Download User Guide - Invertek Drives
Transcript
Optidrive HVAC User Guide V2.00 Optidrive HVAC Start Up Guide OPTIDRIVE HVAC (IP55 Enclosure). Mechanical Mounting Information can be found in section 3.7 on page 16 HVAC Display (Status, Diagnostics, and Programming) Keypad Operation can be found in section 5.5 on page 27 Hardware Enable Circuit Link the terminals as shown, optionally through contacts to enable drive operation. Supply Voltage Control Terminal Configuration based on factory settings Run / Stop 10K Pot Close the switch to run (enable) Open the switch to stop Fuses or MCB Check Drive Rating info in section 13.4 PE L1 L2 L3 AC Supply Connection 200 – 240 Volts + / - 10% 380 – 380 Volts + / - 10% Check Drive Input Voltage Ranges on page 47 Motor Cable For correct cable size, see Technical Data on page 47 Observe the maximum permissible motor cable length. For Motor cable lengths > 50 metres, an output filter is recommended. Use a screened (shielded cable). The shield should be bonded to earth at both ends. Motor Connection Check for Star or Delta connection according to the motor voltage rating in section 4.5. Motor Nameplate Details Motor Rated Voltage: P1-07 Motor Rated Current: P1-08 Motor Rated Frequency: P1-09 Motor Rated Speed (Optional): P1-10