Download YASKAWA AC Drive 1000-Series Option Analog Input Installation

Transcript
5 Installation Procedure
◆
Terminal Functions
Table 4 Option Terminal Functions
Signal
Level
Function
V1
Analog signal
input 1
S1
V2
Analog signal
input 2
S2
V3
Description
Voltage/Current
Linear
DIP switch
Accuracy
Terminal
• Input terminals for an analog voltage or
-10 to 10 V current signal from voltage/current
or
reference source
4 to 20 mA • Use jumpers S1, S2, and S3 to select the
Analog signal
type of input signal <1>
input 3
±0.1% F.S.
<2>
S3
AC
Common
–
Common for analog voltage/current input
–
FE
Ground
–
Used for grounding shielded lines
–
–
<1> Default setting is for voltage input.
<2> At an ambient temperature of 25 °C (77 °F).
YASKAWA ELECTRIC TOBP C730600 38B 1000-Series Option AI-A3 Installation Manual
21