Download Installation Instructions and User Guide 15mm

Transcript
Installation Instructions and User Guide
15mm & 22mm
Thermostatic Mixing Valve
TMV3 / TMV2 Combined Valve
C85079
C85081
C85080
C85082
It is important that these guidance notes are read and fully understood prior to product installation
The Pegler Yorkshire Model P405 mixing valve must be installed in accordance with the reg
local water company and the Water Supply (Water Fittings) Regulations 1999.
Approvals
Bulldog TMV When used as a TMV3
(TYPE3) valve:
IMPORTANT INTRODUCTION NOTES
The valves covered by these instructions have been
tested and certified as being in compliance with BS
7942:2000 and NHS Estates Model Engineering
Specification D 08.
Valves operating outside the requirements of these
standards are not covered by the TMV3 Scheme and
are not guaranteed to operate as Type 3 valves.
alves
The installer should be aware of his duty of care and
responsibility in ensuring that compliance with
regulations is maintained. The valve is not guaranteed
to function correctly to the TMV3 specification
unless it is installed and used in accordance with
these instructions.
Regular servicing is essential to ensure continued safe
operation of this thermostatic mixing valve. The
operating
outside
thesemust
conditions
recommended
service interval
be based on can
the not
valve response to the in-service cold water failure
test results.
strainers
should
beunder
installed
as close
as practicable
This product
is certified
the BuildCert
TMV3 scheme
and has beento
independently tes
recognised
test laboratory
WRc-NSF valve
and is a and
Watershould
Regulations
Advisorybe
Scheme (WRAS)
the
location
of the mixing
always
product and listed in the Water Fittings and Materials Directory.
in an accessible location.
Installation
Before
thebehot
andoncold
water
supply
Separateinstallation,
isolation valves must
installed
the hot
and cold
water inlet supplies. To ens
performance
of the
mixingflushed
valve, the to
isolating
valvesany
should preferably be ful
systems
must
bethermostatic
thoroughly
remove
always be fully open during operation.
dirt/debris
that
may have
accumulated.
do
The mixing valve
is supplied
with filter
elements but it isFailure
advisableto
to additionally
install
on the hot and cold water supplies. The isolating valves and strainers should be
soY-strainers
may
adversely
affect
the
performance
of
the
close as practicable to the location of the mixing valve and should always be in an accessib
mixing valve.
Before installation, the hot and cold water supply systems must be thoroughly flushed to re
dirt/debris that may have accumulated. Failure to do so may adversely affect the performa
mixing valve.
Conditions of normal Use
CONDITIONS OF NORMAL USE
Table 1
Table 1
Operating Range
High Pressure
Low Pressure
Maximum static pressure - bar
10
10
Hot & cold flow pressure - bar
1.0 to 5
0.2 to 1
Hot supply temperature - °C
52 to 65
52 to 65
Cold supply temperature - °C
5 to 20
5 to 20
Minimum hot inlet to mixed outlet temperature differential =10°C
Minimum hot inlet to mixed outlet temperature
differential =10°C
Note: Valves operating outside these conditions can
be guaranteedby
by the
to operate
as Type
be not
guaranteed
theScheme
Scheme
to operate
as Ty
3 valves.
The highest flow rates will be achieved under balanced
pressure conditions, but the pressure at the valve
This rates
Bulldog will
TMV by
Yorkshireunder
Model P405
hest flow
bePegler
achieved
balanced pressure
conditions, but the pressure at the val
inlets must be within a ratio of 5:1 under flow
in-line thermostatic mixing valve, available in
ust be 15mm
within
a
ratio
of
5:1
under
flow
conditions
and
the
and
ofofpipework
conditionssize
and the
sizelayout
and layout
pipework andand fitting
and 22mm sizes, is intended to be fitted into
fittings
must
take
this
into
account.
ke this applications
into account.
where the reliable control of hot water
temperature is necessary to prevent scalding. In the
event of cold water supply failure, the product will
shut off the hot water supply.
FITTING
Before installation, the system operating conditions of
pressures, hot
water
temperature
and hot and and hot a
Water the
regulations
nstallation,
system operating conditions of inletinlet
pressures,
hot
water
temperature
cold water flow rates should be determined and
ter flow rates should be determined and confirmed confirmed
to be within
thethe
expected
conditions
of norm
to be within
expected conditions
of
The Bulldog TMV mixing valve must be installed in
accordance with the regulations of the local water
company and the Water Supply (Water Fittings)
Regulations
operate
in1999.
either a high pressure setting
normal use.
Valves must operate in either a high pressure setting
must
or a low
pressure
setting
valves
not
or a low
pressure setting
valves
are not are
capable
of capable o
operation
with,
for instance
hot water
supply in
on with,Approvals
for instance hot water supply in one pressure
range
and
cold water
supply
inone
the other
cold water supply in the other
e range. In these conditions it is necessary to eitherpressure
boostrange
oneandpressure
or reduce the other so
pressure range. In these conditions it is necessary to
This product
is certified
the BuildCert
TMV3 range.
h supplies
are within
a under
common
pressure
either boost one pressure or reduce the other so
scheme and has been independently tested by the
that both supplies are within a common pressure
recognised test laboratory WRc-NSF and is a Water
range.
Regulations Advisory Scheme (WRAS) approved
product
and mixing
listed in the
Water is
Fittings
and Materials
location
of the
valve
important
to ensure Correct
that itlocation
is accessible
commissioning
of the mixingfor
valve
is important to
Directory.
ensure that it is accessible for commissioning and
g.
servicing.
