CM a10w , CM a11w User's
M anual
CM a10w , CM a11w
The CMa10w/CMa11w is a Wireless M-Bus temperature
and humidity sensor for indoor use.
CMa10w/CMa11w complies with the OMS standard and
operates in Wireless M-Bus mode T1. CMa10w/CMa11w
is the perfect choice when wiring is not an option.
CM a10w , CM a11w User's M anual– Version 1.3
CM a10w , CM a11w User's M anual
Contents
CON TEN TS ............................................................................................................ 2
1
D OCU M EN T N OTES .................................................................................... 4
1.1
1.2
2
U SIN G THIS M A N U A L ................................................................................. 5
2.1
2.2
2.3
3
PURPOSE AND AUDIENCE................................................................................................ 5
M ODELS ........................................................................................................................ 5
A DDITIONAL AND UPDATED INFORM ATION ....................................................................... 5
IN TROD U CTION ........................................................................................... 6
3.1
3.2
3.3
4
COPYRIGHT AND TRADEM ARK ......................................................................................... 4
CONTACTS ..................................................................................................................... 4
PRODUCT CONFIGURATION ............................................................................................. 6
CAPABILITIES ................................................................................................................. 6
A PPLICATIONS................................................................................................................ 6
GETTIN G STA RTED ..................................................................................... 7
4.1
4.2
4.3
OVERVIEW ..................................................................................................................... 7
M OUNTING .................................................................................................................... 9
W IRELESS M -BUS .......................................................................................................... 9
4.3.1
Installation procedure ............................................................................................... 9
4.3.1.1 Installation procedure – Select Unencrypted m ode ...................................... 9
4.3.1.2 Installation procedure – Select Encrypted m ode........................................... 9
5
A PPLICA TION D ESCRIPTION .................................................................... 1 1
5.1
OPERATION .................................................................................................................. 11
5.1.1
5.2
Operation m odes ..................................................................................................... 11
5.1.1.1
5.1.1.2
5.1.1.3
5.1.1.4
Inactive m ode ...............................................................................................11
Installation procedure...................................................................................11
Norm al operation – Unencrypted m ode ......................................................11
Norm al operation – Encrypted m ode ...........................................................11
DISPLAY (CM A 10W ) .................................................................................................... 12
5.2.1
Display sym bols ...................................................................................................... 12
5.2.1.1 Operation m ode indicator ............................................................................12
5.2.1.2 Battery level indicator ..................................................................................13
5.2.2
5.3
6
Display m enu ........................................................................................................... 14
5.2.2.1
5.2.2.2
5.2.2.3
5.2.2.4
5.2.2.5
5.2.2.6
5.2.2.7
Deactivate the product .................................................................................15
Reset to factory default ................................................................................15
Change language..........................................................................................15
Change contrast ...........................................................................................15
Enable/disable encryption ............................................................................15
Change transmit interval ..............................................................................15
Lock the product ...........................................................................................15
LED INDICATIONS ........................................................................................................ 16
A D M IN ISTRA TION OF THE PROD U CT ...................................................... 1 7
6.1
6.2
M -BUS PRODUCT IDENTIFICATION ................................................................................. 17
W IRELESS M -BUS M ODE .............................................................................................. 17
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 2 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
6.3
6.4
6.5
6.6
M -BUS ADDRESSING .................................................................................................... 17
OPERATION M ODE ........................................................................................................ 17
SPONTANEOUS TRANSM ISSION .................................................................................... 17
M -BUS COM M ANDS ..................................................................................................... 17
6.6.1
Send spontaneous data (SND_NR) ........................................................................ 17
6.6.1.1 Slave to master – Telegram 1 (SND_NR)......................................................17
7
TROU BLESHOOTIN G ................................................................................. 2 3
7.1
7.2
7.3
8
COLLECTOR DOES NOT RECEIVE ANY TELEGRAM SENT FROM THE PRODUCT .................... 23
INFORM ATION NOT VISIBLE ON THE DISPLAY .................................................................. 23
TEM PERATURE VALUE IS INACCURATE ........................................................................... 23
TECHN ICA L SPECIFICA TION S .................................................................. 2 4
8.1
8.2
CHARACTERISTICS ........................................................................................................ 24
FACTORY DEFAULTS ..................................................................................................... 25
9
TY PE A PPROV A LS .................................................................................... 2 6
10
SA FETY A N D EN V IRON M EN T ................................................................... 2 7
10.1
11
D OCU M EN T HISTORY ............................................................................... 2 8
11.1
12
SAFETY PRECAUTIONS .................................................................................................. 27
DOCUM ENT SOFTWARE AND HARDWARE APPLIANCE...................................................... 28
REFEREN CES ............................................................................................. 2 9
12.1
12.2
REFERENCES ................................................................................................................ 29
TERM S AND ABBREVIATIONS ......................................................................................... 29
12.2.1 Num ber representation........................................................................................... 29
13
A PPEN D IX A – EX A M PLE ......................................................................... 3 0
13.1
13.2
DENOM INATION OF VALUES IN REPORTS........................................................................ 30
DENOM INATION OF VALUES FOR USE IN FILTERS ............................................................ 32
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 3 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
1
Docum ent notes
All inform ation in this m anual, including product data, diagrams, charts, etc. represents
inform ation on products at the tim e of publication, and is subject to change w ithout prior
notice due to product improvem ents or other reasons. It is therefore recomm ended that
custom ers contact Elvaco AB for the latest product inform ation before purchasing a
CM a10w /CM a11w product.
The docum entation and product are provided on an “as is” basis only and m ay contain
deficiencies or inadequacies. Elvaco AB takes no responsibility for dam ages, liabilities or
other losses by using this product.
1 .1
Co p y r i g h t an d t r ad em ar k
© 2012, Elvaco AB. All rights reserved. No part of the contents of this m anual m ay be
transmitted or reproduced in any form by any m eans w ithout the w ritten perm ission of
Elvaco AB. Printed in Sw eden.
CM a10w /CM a11w is a tradem ark of Elvaco AB, Sw eden.
1 .2
Co n t ac t s
Elvaco AB Headquarter
Teknikgatan 18
434 37 Kungsbacka
SWEDEN
Phone: +46 300 30250
Fax: +46 300 18440
E-M ail: [email protected]
Elvaco AB Technical Support
Phone: +46 300 434300
E-M ail: [email protected]
Online: http://w ww .elvaco.com
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 4 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
2
Using this m anual
2 .1
Pu r p o se an d au d i en c e
This m anual covers inform ation needed to mount, configure and use the CM a10w /CM a11w
Wireless M -Bus indoor temperature and hum idity sensor. It is intended for field engineers
and developers.
2 .2
M o d el s
CM a10w , CM a11w
2 .3
A d d i t i o n al an d u p d at ed i n f o r m at i o n
Latest docum entation version is available on Elvaco w eb site at http://w w w.elvaco.com .
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 5 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
3
Introduction
3 .1
Pr o d u c t c o n f i g u r at i o n
Use the table below to find out the capabilities of your product.
Pr o d uc t
n am e
Co m m ent s
CM a10w
Indoor Wireless M -Bus temperature and hum idity sensor w ith
display
CM a11w
Indoor Wireless M -Bus temperature and hum idity sensor w ithout
display
Table 1 Product configuration
3 .2
Cap ab i l i t i es
The CM a10w /CM a11w is a 1-w ay Wireless M -Bus comm unicating temperature and
hum idity sensor for indoor use. CM a10w /CM a11w is the ideal product for com fort level
billing. The high accuracy sensor and user friendly handling m ake the CM a10w /CM a11w
the perfect choice for tenant owners.
3 .3
A p p l i c at i o n s
The CM a10w /CM a11w should be used in the follow ing scenarios:

