Download User Manual - Automatikprodukter
Transcript
User Manual PCl 2 Page 13 3.5.5 External Relay Operation Assignment to a digital input (DI) for external switching of the alarm relay (ON and/or OFF). This function has priority to gas alarm and/or manual switching in the menu “Status Relay“. 3.5.6 Setting Status Function Relay No. External On 0 If digital input closed, relay switches ON External Off 0 If digital input closed, relay switches OFF Symbol Description R 01 DI-ON DI-OFF Relay Selection Delay Mode of the Relay. Delay time ON starts when the alarm is released and/or delay time OFF starts when the alarm returns to normal condition. 3.6 Setting Status Symbol Description R 01 Relay No. 0s Delay Time ON 0s Delay Time OFF 0 Function Relay Selection Mode ON: Relay is only activated at the end of the defined time (sec.) 0 sec. = No delay 0 Mode OFF: Relay is only deactivated at the end of the defined time (sec.) 0 sec. = No delay Menu MP Parameters Display and change of parameters, assignment of alarms to alarm relays and activation of Measuring Points (MP). MP Parameter (Main Menu) MP 01 active (Selection of MP) MP Mode active Gas Type CL2 Measuring Range 20 ppm MP Signal linear Activate or deactivate MP See 3.6.1 Define gas type See 3.6.2 Define measuring range See 3.6.3 Adjust signal form of the transmitter See 3.6.4