Installation
• The valve body is clearly marked with Separate
isolation
valves
must
be
installed
on
the
hot
for Cold and a valve body is clearly marked with ‘C’ for Cold and a ‘C’
blue
and cold water inlet supplies. To ensure proper
blue indicator and
cator and
‘H’
for
Hot
and
a
red
indicator.
performance of the thermostatic mixing valve, the
‘H’ for Hot and valve must
correctly
connected
to the
isolatingbe
valves
should preferably
be full bore
and respective
supplies.
a red indicator. The always be fully open during operation.
valve must be The mixing valve is supplied with filter elements but
correctly connected it is advisable to additionally install Y-strainers on the
to the respective hot and cold water supplies. The isolating valves and
supplies.
and
2
use of sealing compounds must be avoided since
they may intrude into the water supply and
this arrangement is used, the requirements for isolation valves and Y-strainers
regarded as fulfilled.
• The use of sealing
compounds
must
avoided valve
Exploded
view
ofbeangled
since they may intrude into the water supply and impair the valve performance.
Exploded view of angled valve assembly
assembly
The Pegler Model Yorkshire P405UA mixing valve is optionally p
the tailpiece arrangement shown above. This allows the connec
be parallel to the mixed water outlet for ease of piping layouts.
non-return valves, filters, isolation valves and test points
The Bulldog TMV thermostatic mixing valve is supplied
with the tail pieces, inlet filter screen and main body
gasket seals separately located in the packing box.
Each tail piece comprises: a housing with union nut
and an internally fitted, WRAS approved non-return
valve.
The assemblies comprise an integral full bore ball valve and inthis arrangement is used, the requirements for isolation valves
regarded as fulfilled.
Assembly Procedure
•
•
•
•
•
•
Unpack the main valve assembly and check that the Exploded view of angled valve assembly
bores are free of debris and the end sealing faces are clean.
Unpack the two tailpieces and confirm they are complete with union nuts and compression nuts
and olives.
Locate the sealing gaskets, insert them into the union nuts against the faces of the tailpieces and
screw the union
nuts onto the valve until a tight APPLICATION
seal has been made.
Application
Remove the compression nuts and olives from the The Pegler
Yorkshire
Model
mixing valve has been independently t
tailpieces.
Locate the
inlet filter screens
andP405
insert thermostatic
The Bulldog TMV thermostatic mixing valve has
them
intorequirements
the bore of the tailpieces
to the the
of BS up7942:2000
and NHS
D08 and certified
as complying
with the
been independently
tested by WRc-NSF
against
shoulder.
the requirements
of BS 7942:2000
and
NHSbelow.
D08
Scheme
and
is
suitable
for
use
in
the
designations
shown
in
the
table
Assemble the valve to the pipework and ensure the andAPPLICATION
certified as complying with the requirements
hot and cold water pipes have full penetration into of the TMV3 Scheme and is suitable for use in the
The use
Pegler ‘HP’
Yorkshire
Model P405
mixing valve has been
theValves
tailpiece. approved for designation for
only:athermostatic
water
designations
shown
in theIftable
below. supply is fed by
the requirements of BS 7942:2000 and NHS D08 and certified as com
Tighten the compression nuts ensuring that the end supply pressure should be verified to ensure
theis suitable
conditions
oftheuse
are appropriate
for
Scheme and
for use in
designations
shown in the table
of the pipe remains in contact with the filter
Valves approved for designation for use ‘HP’ only:element.
If a water supply is fed by gravity then the supply
Valves approved for designation for use ‘HP’ only:- If a water s
pressure
should
be verified
to ensure
the the
conditions
supply
pressure
should
be verified
to ensure
conditions of use are
Exploded view of tail pipe assembly
Exploded view of tail pipe assembly
of use are appropriate for the valve.
Table 2 – Required maximum set outlet
Table 2 – Required maximum set outlet
temperatures
at commissioning.
temperatures
at commissioning.
Table 2 – Required maximum set outlet temperatures at com
Application
Bidet
Designation
HP-B
Application
Designation
Maximum
Set Mixed
Water Temperature
Bidet
HP-B
LP-B
38°C
Shower
HP-S
Maximum Set Mixed
Water Temperature
38°C
41°C
The Bulldog
TMV mixingP405UA
valve is optionally
provided
LP-B valve
LP-S
The Pegler
Model Yorkshire
mixing
is optionally provided with angled
assemblies in lieu of
with angled
assemblies
in lieuabove.
of the tailpiece
Washbasin
HP-W
41°C to
the tailpiece
arrangement
shown
This
allows the connections
of the hot
and cold water supplies
Shower
HP-S
41°C
arrangement shown
above. This allows
the connections
LP-Wassemblies incorporate
be parallel to the mixed water outlet for ease of piping layouts. The angled valve
of the hot and cold water suppliesLP-S
to be parallel to
non-return valves, filters, isolation valves and test points
Bath*
HP-T44
44°C
the mixed water
outlet for ease ofHP-W
piping layouts. The
Washbasin
41°C LP-T44
angled valve assemblies incorporate non-return valves,
Bath*
HP-T46
46°C
LP-W
filters, isolation valves and test points.
(assisted)
LP-T46
The assemblies
comprise
an integral
fullfull
bore
strainer in an angled housing. When
The assemblies
comprise
an integral
boreball
ballvalve and in-line
*22mmonly
only
this arrangement
is used,
the in
requirements
for isolation valves *22mm
and Y-strainers
previously mentioned are
valve and in-line
strainer
an angled housing.
regarded
as fulfilled.
When
this arrangement is used, the requirements for
The range of available temperature adjustment is 35°C to 48°C BUT
isolation valves and Y-strainers previously mentioned
theThe
terminal
should
never be
set to a temperature
tha
range offitting
available
temperature
adjustment
is
areview
regarded
as fulfilled.
outlet
for the
application
(Table 2).