Indoor m easurem ent of tem perature and/or humidity

High accuracy indoor clim ate logging

Use instead of CM a10/CM a11 w hen w iring is not an option
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 6 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
4
Getting Started
This chapter covers the steps required for getting the CM a10w /CM a11w installed and
operational. No pre-configuration is needed before using the CM a10w/CM a11w .
4 .1
Ov erv i ew
1
2
1. Push-button (SW2)
(CM a10w )
2. Display (CM a10w )
3. LED1
4. Push-button (SW1)
5. Serial Num ber
(Identification)
Figure 1 Front view
3
4
5
Figure 2 Bottom view (rear cover rem oved)
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 7 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
6
6
6. Do not use for
m ounting
DOWN
Figure 3 Rear cover
Figure 4 Dem ounting
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 8 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
4 .2
M ount ing
When mounting the CM a10w /CM a11w , avoid rooms w ith a lot of supplem entary heat,
such as kitchens or south facing rooms. Position the sensor aw ay from direct sunlight.
Avoid placing on an external w all or near an external door. M ake sure that the sensor is
not positioned closer than 1 m from the nearest radiator and at least 1.5 m above the floor.
The CM a10w /CM a11w can be mounted directly on the w all, or over a m ounting box. If the
CM a10w /CM a11w is placed over a conduit pipe, it is recomm ended to fill the pipe to
prevent air flow w hich could affect accuracy of the values.
Rem ove the rear cover to be able to press the installation button SW1 (4).
IM PORTA NT
Please take the follow ing in consideration:
4 .3

Do not use mounting holes (6) as in Figure 3.

Turn the rear cover as shown in Figure 3.

