Download USER MANUAL TREF GB
Transcript
Codification This codification describe the whole INNOV@ range. All operating modes are not available on each type of unit. Type of unit DM DH IN Medium range height 1875mm High range height 1998mm ENERGY range : eDrive unit with EC plug fan and BLDC compressor Operating mode A W Z F C : : : : : Direct expansion with remote condenser Direct expansion water condensed with remote dry-cooler Direct expansion city water condensed Direct expansion water condensed with remote dry-cooler and indirect Free-cooling Chilled water unit Dual cooling units In this case this is combination of unit with operating mode above and chilled water to work with chiller. Which provide more safety to your installation. D K Q : : : Direct expansion with remote condenser +chilled water coil Direct expansion water condensed with remote dry-cooler+chilled water coil Direct expansion city water condensed+chilled water coil Airflow configuration U D X : : : Upflow Downflow Displacement Type of fan C R : : Centrifugal double inlet forward curve EC plug fan Nominal capacity Capacity in kW (in this case 11kW) DMAUR0110 Refrigerant circuit 0 2 4 5 INNOV@ ENERGY -AGU-1407-E : : : : 1 or No compressor (CW) 2 compressors / 2 circuits 4 compressors / 2 circuits 1 compressor / 1 circuit •2•