Exploded
of angled
valve assembly
35°Ctemperature
to 48°C BUT the
mixed
water temperature
at the terminal fitting should never be set to a
Note:
temperature that exceeds the maximum set outlet
46°C is the maximum recommended mixed water temperature from t
temperature for the application (Table 2).
3
takes account of the allowable temperature tolerances inherent in the
losses in metal baths.
46°C is not a safe bathing temperature for adults or children.
Note:
•
•
46°C is the maximum recommended mixed water
temperature from the bath tap. The maximum
temperature takes account of the allowable
temperature tolerances inherent in thermostatic
mixing valves and temperature losses in metal baths.
46°C is not a safe bathing temperature for adults
or children.
Bath*
HP-T44
44°C
The British Burns
Association recommends 37°C to
LP-T44
37.5°C
Bath* as a comfortable
HP-T46 bathing temperature
46°C for
children. In premises
(assisted)
LP-T46 covered by the Care Standards
Act 2000, the maximum mixed water outlet
temperature
*22mm
only is 43°C.
using a close fitting spanner, reduce the mixed outlet temperature by turning clockwise.
increase the mixed water outlet temperature by turning counter clockwise.
When the valve has been installed with the correct
conditions of use it is advised that the valve is
subjected to exercise prior to the commissioning at
the application temperature. With hot and cold water
flowing through the valve, operate the valve from full
cold to full hot at least three times.
With the valve at the full cold position bring the valve
to the correct application temperature by turning the
spanner counter clockwise. If the valve overshoots
thisthe
temperature,
returntemperature
the valve to theatfull cold
The range
of available temperature
mixed water
COMMISSIONING
(TMV 3) adjustment is 35°C to 48°C BUT
condition,
and the
resetmaximum
it to the correct
the terminal fitting should never be set to a temperature that
exceeds
set temperature
+0-2°C. Do not set a valve on a lowered temperature
valve must be
under (Table
normal site
outlet The
temperature
forcommissioned
the application
2).
as this will not provide consistent operation.
system conditions and after establishing supply
Note: conditions with the hot and cold water supplies open,
When
set maximum
to the required
temperature for
the systemrecommended
running to allow
temperatures
and
46°C is leave
the maximum
mixed
water temperature
from
the the
bathvalve
tap.isThe
temperature
the applicationmixing
carry out
5 cold
isolation tests
takes account
ofto
the
allowable
valves
andwater
temperature
pressures
stabilise
and temperature
be checked. tolerances inherent in thermostatic
to further exercise the valve.
losses in metal baths.
commissioning,
thefor
following
46°C isPrior
nottoa commencing
safe bathing
temperature
adults or children.
Commissioning Test sequence
checks should be carried out.
The British Burns Association recommends 37°C to 37.5°C as a comfortable bathing temperature for children.
adjust
thebring
temperature
water
in
• Thecovered
designation
of the
thermostatic
valve
maximum
In premises
by the
Care
Standards mixing
Act
2000,
the
mixed
water
outlet
is
43°C.
With
the
valve
at the fullAfter
cold
position
thetemperature
valveoftothe
themixed
correct
application
tempera
accordance
withovershoots
the valve application
(see Table
matches the application.
spanner counter clockwise.
If the valve
this temperature,
return the valve to
2)
and
the
carry
out
the
following
sequence:
COMMISSIONING
(TMV 3)and temperaturescondition,
• The supply pressures
are withinand
reset it to the correct temperature +0-2°C. Do not set a valve on a lower
1.Record
the temperature of the hot and cold water this will not provide consistent
operation.
the operating range of the valve.
supplies.
The valve
must be valves
commissioned
under
site system conditions
and after establishing
• Isolating
and strainers
are normal
provided.
When
set to2.Record
the system
required
temperature
forthe
the
application
therunning
temperature
of
mixed
water carry
at theout
5 cold wa
supply conditions
with
the hot and
water
supplies
open,is leave
the
to allow
temperatures
• The supply
temperatures
arecold
within
the
rangethe
valve
to further
largest draw-off flow rate.
and pressures
to stabilise
checked.
permitted
for the and
valvebeand
by guidance
exercise the valve.
3.Record the temperature of the mixed water flow information on the prevention of legionella etc.
Commissioning
Testbe
sequence
carried
at a smaller
Prior to commencing commissioning, the following
checks should
out. draw-off flow rate, which shall be measured.
If all these conditions are met, proceed to set the
After adjust
temperature
of thethe
mixed
accordance
with thevalve
valve application
4.Isolate
cold water
water in
supply
to the mixing
• temperature
The designation
of the below.
thermostatic
mixing
matches
the
application.
as described
The Bulldog
TMVvalvethe
2) and the carry out the following
sequence:
and range
monitor
• thermostatic
The supply mixing
pressures
temperatures
ofthe
themixed
valve.water temperature recording valveand
is supplied
factoryare
set within the operating
1. Record the temperature of the hot and cold water supplies.
the maximum temperature achieved and the final • atIsolating
andmay
strainers
are adjusted
provided.after
43°C butvalves
the valve
be simply
2. Record the temperature of the mixed water at the largest draw-off flow
stabilised
temperature.
• installation.
The supply temperatures are within the range permitted
forthe
the
valve and
bythe
guidance
information
3. Record
temperature
of
mixed water
flow at a smaller draw-off fl
5.Record the equipment, thermometer etc. used for on the prevention of legionella etc
which shall be measured.
thethe
measurements.
If all these
conditions
met, proceed
to set
the temperature
as described
below.
The mixed
waterare
temperature
at the
terminal
fitting
4. Isolate
cold
water
supply to the mixing valve and monitor the mixed
Note:factory
The final
stabilised
should
not and the fina
The Pegler
model
thermostatic
mixing valve temperature
is supplied
setthe
at maximum
43°C temperature
but temperature
the valve
may
mustYorkshire
never exceed
theP405
maximum
temperature
recording
achieved
exceed the values in Table 3.
be simply
adjusted
after
installation.
setting
for the
particular
application (See Table 2). temperature.
