"Expert" Startup with Parameter Function
Parameter description
0
Parameter 160
Setpoint n_f1
The setpoint n_f1 is valid if
Parameter 161
•
the setpoint potentiometer f1 is deactivated, i.e. if P102:13 = "1"
•
Parameter P600 Binary inputs = "0"
•
The signal "0" is present at terminal f1/f2 X6: 7,8
Setpoint n_f2
The setpoint n_f2 is valid if
Parameters
170...173
•
The switch f2 is deactivated, i.e. if P102:14 = "1"
•
Parameter P600 Binary inputs = "0"
•
The signal "1" is present at terminal f1/f2 X6: 7,8
Fixed setpoint n0...n3
The fixed setpoints n0...n3 are valid if parameter P600 Binary inputs = "1".
The fixed setpoints n0...n3 can then be selected via the programmed functionality of the
input terminals.
The sign of the fixed setpoint determines the direction of rotation of the motor.
Parameter
8.7.3
Active setpoint
Status
Terminal L
X6:9,10
OFF
Status
Terminal f1/f2 X6:7,8
P170
n0
OFF
P171
n1
ON
OFF
P172
n2
OFF
ON
P173
n3
ON
ON
Motor parameters
Parameter 300
Start/stop speed
This parameter defines the smallest speed request which the inverter sends to the motor
when enabled. The transition to the speed determined in the setpoint selection is made
using the active acceleration ramp.
Parameter 301
Minimal speed (when switch f2 is deactivated)
This parameter defines the minimum speed nmin of the drive.
The drive does not fall below this speed value even when the setpoint specification is
slower than the minimum speed.
Parameter 302
Maximum speed (when switch f1 is deactivated)
This parameter defines the maximum speed nmax of the drive.
The drive does not exceed this speed value even when the setpoint specification is
higher than the maximum speed.
If you set nmin > nmax, then the value set in nmin applies to the minimum speed and the
maximum speed.