Download Operating Instructions - OPTISWITCH 4000 C - with
Transcript
Set up It is absolutely necessary that you remove the test magnet after the test from the instrument housing. 6.3 Function chart The following chart provides an overview of the switching conditions depending on the adjusted mode and level. Level Switching status Control lamp Mode max. transistor conducts Green Mode max. transistor blocks red Mode min. transistor conducts Green Mode min. transistor blocks red transistor blocks flashes red any 31763-EN-060830 Failure OPTISWITCH 4000 C - with transistor output 19