5. Record
the equipment,
etc. used for the measurements.
The mixed
temperature
at the
terminal
fitting
must never
exceed thermometer
the maximum
Note, water
It is not
possible to install
one
thermostatic
Note: The final
stabilised
temperature
should
not
exceed the
values
in Table3
temperature
setting
for the
particular
application
(See
Table
2). 3
Note,
It
is to
not
possible
to
install
mixing valve
to supply
two
differing applications
Table
– Guide
maximum
stabilised
one thermostatic
mixing valve
tohigher
supply
two differing
applications
unlessrecorded
the temperature
unless the temperature
of the
setting
is
temperatures
during of the
higherlimited
settingtoisthat
limited
thatapplication.
of the lower application. commissioning
of thetolower
Table 3 – Guide to maximum stabilised temperatures recorded during comm
• •Remove
capon
ontop
topofofthe
the valve with the supplied Allen key or other suitable tool.
Removethe
the plastic
plastic protective
protective cap
Application
Mixed water temperature °C
valve with the supplied Allen key or other suitable Bidet
40
tool.
o using a close fitting spanner,
Shower
43
reduce theWashbasin
mixed outlet
43
temperature
turning
Bath by
(44°C
fill)
46
clockwise.
Bath (46°C fill)
48
o increase the mixed water
outlet temperature by turning counter
clockwise.
4
After correct commissioning secure the protective cap u
supplied screw. The Pegler Yorkshire model P405 is sup
two protective caps. One blue TMV 3 cap and one whit
Ensure that the blue colour TMV 3 cap is fitted as this w
With an acceptable mixed water temperature complete
the Commissioning test sequence detailed above. If
the final mixed water temperature is greater than the
values in Table 3 and/or the maximum temperature
exceeds the corresponding value from the previous
test results by more than about 2°C the need for
service work is indicated (see TMV servicing and
cleaning instructions).
In-service tests should be carried out with a frequency
which identifies a need for service work before an
unsafe water temperature can result.
Frequency of in-service testing
6 to 8 weeks after commissioning carry out the test
sequence detailed above.
12 to 15 weeks after commissioning carry out the test
sequence detailed above.
Depending on the results obtained, the following
course of actions must be followed:
After correct commissioning secure the protective cap
using the supplied screw. The Bulldog TMV model is
supplied with two protective caps. One blue TMV 3 cap
and one white TMV 2 cap. Ensure that the blue colour
TMV 3 cap is fitted as this will indicate the valve has
been commissioned to the TMV 3 standard.
•
•
•
•
In Service Testing (TMV 3)
The purpose of in-service testing is to regularly
monitor and record the performance of the
thermostatic mixing valve. Deterioration in
performance can indicate the need for service work on
the valve and/or water supplies.
Carry out the test sequence detailed below using
the same or equivalent equipment as used for
commissioning the valve.
•
•
•
•
Check the designation of the thermostatic valve matches the application.
Check that the supply pressures and temperatures are within the operating range of the valve.
Check that the supply temperatures are within the range permitted for the valve and by guidance
information on the prevention of legionella etc
Check there have been no significant changes in inlet supply temperatures and pressures since
commissioning or the previous in service test.
If significant changes have occurred it is
recommended to re-commission the valve.
If the mixed water temperature has changed
significantly from the previous test results (e.g.>1°C),
record the change and before re-adjusting the mixed
water temperature carry out the following checks;
•
•
•
If no significant changes (e.g.<1 °C) in mixed
water temperature are recorded between commissioning and testing at 6 to 8 weeks, or between commissioning and testing at 12 to
15 weeks, the next in-service test can be deferred to 24 to 28 weeks after commissioning.
If small changes (e.g.1 to 2 °C) in mixed water temperature are recorded in only one of
these periods, necessitating adjustment of the mixed water temperature, then the next inservice
test can be deferred to 24 to 28 weeks after commissioning.
If small changes (e.g.1 to 2 °C) in mixed water temperature are recorded in both of these
periods, necessitating adjustment of the mixed water temperature, then the next in-service
test should be carried out at 18 to 21 weeks after commissioning.
If significant changes (e.g. >2 °C) in mixed water temperature are recorded in both of these
periods, necessitating service work, then the next in-service test should be carried out at 18
to 21 weeks after commissioning.
The general principle to be observed after the first 2 or 3 in-service test is that the intervals of future
tests should be set to those which previous tests have shown can be achieved with no more than a
small change in mixed water temperature.
It is recommended that In-Service Tests are carried out once every 6 months as a minimum.
Note:
All in-line or integral strainers are clean
Any in-line or integral non-return valves or other anti-backsiphonage devices are in good working order.
Any isolation valves are fully open.
5
If there is a residual flow during the commissioning or in
service test during the cold water supply isolation test
then this is acceptable providing the temperature of the
water seeping from the valve is no more than 2°C above
the designated maximum mixed water outlet temperature
setting of the valve as defined in Table 2.
Temperature readings should be taken at the normal flow
rate after allowing the system to stabilise. The sensing
part of the thermometer probe must be fully submerged
in the water that is to be tested.
The mixing valve is supplied with filter elements but
it is advisable to additionally install Y-strainers on the
hot and cold water supplies. The isolating valves and
strainers should be installed as close as practicable to
the location of the mixing valve and should always be
in an accessible location.
Any TMV that has been adjusted or serviced must be
re-commissioned and re-tested in accordance with the
manufacturer’s instructions.
Before installation, the hot and cold water supply
systems must be thoroughly flushed to remove any
dirt/debris that may have accumulated. Failure to do
so may adversely affect the performance of the mixing
valve.
