Download INSTALLATION MANUAL
Transcript
444 SYSTEM CONFIGURATION 444444 System configuration In case of one outdoor unit connected •• From outdoor unit to the farthest indoor unit: a+f < = 150m, a+p < = 150m (actual pipe length) •• From the first separation tube to the farthest indoor unit: f< = 60m, p < = 60m (actual pipe length) •• Difference in height between outdoor units and indoor units (H1) 50m: For the indoor unit stated below 40m: For the outdoor unit stated below •• Difference in height between indoor units and indoor units H2 < = 15m, H3 < = 15m •• Total pipe length a+f+h+j+l+n+p+q+s+u < = 700m •• Total refrigerant amount < = 31.5kg FFFFFA Outdoor unit (Master) h j n Indoor unit Indoor unit Indoor unit H1 Indoor unit p q s Indoor unit u Indoor unit H2 Indoor unit H3 Indoor unit FFFFFB Outdoor unit 1 (Master) Outdoor unit 2 (Slave) H4 a b e f h j l Indoor unit In the case of three outdoor units connected •• From outdoor unit to the farthest indoor unit: a+e+f < = 150m, a+e+p < = 150m (actual pipe length) •• From the first separation tube to the farthest indoor unit: f< = 60m, p < = 60m (actual pipe length) •• Difference in height between outdoor units and indoor units (H1) 50m: For the indoor unit stated below 40m: For the outdoor unit stated below •• Difference in height between indoor units and indoor units (H2,H3) H2 < = 15m, H3 < = 15m •• Difference in height between outdoor unit and outdoor units (H4) H4 < = 0.5m •• From outdoor unit to outdoor unit branch kit a< = 3m, b < = 3m, c < = 3m •• Between the farthest outdoor unit to the first outdoor unit branch kit b+d < = 12m, c+d < = 12m •• Total pipe length a+b+c+d+e+f+h+j+l+n+p+q+s+u < = 1000m •• Total refrigerant amount < = 94.5kg •• Outdoor unit capacity Master > = slave 1 > = slave 2 NNNNNN • If the outdoor temperature during cooling operation is expected to be –5 °C or less, do not install the outdoor unit lower than the indoor unit. ・Please refer to “8.3.2. Checking total amount of refrigerant and calculating the amount of refrigerant charge to be added” for the total amount of refrigerant. l Indoor unit In case of two outdoor unit connected •• From outdoor unit to the farthest indoor unit: a+e+f < = 150m, a+e+p < = 150m (actual pipe length) •• Difference in height between outdoor units and indoor units (H1) 50m: For the indoor unit stated below 40m: For the outdoor unit stated below •• From the first separation tube to the farthest indoor unit f< = 60m, p < = 60m (actual pipe length) •• Difference in height between indoor units and indoor units (H2, H3) H2 < = 15m, H3 < = 15m •• Difference in height between outdoor unit and outdoor units (H4) H4 < = 0.5m •• From outdoor unit to outdoor unit branch kit a< = 3m, b < = 3m •• Total pipe length a+b+e+f+h+j+l+n+p+q+s+u < = 1000m •• Total refrigerant amount < = 63kg •• Outdoor unit capacity Master > = slave a f n Indoor unit Indoor unit Indoor unit Indoor unit H1 p q s Indoor unit Indoor unit u H2 Indoor unit H3 Indoor unit FFFFFC Outdoor unit 1 (Master) Outdoor unit 2 (Slave 1) Outdoor unit 3 (Slave 2) H4 a b c d e f j h Indoor unit l Indoor unit H1 n Indoor unit Indoor unit Indoor unit p q Indoor unit s Indoor unit u H2 Indoor unit H3 Indoor unit En-11 English CAUTION •• When connecting multiple outdoor units, set the nearest outdoor unit to the indoor unit on the refrigerant pipe as the master unit. •• When connecting multiple outdoor units, install the outdoor unit with the largest nominal system capacity nearest to the indoor unit and on the refrigerant pipe, followed by those with less nominal system capacities. •• Always keep to the limit on the total amount of refrigerant.Exceeding the limit on the total amount of refrigerant when charging will lead to malfunction.