Do not mount the product inside a steel cabinet, which w ill dram atically low er the
possibilities to connect to a collector.
Wi r el ess M -Bu s
The product is delivered w ith the radio turned off. The radio must be m anually switched on
during the installation procedure.
Th e pr o d uct w il l n ot be ac t ivat ed u nt i l t he i n st al lat io n pr oc ed ure i s st art ed.
4 .3 .1 In st al l at i o n p r o c ed u r e
The product can be installed and enabled in tw o modes:

U n enc ry pt ed m o de: Data is sent unencrypted and the encryption key is not
needed to decrypt the data.

En c ry pt ed m o de: Data is sent in encrypted m ode and the encryption key is
needed to decrypt the data.
Please advise your project m anager w hich operation m ode is used in your project.
4 .3 .1 .1
In st al lat i o n pr oc edu re – Sel ec t U nen cr yp t ed m o d e
By perform ing the follow ing steps, the product w ill start to send spontaneous
u n enc ry p t ed data:
1. Press and hold button SW1 (4) for 5 seconds, until LED1 (3) flashes fast. See Table 2 for
complete inform ation about LED indication.
2. Release SW1 (4)
th
The product will now start to send spontaneous unencrypted SND_NR telegram s every 6
m inute (default).
4 .3 .1 .2
In st al lat i o n pr oc edu re – Sel ec t En cr yp t ed m od e
By perform ing the follow ing steps, the product w ill start to send spontaneous en cr y pt ed
data:
1. Press and hold button SW1 (4) for 10 seconds, until LED1 (1) flashes slow . See Table 2
for complete inform ation about LED indication.
2. Release SW1 (4)
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 9 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
th
3. The product will now start to send spontaneous encrypted SND_NR telegram s every 6
m inute (default).
IM PORTA NT
Please take the follow ing in consideration:

After the product is activated, configuration can still be changed on the CM a10w
using the Setup m enu, see section 5.2.