Bulldog TMV When used as a TMV2
(TYPE 2) Valve
IMPORTANT INTRODUCTION NOTES
The valves covered by these instructions have been
tested and certified as being in compliance with BS
EN 1111:1999 and BS EN 1287:1999.
CONDITIONS OF NORMAL USE
CONDITIONS OF NORMAL USE
Table 4
Valves operating outside the requirements of these
standards are not covered by the TMV2 Scheme and
are not guaranteed to operate as Type 2 valves.
Table 4
Operating Range
Maximum static pressure - bar
Hot & cold flow pressure - bar
Hot supply temperature - °C
Cold supply temperature - °C
Mixed water temperature - °C
BS EN 1111
High Pressure
10
1.0 to 5
55 to 65
≤ 25
Maximum 46
BS EN 1287
Low Pressure
10
0.1 to 1
55 to 65
≤ 25
Maximum 46
The installer should be aware of his duty of care and
responsibility in ensuring that compliance with
Minimum hot inlet to mixed outlet temperature differential =10°C
Minimum hot inlet to mixed outlet temperature
regulations is maintained. The valve is not guaranteed Note: Valves
operating outside these conditions can not be guaranteed by the Scheme to operate as T
2 valves. differential =10°C
to function correctly to the TMV2 specification
unless it is installed and used in accordance with
The highest flow rates will be achieved under balanced pressure conditions, but the pressure at the va
Note:
Valves
outside
these
conditions
can
inlets must
be within
a ratio operating
of 5:1 under flow
conditions
and the
size and layout
of pipework and fittin
these instructions. Regular servicing is essential to
must take this into account.
not be guaranteed by the Scheme to operate as Type
ensure continued safe operation of this thermostatic
2 valves.
mixing valve. The recommended service interval is no FITTING
greater than 12 months.
Before installation, the system operating conditions of inlet pressures, hot and cold inlet temperature a
hot and cold
flow rates
should
be determined
confirmedunder
to be within
the expected condition
Thewater
highest
flow
rates
will be and
achieved
balanced
of normal use shown in Table 4.
pressure conditions, but the pressure at the valve
This Bulldog TMV thermostatic mixing valve, available
must
operate
in either
high pressure
setting
a lowunder
pressureflow
setting. These valves are not
inlets
must
be awithin
a ratio
ofor5:1
in 15mm and 22mm sizes, is intended to be fitted into Valves
capable of operation with, for instance hot water supply in one pressure range and cold water supply
theconditions
size and
pipework
and
the other conditions
pressure range.and
In these
it is layout
necessaryof
to either
boost one
pressure or reduce th
applications where the reliable control of hot water
other so that
both supplies
within
a common
pressure range.
fittings
mustare
take
this
into account.
temperature is necessary to prevent scalding. In the
If your water supply cannot meet these conditions then the valve cannot be guaranteed to operate as
Type 2 valve.
event of cold water supply failure, the product will
shut off the hot water supply.
OperatingFITTING
pressures above 5.0 Bar will require the installation of a pressure reducing valve.
Water regulations
The Bulldog TMV mixing valve must be installed in
accordance with the regulations of the local water
company and the Water Supply (Water Fittings)
Regulations 1999.
Approvals
This product is certified under the BuildCert TMV2
scheme and has been independently tested by an
approved testing laboratory WRc-NSF and is a Water
Regulations Advisory Scheme (WRAS) approved
product and listed in the Water Fittings and Materials
Directory.
Correct location of the mixing valve is important to ensure that it is accessible for commissioning and
servicing.
Before installation, the system operating conditions
of inlet pressures, hot and cold inlet temperature and
The valve body is clearly marked with ‘C’ for Cold and a blue
hotand
and
flow
rates should be determined
indicator,
‘H’ cold
for Hotwater
with a red
indicator.
The valve must be correctly connected to the respective supplies.
and confirmed to be within the expected conditions
of normal use shown in Table 4.
•
•
The use of sealing compounds must be avoided since they may intrude into the water supply an
impairValves
the valvemust
performance.
operate in either a high pressure setting
•
The valve must be so installed that it is readily accessible for commissioning and maintenance wh
beingcapable
installed in of
accordance
with TMV2.
operation
with, for instance hot water
•
The valve must be installed with isolation valves on both the hot and cold water systems as close
possible
the valve;
so as to allow
the valve
be commissioned
and it
tested
theto other
pressure
range.
In to
these
conditions
is correctly.
or a low pressure setting. These valves are not
supply in one pressure range and cold water supply in
necessary
either
pressure
orwater
reduce
thetherefore in-line
The valve
is suppliedto
with
integralboost
strainersone
on the
hot and cold
supplies
strainers
should
be required.
other
sonotthat
both supplies are within a common
•
pressure range.
If your water supply cannot meet these conditions
then the valve cannot be guaranteed to operate as a
Type 2 valve.
Installation
Separate isolation valves must be installed on the hot
and cold water inlet supplies. To ensure proper
performance of the thermostatic mixing valve, the
isolating valves should preferably be full bore and
always be fully open during operation.
Operating pressures above 5.0 Bar will require the
installation of a pressure reducing valve. Correct
location of the mixing valve is important to ensure
that it is accessible for commissioning and servicing.
