Transcript
+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 75 Monday, October 5, 2009 2:09 PM [A02] Error Temperature rise and error short circuit Start (TWI,TWO,THO 70°C) TWI, TWO, and THO sensor characteristics are correct No Replace TWI, TWO, and THO sensors Yes Flow switch is normal No Replace flow switch Yes Water outlet temperature is 70°C or higher No Yes Hot water from boiler or other circuits does not come in Yes Correct water circuit (To prevent hot water of other circuits from entering) Yes Failure of backup heater (Too large heater input, thermostat short circuit) No Backup heater is energized (Measure heater current) No Replace water heat exchange control board Replace heater unit 75 Toshiba