The device can be locked for future configuration, see section 5.2.2.7.
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 10 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
5
Application description
This chapter covers general application description and configuration of the product.
5 .1
Op er at i o n
th
The product will autom atically, after the installation procedure, send T1 m essages every 6
m inute containing sensor data, such as instantaneous tem perature and hum idity. The
product w ill also send product status inform ation, containing battery status and other
relevant inform ation.
Product configuration can be changed using the Setup m enu (CM a10w ) as long as the
product has not been locked for future configuration, see section 5.2.2.7.
5 .1 .1 Op er at i o n m o d es
The product has the following operation m odes:
1. Inactive (on delivery)
2. Installation procedure (during installation)
3. Norm al operation - encrypted m ode
4. Norm al operation - unencrypted m ode
5 .1 .1 .1
In act iv e m o de
The product is delivered inactive, w hich m eans that the product does not perform any
tasks before an installation procedure is started. This saves the battery lifetim e and
ensures that there is no radio activity until the product is m anually activated.
5 .1 .1 .2
In st al lat i o n pr oc edu re
The installation procedure is used to activate the product, see 4.3.1.
5 .1 .1 .3
N o r m al op er at i o n – U nen cry p t ed m o d e
In norm al operation unencrypted m ode, the product w ill by default send spontaneous
th
u n enc ry p t ed m essages every 6 minute. This can be changed as long as the product has
not been locked. This mode is norm ally used w hen the collector or AM R/AMM system
does not handle AES encryption or if the AES key is unknown to the host system .
5 .1 .1 .4
N o r m al op er at i o n – Enc ry p t ed m o de
In norm al operation encrypted m ode, the product will by default send spontaneous
th
en cr yp t ed m essages every 6 m inute. This can be changed as long as the product has not
been locked. This mode is used to secure data sent from the product to the collector or
AM R/AM M system . To be able to decrypt the data, the private 128 bit AES key must be
know n by the collector or by the host system . The private 128 bit AES key is on dem and
provided to the custom er by Elvaco AB.
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 11 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
5 .2
D i sp l ay (CM a1 0 w )
The display show s current sensor inform ation and is also used to change and view the
CM a10w configuration.
The display is in norm al operation turned off to save battery. The display is turned on as
soon as SW2 (1) is pushed and will be turned off if no button is pressed w ithin 5 seconds.
When the display is turned off, the m enu page w ill be reset to the first page.
Please see Figure 5 for display design.
Figure 5 CM a10w display
5 .2 .1 D i sp l ay sy m bo l s
To easily show current operation and functionality of the product, the display is equipped
w ith display sym bols, w hich indicate Wireless M -Bus mode, encryption and battery level.
5 .2 .1 .1
Op er at i o n m o de i n d icat or
This indicator shows if the product runs in encrypted or unencrypted mode. If the indicator
is visible, all comm unication is encrypted, otherw ise all com munication is sent
unencrypted.
Sy m b o l
D escr i pt i o n
Product is encrypting all m essages w ith AES 128 bit encryption.
If the product is running in unencrypted m ode, the operation mode
indicator is hidden.
Steady
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 12 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
5 .2 .1 .2
Bat t er y level in d i cat o r
The battery level indicator show s current battery level. The product should be exchanged
w hen the battery level indicator is flashing.
Sy m b o l
D escr i pt i o n
Battery has full capacity.
Battery level is m edium .
Battery level is low.
Battery is almost em pty.
Steady
Battery is em pty and the product w ill stop w orking w ithin 12
m onths.
Flashing
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 13 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
5 .2 .2 D i sp l ay m en u
Please see Figure 6 for m enu options.
Standard menu
Setup menu
Enter next page by pressing SW2
Change values using SW2
Confirm/enter next page by pressing SW1 for 1s.
DISPLAY OFF
*SETUP STARTS*
SW1
2s
SW2
Temp: 25.5°C
Humi: 40% RH
SETUP:
Deactivate=n/Y
SW2
SW1
MIN
MAX
25.5°C
25 .5°C
40% RH 40% RH
SETUP:
Total Reset=n/Y
SW2
Press 5 sec. To
reset MIN/MAX
value
SW1
SW2
5s
MIN/MAX values
are now reset
SW2
SETUP:
Language=Eng/
Deu/Sve
SW1
1 h AVERAGE
SETUP:
Contrast= -10..+10
25 .5°C
SW2
SW1
24h AVERAGE
SETUP:
Encryption=n/Y
25 .5°C
SW2
SW1
SETUP:
TxIntvl= 1..15 min
SW1
SETUP:
Setup Lock=n/Y
SW1
*END OF SETUP*
Restarting...
Figure 6 CM a10w Display m enu
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 14 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
5 .2 .2 .1
D eac t i vat e t h e pr o du ct
Navigate to Setup m enu and select “y” in “Deactivate” m enu page. This will deactivate the
product and the product must be activated w ith a new installation procedure.
5 .2 .2 .2
Reset t o f ac t o ry def au l t
In order to reset the product configuration to factory default, navigate to “Total Reset” in
the setup m enu and select “y”.
5 .2 .2 .3
Ch an g e l ang u ag e
Navigate to Setup m enu and select language (English, Deutsch or Svenska) in the
“Language” m enu page.
5 .2 .2 .4
Ch an g e c o nt rast
Navigate to Setup m enu and select contrast from -10 to +10 in “Contrast” m enu page. A
higher value indicates a higher contrast.
5 .2 .2 .5
En ab le/di sab le en cr yp t i on
Navigate to Setup m enu and select “y” to enable encryption and “n” to disable encryption
in the “Encryption” m enu page. This has the sam e functionality as activating the product
in encrypted or unencrypted mode.
5 .2 .2 .6
Ch an g e t ran sm i t i nt erv al
Navigate to Setup m enu and change interval from 1 minute to 15 m inutes in the “TxIntvl”
m enu page.
5 .2 .2 .7
Lo ck t he pr o d uc t
The product can be locked for future changes. Navigate to Setup m enu and select “y” in
“Setup Lock” m enu page. This w ill disable the possibility to enter the Setup m enu again.
IM PORTA NT
Lo ck i n g t h e p ro d u ct c ann o t b e u n d o ne an d any c on f i gu rat io n m ade can n ot be
c h an g ed. If y o u n eed t o un l o ck t he pr o d uct , i t n eed s t o b e sen t t o El vaco .
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 15 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
5 .3
LED i n d i cat i o n s
LED 1
St at e/D esc r ip t i on
Perm anently off
Off
Fast flash
Triggered w hen button is
pressed more than 5
seconds to select
unencrypted operation
m ode. Releasing the button
in this state w ill select
unencrypted operation
m ode.
50 m s on / 50 ms off
Slow flash
250 m s on / 250 m s off
V i su al
Triggered w hen button is
pressed more than 10
seconds to select encrypted
operation mode. Releasing
the button in this state w ill
select encrypted operation
m ode.
Table 2 LED 1 indications
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 16 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
6
Adm inistration of the product
This chapter covers the configuration and Wireless M -Bus implem entation of the product.
The Wireless M-Bus slave im plem entation is according to the new M -Bus standard
EN13757-2, EN13757-3, EN13757-4 and the OM S specification.
6 .1
M -Bu s p r o d u c t i d en t i f i c at i o n
The product can be identified by the following inform ation:

M anufacturer string = ELV

M edium = 0x1B (Room sensor)