6
Exploded view of tailpiece assembly
• The valve body is Exploded view of tail pipe assembly
ld and a clearly
blue marked with ‘C’ for Cold and a blue indicator and
‘H’ for Hot and supplies.
a red indicator. The valve must be
Pegler Model Yorkshire P405UA mixing valve is optionally provided with an
The
correctly connected the tailpiece
arrangement shown above. This allows the connections of the hot
to the respective
ease
piping
layouts.
angled valv
supplies. be parallel to the mixed water outlet
The for
Bulldog
TMV of
mixing
valve is
optionallyThe
provided
they may intrude into the water supply
and
The
Pegler Model Yorkshire P405UA mixing valve is optionally p
with
angledand
assemblies
in lieu of the tailpiece
non-return valves, filters, isolation
valves
test
points
the tailpiece
arrangement shown above. This allows the connec
• The use of sealing compounds must be avoided arrangement shown above. This allows the connections
be parallel
to
theand
mixed
outlet for
ease
of piping
since they may intrude into the water supply and
of the hot
cold water
water supplies
to be
parallel
to the layouts.
non-return
filters,forisolation
valveslayouts.
and test points
impair the valve performance.
mixedvalves,
water outlet
ease of piping
spective
since
g valve is supplied with the tail pieces, inlet filter
The assemblies comprise an integral full bore ball
ed in the
packing
box.
• The
valve must
be so installed that it is readily valvefull
andbore
in-line ball
strainer
in an angled
housing. strainer in a
The
assemblies
comprise
an
integral
valve
and in-line
accessible forfitted,
commissioning
andapproved
maintenance non-return
When this arrangement is used, the requirements for
and an internally
WRAS
arrangement
is used,
requirements
for
valves
and
when being this
installed
in accordance with
TMV2. theThe
assemblies
comprise
an integral
full bore
ballY-strainers
valve
isolation valves
andisolation
strainers
previously
mentioned
are and inregarded as fulfilled.
this arrangement
is used, the requirements for isolation valves
regarded as fulfilled.
•
The valve must be installed with isolation valves on regarded as fulfilled.
both the hot and cold water systems as close as
Exploded view of angled valve assembly
possible to the
valve; so asview
to allow
valve tovalve
be Exploded
of the
angled
assembly
Exploded view of angled valve assembly
commissioned and tested correctly.
that the bores are free of debris and the end sealing
are
• The valve is supplied with integral strainers on the hot and cold water supplies therefore in-line
complete
nuts and compression
strainerswith
shouldunion
not be required.
nuts
• Thenuts
valve is
fitted with
integral
“listed”
non-return
the union
against
the
faces
of the
tailpieces
and
valve cartridges which command the water supply,
tight seal
has been
made. valve is protected therefore
the thermostatic
against cross-flow
due to
unbalanced
line pressures
and
om the tailpieces.
Locate
the
inlet filter
screens
as required by the Water Supply (Water Fittings) p to the shoulder.
Regulations 1999.
sure the hot and cold water pipes have full
Assembly Procedure
the end of the pipe remains in contact with the filter
•
•
•
•
•
•
Unpack the main valve assembly and check that the bores are free of debris and the end sealing faces APPLICATION
are clean.
Unpack the two tailpieces and confirm they areThe
Pegler Yorkshire Model P405 thermostatic mixing valve has been
complete with union nuts and compression nuts
the requirements of BS 7942:2000 and NHS D08 and certified as com
and olives. APPLICATION
APPLICATION
Scheme and is
suitable for use in the designations shown in the table
Locate the sealing gaskets, insert them into the union
nuts
against the
faces of theModel
tailpieces
and
The Bulldog
TMV thermostatic
mixing
valveindependently
has
Valves
approved
formixing
designation
use
‘HP’
only:If a water st
The
Pegler
Yorkshire
P405
thermostatic
valve for
has
been
screw the union nuts onto the valve until a tight been
independently
tested
WRc-NSF
the of use are
supply and
pressure
should
be
verified
to by
ensure
theagainst
conditions
the
requirements
of
BS
7942:2000
NHS
D08
and
certified
as
complying
with the
seal has been made.
requirements of BS EN 1287 (Low Pressure-LP) and
Remove
the compression
nuts and olives
Scheme
and is suitable
forfrom
usethein the designations
shown
in
the
table
below.
BS EN 1111 (High Pressure-HP) and certified as
tailpieces. Locate the inlet filter screens and
complying with the requirements of the TMV2 Scheme
insert them into the bore of the tailpieces up to the and is suitable for use in the designations shown in
Valves
approved
for
designation
for
use ‘HP’ only:- If a water supply is fed by
shoulder.
the table (next page).
Table
2 –ensure
Required
set of
outlet
at com
Assemble
thepressure
valve to the pipework
the to
supply
shouldand
beensure
verified
themaximum
conditions
use temperatures
are appropriate
for
hot and cold water pipes have full penetration into Valves approved for designation for use ‘HP’ only:Application
Designation
the tailpiece.
If a water
supply is fed byMaximum
gravity thenSet
theMixed
supply
Water
Temperature
Tighten the compression nuts ensuring that the end pressure should be verified to ensure the conditions
of the pipe remains in contact with the filter
Bidet of use are
HP-B
appropriate for the valve. 38°C
element.
LP-B
Shower
41°C
Table 2 – Required maximum set
outlet HP-S
temperatures at commissioning.
Application
Designation
LP-S
HP-W
Maximum
Set Mixed
LP-W
7
Washbasin
Water Temperature
41°C
APPLICATION
The Pegler Yorkshire Model P405 thermostatic mixing valve has been independently tested by WRc-NSF
against the requirements of BS EN 1287 (Low Pressure-LP) and BS EN 1111 (High Pressure-HP) and
certified as complying with the requirements of the TMV2 Scheme and is suitable for use in the
designations shown in the table below.
•
Remove the plastic protective cap on top of the valve with
Table 5 – Recommended set mixed water
outlet temperatures
o using
reduc
temp
clock
Valves approved for designation for use ‘HP’ only:- If a water supply is fed by gravity then the
supply pressure should be verified to ensure the conditions of use are appropriate for the valve.
