Download User's manual
Transcript
SVERKER 750/760 6.3 Selecting the 6.4 Measuring current correct current output Select the output at which the setting knob must be turned the furthest to obtain the desired current. This will improve setting accuracy and enable Sverker to deliver maximum power. When the object being tested has high impedance or may reach saturation, it is especially important to use the output having the highest possible voltage. This will drive the desired current through the object being tested efficiently and minimize distortion of the current waveform. The ammeter in Sverker has four inputs. Three of them are internal inputs fixed to the individual current outputs, and one is an external input located on the control panel. Active input (i.e. ammeter test point) is indicated by an indicator lamp. Use the button marked A to transfer the ammeter test point to the selected input. The internal inputs are used to measure the current generated by Sverker. The external input is used to measure current in an external circuit. If so desired, however, it can be used for measurement of current from Sverker. This is useful since ammeter accuracy is highest when measurement proceeds via the external input. The external input can be used for currents of up to 6 A. The HOLD (freeze) function makes it possible to measure currents of very short duration. Activate it by pressing the button marked HOLD. See the section headed ”Ammeter and voltmeter” in Chapter 3. 40 Programma Electric AB ZP-CD01E R05A