Generation = 01-09 (CM a10w ), 10-19 (CM a11w )
The generation field betw een product releases will o n l y change (increase by 1) if the M Bus protocol inform ation changes betw een versions. Use the softw are version field in the
M -Bus telegram to identify current softw are version.
6 .2
Wi r el ess M -Bu s m o d e
The product is using Wireless M -Bus m ode T1, w hich m eans that the product sends
spontaneous data in one direction, from product to collector.
6 .3
M -Bu s ad d r essi n g
The address used is a globally unique address, which is set during production.
6 .4
Op er at i o n m o d e
The product can operate in encrypted or unencrypted mode. In encrypted mode, OM S
encryption mode 5 is used w ith AES 128 bit key for all telegram s. When running in
unencrypted mode, all telegrams will be sent unencrypted
6 .5
Sp o n t an eo u s t r an sm i ssi o n
The product will autom atically start sending spontaneous telegram s w ith m easurem ent
data after the installation procedure is completed. The product sends by default an
th
SND_NR telegram every 6 minute. The transmission interval is configurable in the Setup
m enu of the CM a10w .
6 .6
M -Bu s c o m m an d s
All data in the tables are described unencrypted.
6 .6 .1 Sen d spo n t an eo us d at a (SN D _N R)
During norm al operation, the Wireless M -Bus comm and SND_NR is sent by default every
th
6 minute.
6 .6 .1 .1
Sl ave t o m ast er – Telegr am 1 (SND _N R)
By t e i n dex
D at a
D escr i pt i o n
0
0xnn
L-Field
1
0x44
C-Field: SND_NR
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 17 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
2..3
0x9615
M anufacturer
“ELV”
4..7
0xnnnnnnnn
Identification number
8
0xnn
Version field
9
0x1B
Device type (M edium ) = Room sensor
10..11
0xnnnn
CRC-field
12
0x7A
CI-Field (Short header)
13
0xnn
Access num ber
14
0xnn
Status
15..16
0xnnnn
Configuration w ord
17..18
0x2f2f
AES check (idle filler)
19
0x02
Instantaneous temperature DIF
20
0x65
Instantaneous temperature VIF, external
tem perature
21..22
0xnnnn
Instantaneous temperature x 100
In case of error the tem perature w ill be set
to 0.
23
0x42 | 0x72
1-hour temperature rolling average DIF,
storage number 1
0x42 = The value is available
0x72 = The value is not yet calculated
24
0x65
1-hour temperature rolling average VIF,
external temperature
25..26
0xnnnn
1-hour temperature rolling average x 100
This value is unavailable (0) until 1 hour has
passed since pow er-on. During this first
hour the value w ill be flagged as “value
during error state”, DIF bits 5 and 4 = 1.
This value is updated every 6 m inute.
The temperature data w ill be 0 in case of
sensor error. See slave status byte in data
header.
27
0x82 | 0xb2
24-hour temperature rolling average DIF,
storage number 2
0x82 = The value is available
0xb2 = The value is not yet calculated
28
0x01
24-hour temperature rolling average DIFE
29
0x65
24-hour temperature rolling average VIF,
external temperature
30..31
0xnnnn
24-hour temperature rolling average x 100
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 18 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
This value is unavailable (0) until 24 hour
has passed since pow er-on. During this
period the value will be flagged as “value
during error state”, DIF bits 5 and 4 = 1.
This value is updated every hour.
The temperature data w ill be 0 in case of
sensor error. See slave status byte in data
header.
32
0x22
1-hour minim um tem perature DIF
33
0x65
1-hour minim um tem perature VIF, external
tem perature
34..35
0xnnnn
1-hour minim um tem perature x 100
In case of error the tem perature w ill be set
to 0.
This is the low est instantaneous
tem perature since last 1-hour period.
36
0x12
1-hour m aximum tem perature DIF
37
0x65
1-hour m aximum tem perature VIF, external
tem perature
38..39
0xnnnn
1-hour m aximum tem perature x 100
In case of error the tem perature w ill be set
to 0.
This is the highest instantaneous
tem perature since last 1-hour period.
40
0x62
24-hour minimum tem perature DIF
41
0x65
24-hour minimum tem perature VIF, external
tem perature
42..43
0xnnnn
24-hour minimum tem perature x 100
