TE10P chp 9, 10 & index 6/28/00 7:40 AM Page 9-3 Maintenance DIAGNOSTICS Diagnostic unit To make maintenance easier and to diagnose the state of the controller, it is advisable to use the Eurotherm type 260 diagnostic unit. The diagnostic unit is fitted with a flat ribbon cable which plugs into the 20-pin connector. This diagnostic connector is located: · on the top part of the controller for units rated 16A to 100A; the connection is accessible without opening the access door; · on the driver board accessible with the front door open for 125A to 400A units. ’Scope’: measured signal output (oscilloscope or rms voltmeter) 0V (ground) Diagnostic connector located on controller Signal Digital display of average values (4 digits) V Flat cable (delivered with unit) 100 V ribbon Scaling switch ext off 20 ext 1 20 V 9V power supply: Battery or rechargable External signal input Battery charger EUROTHERM diagnostic unit Figure 9-1 The EUROTHERM type 260 diagnostic unit Provided with a 20-way switch, the diagnostic unit is used to measure the values of certain control parameters. In the ‘20V’ position of the scaling switch, the digital display shows two decimal places to give a precise reading of the selected values. The diagnostic unit display corresponds to the average values of the rectified signals. Because of the ‘Scope’ output, the signals may also be viewed using an oscilloscope, or measured with an rms reading voltmeter for the AC component (voltmeter in AC position). The following table gives a description of each position of the EUROTHERM type 260 diagnostic unit, together with typical values of the signals measured. TE10P User manual 9-3