Download INSTALLATION AND OPERATING INSTRUCTIONS FOR
Transcript
Notes Operation If there is a residual flow during the commissioning or the annual verification (cold water supply isolation test), then this is acceptable providing the temperature of the water seeping o from the valve is no more than 2 C above the designated maximum mixed water outlet temperature setting of the valve. The unit has a single control lever that turns the unit on and off and adjusts the temperature. Turning the handle anti clockwise from the off position firstly gives cold water flow then increases the temperature to the maximum set value. Temperature readings should be taken at the normal flow rate after allowing for the system to stabilise. Maintenance The sensing part of the thermometer probe must be fully submerged in the water that is to be tested. This product is designed to be easily serviced, it has integral isolation, integral hot water flushing to pasteurise the mixed water chambers reducing the incidence bio film growth and unions that allow the complete body to be removed for servicing in the workshop. Any TMV that has been adjusted or serviced must be re-commissioned and re-tested in accordance with the manufacturers' instructions. The installation of thermostatic mixing valves must comply with the requirements of the Water Supply (Water Fittings) Regulations 1999. Specifications Minimum pressure drop through fitting for mixing Dynamic pressure drop through fitting for mixing Maximum static pressure to be applied to fitting Maximum pressure loss ratio Temperature stability with normal variation of supply temperatures and pressures Factory standard blend temperature Maximum hot supply temperature 0.1 bar 5 bar 10 bar 20:1 either supply Isolating and removal of the valve Using Fig.3 & 4 as a reference (page 6) The valve has integral isolation this is accessed by unscrewing the shroud (54) and pulling it back along the elbow taking care not to scratch the chrome, the 2.5mm hexagon wrench is inserted in the isolating plug and rotating it clockwise until it locks. The securing nut (52) is then removed whilst supporting the valve to stop it falling and damaging the surface below it. The valve can then be replaced or serviced as is most convenient. The valve is replaced by reversing the above procedure ensuring the Oring is undamaged and in place. Cleaning integral filters The integral filters are fitted into the inlet elbows to the fitting. The fitting should be removed from the bases as described in the previous section the filters are then accessible for servicing as shown in Fig3. They are a friction fit into the adaptors and should be care fully prizes out washed and refitted. Failure to refit the filters may invalidate the guarantee. ± 2°C from set temperature 43°C 80°C The sensitive wax capsule will shut down the operation of the valve if either the hot or cold water supply fails, provided a minimum differential of 10°C exists between the mixed water temperature and the remaining supply. FLOW RATES The flow rates (L/min) for the tap with and without flow limiters are quoted in the table below Pressure Drop Bar Low Pressure Flow Rate without Limiters High Pressure Flow Rate with limiters (Grey 6l Hot side & Yellow 10l cold Side) High Pressure that conforms to BREEAM flow rate for Basin Mixers < 6.0l/min at 3.0 Bar Flow Rate with limiters (Lime Green 2.75l Hot side & Yellow 10l cold Side) Supplied Factory Fitted 0.1 0.2 0.4 0.6 4.0 5.8 8.0 10.0 11.6 0.8 1.0 1.5 2.0 3.0 4.0 5.0 Not recommended, use flow regulators as below. Use Low Pressure Setup 8.5 9 9.3 9 9 9 Use Low Pressure Setup 4 4.3 4.6 4.9 4.8 4.8 5 10 For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - [email protected]