In case of error the tem perature w ill be set
to 0.
This is the low est instantaneous
tem perature since last 24-hour period.
44
0x52
24-hour m aximum temperature DIF
45
0x65
24-hour m aximum temperature VIF,
external temperature
46..47
0xnnnn
24-hour m aximum temperature x 100
In case of error the tem perature w ill be set
to 0.
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 19 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
This is the highest instantaneous
tem perature since last 24-hour period.
48
0x02
Instantaneous relative hum idity DIF
49
0xfb
Instantaneous relative hum idity VIF,
extension table FB
50
0x1a
Instantaneous relative hum idity VIFE
51..52
0xnnnn
Instantaneous relative hum idity x 10
In case of error the relative humidity will be
set to 0.
53
0x42 | 0x72
1-hour hum idity rolling average DIF,
storage number 1
0x42 = The value is available
0x72 = The value is not yet calculated
54
0xfb
1-hour relative humidity VIF, extension
table FB
55
0x1a
1-hour relative humidity VIFE
56..57
0xnnnn
1-hour relative humidity x 10
In case of error the relative humidity will be
set to 0.
58
0x82 | 0xb2
24-hour humidity rolling average DIF,
storage number 2
0x82 = The value is available
0xb2 = The value is not yet calculated
59
0x01
24-hour humidity rolling average DIFE
60
0xfb
24-hour relative hum idity VIF, extension
table FB
61
0x1a
24-hour relative hum idity VIFE
62..63
0xnnnn
24-hour relative hum idity x 10
In case of error the relative humidity will be
set to 0.
64
0x22
1-hour minim um relative humidity DIF
65
0xfb
1-hour minim um relative humidity VIF,
extension table FB
66
0x1a
1-hour minim um relative humidity VIFE
67..68
0xnnnn
1-hour minim um relative humidity x 10
In case of error the relative humidity will be
set to 0.
This is the low est instantaneous relative
hum idity since last 1-hour period.
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 20 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
69
0x12
1-hour m aximum relative humidity DIF
70
0xfb
1-hour m aximum relative humidity VIF,
extension table FB
71
0x1a
1-hour m aximum relative humidity VIFE
72..73
0xnnnn
1-hour m aximum relative humidity x 10
In case of error the relative humidity will be
set to 0.
This is the highest instantaneous relative
hum idity since last 1-hour period.
74
0x62
24-hour minimum relative humidity DIF
75
0xfb
24-hour minimum relative humidity VIF,
extension table FB
76
0x1a
24-hour minimum relative humidity VIFE
77..78
0xnnnn
24-hour minimum relative humidity x 10
In case of error the relative humidity will be
set to 0.
This is the low est instantaneous relative
hum idity since last 24-hour period.
79
0x52
24-hour m aximum relative hum idity DIF
80
0xfb
24-hour m aximum relative hum idity VIF,
extension table FB
81
0x1a
24-hour m aximum relative hum idity VIFE
82..83
0xnnnn
24-hour m aximum relative hum idity x 10
In case of error the relative humidity will be
set to 0.
This is the highest instantaneous relative
hum idity since last 24-hour period.
84
0x02
Product status DIF
85
0xfd
Product status VIF, extension table FD
86
0x1b
Product status VIFE, digital input
87..88
0xnnnn
16-bit integer value w ith follow ing bit-m ask:
Bit15: 24-hour toggle bit
Bit14: 10 m inute toggle bit
Bit13..10: Not used
Bit 8..9: Battery level
00b = Em pty
01b..11b (1d-3d) = Level 1 to 3 (full)
Bit 4..7: Tx interval
0d..15d minutes
Bit 3..1: Not used
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 21 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
Bit 0: Sensor failure
- 1 = Sensor failure (sam e as 0x0a in
header status byte)
- 0 = No sensor failure
89
0x0d
Firm w are version DIF
90
0xfd
Firm w are version VIF
91
0x0f
Firm w are version VIFE = “Other softw are
version”
92
0x05
Length of firm w are string
92..96
0xnnnnnnnnnn
Firm w are version string in form at:
M ajor.Minor.PatchLevel
97
0x0F
End of telegram, no more data.
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 22 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
7
Troubleshooting
7 .1
Co l l ec t o r d o es n o t r ec eiv e an y t eleg r am sen t f r o m t h e p r o d u c t
This can be a due the follow ing reasons:
7 .2

