Download Manuale User manual - Temperature Controller
Transcript
5.4.2 MCM260-5AD Modbus Address 0 1 5 900 901 1000 1001 1002 1003 1100 1101 1102 2002 2003 2004 Description Device Type Contains the device identification code. (Default 165) Firmware Version Contains the device firmware version. Slave Address Contains the selected modbus slave address. (Depends on the position of the rotary-switch) Cold Junction Temperature For AI1 and AI2 Cold Junction Temperature For AI3 and AI4 Contains the value of cold junction in tenths of degree Process Value AI1 Process Value AI2 Process Value AI3 Process Value AI4 Contain process value. For temperature sensors the value is in tenths of degree; for the other sensors the value depends on the words 3005-3012. AO1 Value AO2 Value Contain analogue outputs value. The current or voltage value of outputs depends on the values set on the word 4003-4006. (Defualt 0). Q-ID Status Manages Q-ID output status. (default 0) Bit 0: Reserved Bit 1: Reserved Bit 2: Q-ID output status. Off-line Time (0-60000) It’s the maximun time (in ms) that can elapse between two Modbus messages without the slave sets outputs to word 2000 value. With 0 control is not performed. (Default 0). Reserved Delay Modbus Answer (0-250ms) Select modbus answer delay. (Default 0). 21 RO RO RO RO RO R/W R/W R/W R/W