Table 5 – Recommended set mixed water outlet temperatures
Pressure
Application
Shower
Wash basin
Bidet
Bath (Tub)
15mm
HP
HP
HP
HP
22mm
HP and LP
HP and LP
HP and LP
HP
Maximum set mixed
water temperature
41°C
41°C
38°C
44°C
o increa
outle
clock
The above temperatures are recommended by the Thermostatic Mixing Valve (manufacturers) Association
as relevant settings for the varying applications shown. This is the maximum commissioning temperature
but valves may exceed this by 2°C in use.
The range of available temperature adjustment is 35°C to 48°C but
46°C is the maximum recommended mixed water temperature from a bath tap. The maximum temperature
takes account of the allowable temperature tolerances inherent in thermostatic mixing valves and temperature
losses in metal baths.
46°C is not a safe bathing temperature for adults or children.
The above temperatures are recommended by the
Thermostatic Mixing Valve (manufacturers) Association
as relevant settings for the varying applications
• using
a close
fitting
When
the valve
has
beenspanner,
installedreduce
with the
the correct
conditions o
shown. This is the maximum commissioning
mixed prior
outlettotemperature
by turningatclockwise.
the commissioning
the application tempe
temperature
but valves
exceed
this by
2°C
in use.
The British
Burns Association recommends
37°C may
to 37.5°C
as a comfortable
bathing
temperature
for children. to exercise
In premises covered by the Care Standards Act 2000, the maximum mixed water outlet temperature is 43°C.
• increase
the mixed
water
outlet
by to full hot at
through
the valve,
operate
the
valvetemperature
from full cold
COMMISSIONING (TMV 2)
turning counter clockwise.
The range of available temperature adjustment is
The valve35°C
must be to
commissioned
under46°C
normal site
conditions and after
establishing
48°C but
is system
the maximum
recommended
supply conditions with the hot and cold water supplies open, leave the system running to allow temperatures
When the valve has been installed with the correct
and pressures
to stabilise
and be
checked.
mixed
water
temperature
from a bath tap. The
conditions of use it is advised that the valve is
maximum
temperature
takes
of the
Prior to commencing
commissioning,
the following
checksaccount
should be carried
out. allowable
subjected to exercise prior to the commissioning at
temperature
inherent
inthethermostatic
• The
designation of thetolerances
thermostatic mixing
valve matches
application.
• The supply pressures and temperatures are within the operating range of the valve.
the application temperature. With hot and cold water
mixing
valves
and
temperature
losses
in
metal
baths.
• Isolating valves and strainers are provided.
flowing through the valve, operate the valve from full
46°C is not a safe bathing temperature for adults
If all these conditions are met, proceed to set the temperature as described below.
cold to full hot at least three times.
or children.
The Pegler Yorkshire P405 thermostatic mixing valve is supplied factory set at 43°C but the valve may be
simply adjusted after installation.
The set mixed water temperature at the terminal fitting must never exceed 46°C
•
With the valve at the full cold position bring the valve
to the correct application temperature by turning the
spanner counter clockwise. If the valve overshoots this
temperature, return the valve to the full cold
condition, and reset it to the correct temperature
+0-2°C. Do not set a valve on a lowered temperature
as this will not provide consistent operation.
The British Burns Association recommends 37°C to
37.5°C as a comfortable bathing temperature for
children. In premises covered by the Care Standards
Act 2000, the maximum mixed water outlet
temperature is 43°C.
Remove the plastic protective cap on top of the valve with the supplied Allen key or other suitable
tool.
COMMISSIONING (TMV 2)
The valve must be commissioned under normal site
system conditions and after establishing supply
conditions with the hot and cold water supplies open,
leave the system running to allow temperatures and
pressures to stabilise and be checked.
When the valve is set to the required temperature for
the application carry out 5 cold water isolation tests
to further exercise the valve.
•
Prior to commencing commissioning, the following
checks should be carried out.
•
•
•
The designation of the thermostatic mixing valve matches the application.
The supply pressures and temperatures are within the operating range of the valve.
Isolating valves and strainers are provided.
If all these conditions are met, proceed to set the temperature as described below.
Set the mixed water temperature to the required value. It is advisable to use a calibrated digital
thermometer for checking the inlet and outlet temperatures.
• Measure and record the temperature of the hot and cold water supplies at the inlets to the valve.
• Measure and record the temperature of the water discharging from the valve at the greatest draw-off
flow rate.
• In the absence of other temperatures being specified those detailed in Table 5 are the desired settings.
The Bulldog TMV thermostatic mixing valve is supplied
factory set at 43°C but the valve may be simply
adjusted after installation.
The set mixed water temperature at the terminal
fitting must never exceed 46°C
Once the required mixed outlet temperature has been
achieved, isolate the cold water supply and monitor
and record the mixed water temperature including the
maximum and final temperatures achieved. The mixed
water temperature should never exceed 46°C.
• Remove the plastic protective cap on top of the valve with the supplied Allen key or other suitable
tool.
8
Isolate the cold water supply and RECORD the
maximum temperature achieved. After 5 seconds, if
water is still flowing RECORD the temperature of the
flow. Restore the cold water supply and RECORD the
stabilised mixed water outlet temperature.
After correct commissioning secure the protective cap
using the supplied screw. The Bulldog TMV is supplied
with two protective caps. One blue TMV 3 cap and one
white TMV 2 cap. Ensure that the white colour TMV 2
cap is fitted as this will indicate the valve has been
commissioned to the TMV 2 standard.
•
If there is no significant change to the stabilised set outlet temperature (±2°C or less deviation from the original setting) and the fail safe shut-off is functioning, then the valve is working correctly and no further service work is required.
• If the maximum mixed water temperature exceeds the previous test results by more than 2°C then the
need for service work on the valve is indicated.
• The equipment used in these In-Service Tests should be RECORDED and should preferably be the same as that used at installation.