The product has not been turned on using the installation procedure, see 4.3.1.

The m aster is not pow ered up or not correctly configured.

The distance to the m aster is not within range.

The m aster antenna is not properly mounted for best perform ance.

The position of the product is inside a m etallic cabinet or is disturbed by other
radio equipm ent.
In f o r m at i o n n o t v i si b l e o n t h e d i sp lay
This can be a due the follow ing reasons:
7 .3

The product has not been turned on using the installation procedure, see 4.3.1.

The LCD contrast is set to a low value.

The battery is empty. Check the serial num ber label of the product when the
product is produced. The lifetim e is 12 years.
Tem p er at u r e v al u e i s i n acc u r at e
The temperature sensor is very accurate, but incorrect positioning of the product m ay
result in unintended temperature variation. Please take the follow ing in consideration
w hen mounting the product:

Do not mount the product close to heat sources (front and rear)

Do not mount the product in direct sunlight

Do not mount the product in the area of a spotlight beam
If the problem persists, please contact Elvaco AB.
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 23 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
8
Technical specifications
8 .1
Ch ar ac t er ist i c s
Ty pe
V al ue
Unit
Co m m ent s
M echanics
Casing m aterial
ABS UL94-V0
-
Protection class
IP20
-
Dim ensions
80 x 80 x 28
mm
Weight
75
g
Antenna Wireless M -Bus
Internal
-
M ounting
Wall
m ounted
White
Electrical
Pow er supply
Internal
battery
Lifetim e
12
Years
Environm ental
Operating temperature range
0 to +50
(CM a10w )
-20 to +55
(CM a11w )
°C
Storage temperature range
-40 to +85
°C
Operating humidity
0 to 95
%RH
No condensation
Temperature sensor
Temperature range
0 to +50
(CM a10w )
-20 to +55
(CM a11w )
°C
Accuracy +10 to +30 °C
+/- 0.2
°C
Accuracy 0 to +10 °C
+/- 0.4
°C
Accuracy -10 to +0 °C
+/- 0.5
°C
Accuracy -20 to +55 °C
+/- 1.5
°C
Humidity sensor
Humidity range
0-100
%RH
Repeatability RH
+/- 0.1
%RH
Accuracy 10 to 90 %RH
+/- 2
%RH
Accuracy 0 to 100 %RH
+/- 4
%RH
User interface
LCD display
Yes
(CM a10w )
-
Display current temperature,
hum idity, m in/m ax values and
configuration.
Button w ith LED
Yes
-
M enu navigation
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 24 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
(CM a10w )
Green LED
Yes
-
Configuration/Activation
Button
Yes
-
Configuration/Activation
Wireless M -Bus
M -Bus standard
EN 13757-4
-
M -Bus com m ands
SND_NR
-
M om entary values
Temperature,
hum idity,
status
-
Historic values
Average
values for
last hour and
last day for
tem perature
and humidity
-
Transm it pow er
10
mW
Sensitivity
-104
dBm
Frequency
868
M Hz
OM S compliant, M ode T1
Band
Table 3 Technical specifications
8 .2
Fac t o r y def au l t s
N am e
V al ue
Language
ENG
Transm it interval
6
Encryption mode
Off
LCD contrast
0
Locked
No
Unit
Co m m ent s
English
m inutes
Tim e betw een SND_NR
telegram s in norm al operation
Can be changed during
installation m ode
Table 4 Factory defaults
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 25 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
9
Type approvals
CM a10w /CM a11w is designed to com ply with the directives and standards listed below .
A p p r oval
D escr i pt i o n
EM C
EN 61000-6-2, EN 61000-6-3
Table 5 Type approvals
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 26 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
10 Safety and environm ent
1 0 .1 Saf et y p r ec au t i o n s
The follow ing safety precautions m ust be observed during all phases of the operation,
usage, service or repair of any CM a10w/CM a11w product. Users of the product are advised
to convey the follow ing safety inform ation to users and operating personnel and to
incorporate these guidelines into all m anuals supplied with the product. Failure to comply
w ith these precautions violates safety standards of design, m anufacture and intended use
of the product. Elvaco AB assum es no liability for custom er’s failure to com ply with these
precautions.
All instructions m ust be carefully read before CM a10w /CM a11w is installed and used. They
contain im portant inform ation about how the product is used properly.
The installation of CM a10w /CM a11w should not be started before the technical
specifications are fully understood. The work m ust be perform ed in the order listed in this
m anual, and only by qualified personnel. The work m ust also be done in accordance w ith
national electrical specifications and applicable local regulations.
In order to avoid the product being dam aged by static electricity, an ESD w ristband should
be worn w hen handling the product.
The labelling of the product m ay not be changed, rem oved or m ade unrecognizable.
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 27 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
11 Docum ent history
V er si o n
D at e
D escr i pt i o n
A u t h or
1.0
2012-04-19
First release
David Vonasek
1.1
2012-09-26
Changes to conform only
