Download User Manual Profinet
Transcript
Absolute value rotary encoder with PROFINET FAQ 8. Question: On using the D410 the error "Synchronization error between Profibus and Profinet" popped up. What is to do? Answer: Both systems have to use the same cycle time. If the Profinet cycle time amounts 1 ms then must use the Profibus the same time. See the next Hardcopy with the settings for 1 ms. 9. Question: What is the different between Encoder Profil 4.0 and 4.1? Answer: G_XIST1 GSDML MAP Parameter 4.0 Position value, left alligned 4.1 Counter value, right aligned Inclusive Telegrams Separate Telegrams 59