the CS121 to the
designated ADMIN at startup per default with the startup status of each connected
alarm. In this case, it is up to the administrator to determine if the emails indicate an
actual
alarm
or
not.
05/27/2005,08:07:31,
MAIL:
subject
"CS121
Event
38"
successfully
sent.
05/27/2005,08:07:43,
MAIL:
subject
"CS121
Event
39"
successfully
sent.
05/27/2005,08:07:44,
MAIL:
subject
"CS121
Event
40"
successfully
sent.
05/27/2005,08:07:57,
MAIL:
subject
"CS121
Event
41"
successfully
sent.
05/27/2005,08:08:02,
MAIL:
subject
"CS121
Event
42"
successfully
sent.
05/27/2005,08:08:03,
MAIL:
subject
"CS121
Event
43"
successfully
sent.
05/27/2005,08:08:03,
MAIL:
subject
"CS121
Event
44"
successfully
sent.
05/27/2005,08:08:03,
MAIL:
subject
"CS121
Event
45"
successfully
sent.
Thiese are 8 Emails sending information about analogue sensors (temperature,
humidity and the like) that are connected to a SENSORMANAGER, indicating that all
controlled values are within tolerance levels - or that no sensor is connected to the
device
or
connection
port.
05/27/2005,08:08:04,
MAIL:
subject
"CS121
Event
54"
successfully
sent.
05/27/2005,08:08:04,
MAIL:
subject
"CS121
Event
55"
successfully
sent.
05/27/2005,08:08:04,
MAIL:
subject
"CS121
Event
56"
successfully
sent.
05/27/2005,08:08:05,
MAIL:
subject
"CS121
Event
57"
successfully
sent.
These 4 Emails indicate that the digital sensors (for airconditioning, fire alarms and
the like) of the SENSORMANAGER, are either in the normal state or that no sensor
is
connected.
05/27/2005,08:08:05,
MAIL:
subject
"CS121
Event
62"
successfully
sent.
05/27/2005,08:08:05,
MAIL:
subject
"CS121
Event
63"
successfully
sent.
05/27/2005,08:08:06,
MAIL:
subject
"CS121
Event
64"
successfully
sent.
05/27/2005,08:08:06,
MAIL:
subject
"CS121
Event
65"
successfully
sent.
These 4 Emails indicate the status of the digital alarm contacts of the sensors (for
Emergency OFF, fire extinguisher and the like) connected with the
SENSORMANAGER, showing either the the status is NORMAL or that nothing is
connected.
05/27/2005,08:08:06,
MAIL:
subject
"CS121
Event
70"
successfully
sent.
This Email shows that no Sensormanager is connected although the CS121 is
configured as having a connection to a Sensormanager. This informs the ADMIN
61