w ith T1 product.
David Vonasek
1.2
2013-01-25
Fixed m issing 1-hour,24hour m in/m ax temperature
description in M -Bus
telegram
David Vonasek
1.3
2013-06-12
Added Appendix A
Peter King/Ericha Bloom
1 1 .1 D o c u m en t so f t w ar e an d h ar d w ar e ap p l i an ce
Ty pe
V er si o n
D at e
Hardw are
R1A
2012-09-26
Softw are
1.0.0
2012-09-26
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
Co m m ent s
page | 28 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
12 References
1 2 .1 Ref er en c es
[1] EN-13757-1, EN-13757-2, EN-13757-3, EN-13757-4 (PR 2011)
Comm unication System for m eters and rem ote reading of m eters, Part1, Part2, Part3, Part 4
[2] Open M etering System Specification – Volum e 2 – Prim ary Comm unication, Issue
3.0.1/2011-01-29
1 2 .2 Ter m s an d ab b r ev iat i o n s
A b b rev iat i o n
D escr i pt i o n
Product, Device,
M -Bus slave
In this docum ent, CM a10w /CM a11w
DIF
Data Inform ation Field (M -Bus data clock inform ation)
VIF
Value Inform ation Field (M -Bus value block inform ation)
1 2 .2 .1
N u m b er r ep r esen t at i o n
Decim al numbers are represented as norm al num ber, i.e. 10 (ten).
Hexadecim al num bers are represented w ith prefix 0x, i.e. 0x0A (ten)
Binary num bers are represented with prefix 0b, i.e. 0b00001010 (ten)
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 29 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
13 Appendix A – Exam ple
1 3 .1 D en o m i n at i o n o f v al ues i n r ep o r t s
D en om i n at i on
D escr i pt i o n
serial-number
M -Bus m aster id
device-identification
M -Bus slave id
Created
Tim e stam p
value-data-count
Index at m ultiple telegram.
Usually 0.
m anufacturer
M anufacturer
version
Hardw are version
device-type
M -Bus slave device type
access-number
Num ber of tim es the m eter has been read
status
Status
signature
Reserved for future use
fabrication-no,,inst-value,0,0,0
Id for the w ireless M -Bus m aster CM eX50
act-duration,m inute(s),inst-value,0,0,0
The values age in minutes
rf-level,dbm ,inst-value,0,0,0
Signal strength in dBm
ext-tem p,°c,inst-value,0,0,0
Temperature, m om entary value
ext-tem p,°c,inst-value,0,0,1
Temperature, 1-hour rolling average
ext-tem p,°c,inst-value,0,0,2
Temperature, 24-hour rolling average
ext-tem p,°c,min-value,0,0,0
Temperature, low est value during last 1hour period
ext-tem p,°c,m ax-value,0,0,0
Temperature, highest value during last 1hour period
ext-tem p,°c,min-value,0,0,1
Temperature, low est value during last 24hour period
ext-tem p,°c,m ax-value,0,0,1
Temperature, highest value during last 24hour period
relative-hum idity,%,inst-value,0,0,0
Humidity, mom entary value
relative-hum idity,%,inst-value,0,0,1
Humidity, 1-hour rolling average
relative-hum idity,%,inst-value,0,0,2
Humidity, 24-hour rolling average
relative-hum idity,%,m in-value,0,0,0
Humidity, low est value during last 24-hour
period
relative-hum idity,%,m ax-value,0,0,0
Humidity, highest value during last 24-hour
period
relative-hum idity,%,m in-value,0,0,1
Humidity, low est value during last 24-hour
period
relative-hum idity,%,m ax-value,0,0,1
Humidity, highest value during last 24-hour
period
digital-input,,inst-value,0,0,0
Product status
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 30 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
D en om i n at i on
D escr i pt i o n
other-sw-version,,inst-value,0,0,0
Softw are version
m anufacturer-specific,,inst-value,0,0,0
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 31 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3
CM a10w , CM a11w User's M anual
1 3 .2 D en o m i n at i o n o f v al ues f o r u se i n f i l t er s
D en om i n at i on
D escr i pt i o n
m bus.dib.fabrication-no.0.0.0.0
Id for the w ireless M -Bus m aster CM eX50
m bus.dib.act-duration,m inute(s).0.0.0.0
The values age in minutes
m bus.dib.rf-level.0.0.0.0
Signal strength in dBm
m bus.dib.ext-tem p.0.0.0.0
Temperature, m om entary value
m bus.dib.ext-tem p.0.1.0.0
Temperature, 1-hour rolling average
m bus.dib.ext-tem p.0.2.0.0
Temperature, 24-hour rolling average
m bus.dib.ext-tem p.0.0.0.2
Temperature, low est value during last 1hour period
m bus.dib.ext-tem p.0.0.0.1
Temperature, highest value during last 1hour period
m bus.dib.ext-tem p.0.1.0.2
Temperature, low est value during last 24hour period
m bus.dib.ext-tem p.0.1.0.1
Temperature, highest value during last 24hour period
m bus.dib.relative-humidity.0.0.0.0
Humidity, mom entary value
m bus.dib.relative-humidity.0.1.0.0
Humidity, 1-hour rolling average
m bus.dib.relative-humidity.0.2.0.0
Humidity, 24-hour rolling average
m bus.dib.relative-humidity.0.0.0.2
Humidity, low est value during last 24-hour
period
m bus.dib.relative-humidity.0.0.0.1
Humidity, highest value during last 24-hour
period
m bus.dib.relative-humidity.0.1.0.2
Humidity, low est value during last 24-hour
period
m bus.dib.relative-humidity.0.1.0.1
Humidity, highest value during last 24-hour
period
m bus.dib.digital-input.0.0.0.0
Product status
Cm a10w,Cm a11w T1 Users M anual
English
Public/Published
page | 32 (32)
2013-06-12
Docum ent id: 1090054 Version 1.3