Note:
Record all the equipment used during commissioning.
If there is a residual flow during the commissioning
or the annual verification (cold water supply isolation
test) then this is acceptable providing the temperature
of the water seeping from the valve is no more than
2°C above the designated maximum mixed water
outlet temperature setting of the valve (See Table 5).
In Service testing (TMV 2)
The Bulldog TMV thermostatic mixing valve will
provide satisfactory service and a high level of
protection, provided it is maintained and subjected
to In-Service Testing.
Temperature readings should be taken at the normal
flow rate after allowing the system to stabilise. The
sensing part of the thermometer probe must be fully
submerged in the water that is to be tested. Any TMV
that has been adjusted or serviced must be
re-commissioned and re-tested in accordance with the
manufacturer’s instructions.
Approximately 6-8 weeks after commissioning, the
following tests should be undertaken.
•
•
•
Check the temperature of the hot and cold water supplies - RECORD
Check the temperature of the mixed water
temperature at the greatest draw off flow rate – RECORD
Check there have been no significant changes in inlet supply temperatures and pressures since
commissioning or the previous in service test.
If significant changes have occurred it is
recommended to re-commission the valve.
In the absence of any other instruction or guidance,
it is recommended that In-Service Tests are carried
out once every 12 months as a minimum. If the
temperature is outside of the expected range it will be
necessary to remove and clean the valve in accordance
with the following instructions.
TMV Cleaning and Servicing Instructions
(TMV 2 & TMV 3)
If the mixed water temperature has significantly
changed from that measured at installation
(e.g. > 1°C), RECORD the change and before making
any adjustments to the valve confirm that:-
Most domestic water supplies contain calcium which
will separate out when the water is heated in a
system. The degree and speed of scaling may vary
depending on factors such as water flow rates,
system design, the hardness of the water and the
temperature to which the water is heated.
Deposits of scale may over time form in the valve,
particularly at the hot inlet. The formation of the
scale may adversely affect the performance of the
valve which will be detected during the in-service
testing. If this occurs it will be necessary to remove
the valve for de-scaling and servicing.
• Strainer elements in the hot and cold water supplies
are clean and undamaged.
• Non-return valves are clean and operating correctly.
• Isolation valves are operating correctly and are set in the fully open position.
If the mixed water temperature is acceptable, the
following additional observations should be made:9
• Isolate the hot and cold supply.
A-1
• Remove the valve to a clean working area.
• Remove the protective cap.
• Unscrew the headwork of the valve.
• Carefully remove the element and valve assembly and put to one side.
A-2
• Remove the main spring and flow guide and pipe assembly
carefully put to one side.
• Inspect the components for contamination or damage.
• Clean or replace as necessary
• Remove the two o rings
• Clean the valve body and headwork using a propriety de-scaler
• Thoroughly rinse the body and headwork in clean water.
• Carefully fit new o rings from the service kit taking care to ensure they are not damaged and are Spare part order
code
Description
Spare part
order code
Description
Strainer
CC85077
A-1 854550
Blue
TMV
3 Protective
P405UA
mixinglocated.
valve is optionally provided with
angled
assemblies
inTailpiece
lieu
ofkitkit cap complete with screw
D
correctly
E
AngleTMV
valve 2
Strainer
CC85078
A-2 854551
White
Protective
cap complete with screw
B
854447
Hexagon key
• Lubricate
the allows
o rings with
theconnections
lubricant provided.
B
854447
Hexagon
key
hown above.
This
the
of the
hot
and
cold
water
supplies
to
C
854454
Service kit
C
854454
D
854449 (15mm), 854450 (22mm)Service kit
• Re-fit the flow guide and spring lubricating the
E (15mm),
854451 (15mm),
(22mm)
D
854449
854450854452
(22mm)
Tailpiece Strainer kit
ter outlet
forguide
ease
of piping
layouts.
angled
assemblies
incorporate
F
854456 (15mm), 854457 (22mm) Sealing washer
flow
around
the greatest
diameterThe
with the
E valve
854451
(15mm),
854452 (22mm) Angle valve strainer kit
G
854455 (15mm), 817012 (22mm)
F
854456 (15mm), 854457 (22mm) Sealing washer
olation valves
test points
lubricantand
provided
G
854455 (15mm), 817012 (22mm) Wafer Strainer
• Lubricate the shuttle valve with the lubricant For genuine spares and technical assistance contact: provided
Pegler Yorkshire
• Re-fit the shuttle valve and element assembly.
St Catherine’s Avenue
• Re-fit the headwork ensuring correct tightening Doncaster
South Yorkshire
•
Re-fit
the
valve
assembly
n integral full bore ball valve and in-line strainer
DN4 8DF in an angled housing. When
• If after cleaning the valve, and replacing the o ring 01302
560560
he requirements
for does
isolation
valves
anditY-strainers
previously
mentioned are
seals, the valve
not function
correctly,
may Tel:
Fax:
01302 560206
be necessary to replace the thermal element.
Exploded view of TMV assembly
lve assembly
Spares
thermostatic
mixing
valve
has been
independently tested by WRc-NSF against
In order to
ensure that
the Bulldog
TMV mixing
valve continues
to provide
satisfactory
service, only with the requirements of the TMV3
0 and NHS
D08 and
certified
as complying
GENUINE Pegler Yorkshire spare parts must be used.
the designations shown in the table below.
10
on for use ‘HP’ only:- If a water supply is fed by gravity then the
Technical Help
Free Phone: 0800 156 0050
Free Fax:
0808 156 1012
Email:
[email protected]
Pegler Yorkshire Group Limited
St. Catherine’s Avenue, Doncaster,
South Yorkshire, DN4 8DF, England.
Tel: 0844 243 4400 Fax: 0844 243 9870